background image

Many  compressor  failures  are  caused  by  the  following  

conditions: 
1.    Improper air flow over the evaporator. 

2.    Overcharged refrigerant system causing liquid to be 

returned to the compressor. 

3.    Restricted refrigerant system. 

4.    Lack of lubrication. 

5.     Liquid refrigerant returning to compressor causing oil 

to be washed out of bearings. 

6.    Noncondensables  such  as  air  and  moisture  in 

 

          the  system.  Moisture  is  extremely  destructive  to  a 

        refrigerant system. 

Single Phase Resistance Test

 

Remove the leads from the compressor terminals and set  

the ohmmeter on the lowest scale (R x 1). 

Touch the leads of the ohmmeter from terminals common  

to start (“C” to “S”). Next, touch the leads of the ohmmeter  

from terminals common to run (“C” to “R”).

Add  values  “C”  to  “S”  and  “C”  to  “R”  together  and 

check resistance from start to run terminals (“S” to “R”).  

Resistance “S” to “R” should equal the total of “C” to “S” 

and “C” to “R.”  

In  a  single  phase  PSC  compressor  motor,  the  highest  

value will be from the start to the run connections (“S” to  

“R”). The next highest resistance is from the start to the  

common connections (“S” to “C”). The lowest resistance  

is from the run to common. (“C” to “R”) Before replacing a 

compressor, check to be sure it is defective. 

Check the complete electrical system to the compressor 

and  compressor  internal  electrical  system,  check  to  be 

certain that compressor is not out on internal overload. 

Complete  evaluation  of  the  system  must  be  made 

when  ever  you  suspect  the  compressor  is  defective. 

If  the  compressor  has  been  operating  for  sometime,  a 

careful

 

examination must be made to determine why the 

compressor failed.  

19

Recommended procedure for compressor  

replacement

 

1.    Be  certain  to  perform  all  necessary  electrical  and 

refrigeration  tests  to  be  sure  the  compressor  is 

actually defective before replacing. 

2.    Recover  all  refrigerant  from  the  system  though 

the  process  tubes. 

PROPER  HANDLING  OF 

RECOVERED  REFRIGERANT  ACCORDING  TO 

EPA  REGULATIONS  IS  REQUIRED. 

  Do  not  use 

gauge  manifold  for  this  purpose  if  there  has  been 

a  burnout.  You  will  contaminate  your  manifold  and 

hoses.  Use  a  Schrader  valve  adapter  and  copper 

tubing for burnout failures.

Unplug and/or disconnect all electrical power 

to the unit before performing inspections, 

maintenances or service.  

 

Failure to do so could result in electric shock, 

serious injury or death.

WARNING

RISK OF ELECTRIC SHOCK 

Sealed Refrigeration System contains refrigerant 

and oil under high pressure.

Proper safety procedures must be followed, 

and proper protective clothing must be worn 

when working with refrigerants.

Failure  to  follow  these  procedures  could 

result in serious injury or death. 

WARNING

HIGH PRESSURE HAZARD 

Extreme care, proper judgment and all safety 

procedures  must  be  followed  when  testing, 

troubleshooting, handling or working around 

unit while in operation with high temperature 

components.  Wear  protective  safety  aids 

such as: gloves, clothing etc. 

Failure to do so could result in serious burn 

injury.

WARNING

HIGH TEMPERATURES 

The  use  of  a  torch  requires  extreme  care  and  proper 

judgment.  Follow  all  safety  recommended  precautions 

and  protect  surrounding  areas  with  fire  proof  materials. 

Have a fire extinguisher readily available. Failure to follow 

this  notice  could  result  in  moderate  to  serious  property 

damage.

NOTICE

FIRE HAZARD 

COMPReSSOR RePLACeMeNT

Summary of Contents for 2010 HAZARDGARD SH15M30A

Page 1: ...R 410A Models Service Manual 2 0 1 0 HG ServMan 4 10 SH15M30A SH20M30A Cool Only Hazardous Duty Room Air Conditioner...

Page 2: ...ard Special Features 9 Component Definitions 10 Component Testing 11 12 R 410A Sealed System Repair Considerations 13 Sealed Refrigeration System Repairs 14 17 Refrigerant Charging 14 17 Compressor Ch...

Page 3: ...sistant if possible Capacitors even when disconnected from the electrical power source retain an electrical charge potential capable of causing electric shock or electrocution Handle discharge and tes...

Page 4: ...contact with liquid refrigerant can result in minor to moderate injury Be extremely careful when using an oxy acetylene torch Direct contact with the torch s flame or hot surfaces can cause serious b...

Page 5: ...the outside to allow water to drain from the unit Do not drill holes in the bottom of the drain pan or the underside of the unit Failure to follow these instructions can result in result in damage to...

Page 6: ...g L Nov C Mar F Jun J Sept M Dec 1st Digit Function S Straight Cool Value Series H HazardGard 3rd and 4th Digit Approximate BTU HR Cooling Heating BTU Hr capacity listed in the Specifi cation Performa...

Page 7: ...obust engineering with design details like 33 thicker fins extend the life of the coil Diamonblue Technology our anti corrosive treatment provides added endurance and protection in coastal or corrosiv...

Page 8: ...acteristics 60 Hertz Energy Efficiency Ratio AHAM Moisture Removal Air Direction Controls Room Side Air Circulation BTU Hr AHAM Volts Rated Amps AHAM Watts EER Pints Hr CFM SH15M30A 14500 14000 230 20...

Page 9: ...FPA 70 ARTICLE 501 THE FIELD PROVIDED CIRCUIT PROTECTION DEVICE HACR CIRCUIT BREAKER OR TIME DELAY FUSE MUST NOT EXCEED THE AMPACITY INDICATED ON THE PRODUCT NAMEPLATE IMPORTANT Before you begin the a...

Page 10: ...15 amp circuit with time delay fuse required Accommodates direct wiring Long lasting 3 8 10mm thick air filter germicidally treated easily removed for cleaning Friedrich Air Conditioning quality has b...

Page 11: ...ng diagrams and schematics in the back of this service manual Solid State Relay Used to energize the compressor and fan motor Each unit has 2 50 amp 208 230 volt relays Capacitor Reduces line current...

Page 12: ...n or shorted It will tell whether the capacitor is within its micro farads rating and it will show whether the capacitor is operating at the proper power factor percentage The instrument will automati...

Page 13: ...valve to open and bypass hot gas from the high pressure side to the low pressure side of the system The hot gas entering the compressor mixes with the cool gas returned through the suction line thus...

Page 14: ...410A equipment To prevent moisture absorption and lubricant contamination do not leave the refrigeration system open to the atmosphere longer than 1 hour Weigh in the refrigerant charge into the high...

Page 15: ...failure SealedRefrigerationSystemcontainsrefrigerant and oil under high pressure Proper safety procedures must be followed and proper protective clothing must be worn when working with refrigerants F...

Page 16: ...EZE HAZARD Proper safety procedures must be followed and proper protective clothing must be worn when working with a torch Failure to follow these procedures could result in moderate or serious injury...

Page 17: ...evaporator will not be encountered because the refrigerant will boil later if at all Gauges connected to system will usually have higher head pressure depending upon amount of over charge Suction pres...

Page 18: ...a partial restriction there may be gurgling sounds at the metering device entrance to the evaporator The evaporator in a partial restriction could be partially frosted or have an ice ball close to th...

Page 19: ...exists mechanically or electrically Single Phase Running and L R A Test NOTE Consult the specification and performance section for running amperage The L R A can also be found on the rating plate Sel...

Page 20: ...to determine why the compressor failed 19 Recommended procedure for compressor replacement 1 Be certain to perform all necessary electrical and refrigeration tests to be sure the compressor is actuall...

Page 21: ...ent The use of nitrogen requires a pressure regulator Follow all safety procedures and wear protective safety clothing etc Failure to follow proper safety procedures result in serious injury or death...

Page 22: ...ems Allow all items to dry thoroughly before reinstalling them ELECTRONIC ELECTRICAL MECHANICAL Periodically at least yearly or bi yearly inspect all control components electronic electrical and mecha...

Page 23: ...stem periodically at least yearly or bi yearly and clean of all obstructions and debris Clean both areas with an antibacterial and antifungal cleaner Rinse both items thoroughly with water and ensure...

Page 24: ...AMPS AMPS RUNNING AMPERAGE DRAW AMPS INDOOR TEMPERATURES INDOOR AMBIENT TEMPERATURE F RELATIVE HUMIDITY RH INDOOR COOL HEAT DISCHARGE AIR TEMPERATURE INDOOR F F RETURN AIR TEMPERATURE INDOOR F F OUTD...

Page 25: ...perative Problem Possible Cause Compressor runs continually Does not cycle off Excessive heat load Test cooling performance of unit Unit undersized Restriction in line Check for partially iced coil Ch...

Page 26: ...vide proper voltage Switch On Off inoperative Test for continuity Defective capacitor Test with analyzer replace if needed Compressor internal overload open Check voltage at compressor terminals If vo...

Page 27: ...r blower wheel housing Adjust fan blade or blower wheel clearance Compressor vibrating Check for deteriorated compressor grommets Replace as needed Loose cabinet parts improperly mounted components tu...

Page 28: ...ELECTROMECHANICAL CONTROL COOL ONLY MODELS SH15M30 A SH20M30 A 27...

Page 29: ...Room Air Conditioner that has been subject to a accident misuse flood fire or neglect b repairs or alterations outside of the Friedrich Authorized Dealer or Service Center so as to affect adversely it...

Page 30: ...ox 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 877 599 5665 x 846 FAX 210 357 4490 Email tac friedrich com www friedrich com Printed in the U S...

Page 31: ......

Page 32: ...n 4 10 FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in...

Reviews: