Undercharged Refrigerant Systems

 

An undercharged system will result in poor performance 

(low  pressures,  etc.)  in  both  the  heating  and  cooling 

cycle. 

Whenever  you  service  a  unit  with  an  undercharge  of 

refrigerant,  always  suspect  a  leak.  The  leak  must  be 

repaired before charging the unit. 

To  check  for  an  undercharged  system,  turn  the  unit  on, 

allow  the  compressor  to  run  long  enough  to  establish 

working pressures in the system (15 to 20 minutes). 
During the cooling cycle you can listen carefully at the exit 

of the metering device into the evaporator; an intermittent  

hissing  and  gurgling  sound  indicates  a  low  refrigerant 

charge. Intermittent frosting and thawing of the evaporator 

is  another  indication  of  a  low  charge,  however,  frosting 

and  thawing  can  also  be  caused  by  insufficient  air  over 

the evaporator. 
Checks for an undercharged system can be made at 

the compressor. If the compressor seems quieter than 

normal, it is an indication of a low refrigerant charge. 

 

Overcharged Refrigerant Systems

A  check  of  the  amperage  drawn  by  the  compressor 

motor  should  show  a    lower  reading.  (Check  the  Unit 

Specification.)    After  the  unit  has  run  10  to  15  minutes, 

check the gauge pressures. Gauges connected to system 

with  an  undercharge  will    have  low  head  pressures  and 

substantially low suction  pressures.  

of  the  evaporator  will  not  be  encountered  because  the 

refrigerant  will  boil  later  if  at  all.  Gauges  connected  to 

system will usually have higher head pressure (depending 

upon amount of over charge). Suction pressure should be 

slightly higher. 

Compressor  amps  will  be  near  normal  or  higher. 

Noncondensables  can  also  cause  these  symptoms.  To 

confirm, remove some of the charge, if conditions improve, 

system may be overcharged. If conditions don’t improve, 

Noncondensables are indicated. 
Whenever  an  overcharged  system  is  indicated,  always 

make  sure  that  the  problem  is  not  caused  by  air  flow 

problems. Improper air flow over the evaporator coil may 

indicate some of the same symptoms as an over charged 

system. 

An overcharge can cause the compressor to fail, since it  

would be “slugged” with liquid refrigerant. 

The charge for any system is critical. When the compressor 

is noisy, suspect an overcharge, when you are sure that 

the air quantity over the evaporator coil is correct. Icing   

ELECTRIC SHOCK HAZARD 

WARNING

Turn  off  electric  power  before  service  or 

installation.

Extreme  care  must  be  used,  if  it  becomes 

necessary  to  work  on  equipment  with  power 

applied.

Failure to do so could result in serious injury or

 

death.

Sealed Refrigeration System contains refrigerant 

and oil under high pressure.

Proper safety procedures must be followed, 

and proper protective clothing must be worn 

when working with refrigerants.

Failure to follow these procedures could 

result in serious injury or death. 

WARNING

HIGH PRESSURE HAZARD 

16

Summary of Contents for 2010 HAZARDGARD SH15M30A

Page 1: ...R 410A Models Service Manual 2 0 1 0 HG ServMan 4 10 SH15M30A SH20M30A Cool Only Hazardous Duty Room Air Conditioner...

Page 2: ...ard Special Features 9 Component Definitions 10 Component Testing 11 12 R 410A Sealed System Repair Considerations 13 Sealed Refrigeration System Repairs 14 17 Refrigerant Charging 14 17 Compressor Ch...

Page 3: ...sistant if possible Capacitors even when disconnected from the electrical power source retain an electrical charge potential capable of causing electric shock or electrocution Handle discharge and tes...

Page 4: ...contact with liquid refrigerant can result in minor to moderate injury Be extremely careful when using an oxy acetylene torch Direct contact with the torch s flame or hot surfaces can cause serious b...

Page 5: ...the outside to allow water to drain from the unit Do not drill holes in the bottom of the drain pan or the underside of the unit Failure to follow these instructions can result in result in damage to...

Page 6: ...g L Nov C Mar F Jun J Sept M Dec 1st Digit Function S Straight Cool Value Series H HazardGard 3rd and 4th Digit Approximate BTU HR Cooling Heating BTU Hr capacity listed in the Specifi cation Performa...

Page 7: ...obust engineering with design details like 33 thicker fins extend the life of the coil Diamonblue Technology our anti corrosive treatment provides added endurance and protection in coastal or corrosiv...

Page 8: ...acteristics 60 Hertz Energy Efficiency Ratio AHAM Moisture Removal Air Direction Controls Room Side Air Circulation BTU Hr AHAM Volts Rated Amps AHAM Watts EER Pints Hr CFM SH15M30A 14500 14000 230 20...

Page 9: ...FPA 70 ARTICLE 501 THE FIELD PROVIDED CIRCUIT PROTECTION DEVICE HACR CIRCUIT BREAKER OR TIME DELAY FUSE MUST NOT EXCEED THE AMPACITY INDICATED ON THE PRODUCT NAMEPLATE IMPORTANT Before you begin the a...

Page 10: ...15 amp circuit with time delay fuse required Accommodates direct wiring Long lasting 3 8 10mm thick air filter germicidally treated easily removed for cleaning Friedrich Air Conditioning quality has b...

Page 11: ...ng diagrams and schematics in the back of this service manual Solid State Relay Used to energize the compressor and fan motor Each unit has 2 50 amp 208 230 volt relays Capacitor Reduces line current...

Page 12: ...n or shorted It will tell whether the capacitor is within its micro farads rating and it will show whether the capacitor is operating at the proper power factor percentage The instrument will automati...

Page 13: ...valve to open and bypass hot gas from the high pressure side to the low pressure side of the system The hot gas entering the compressor mixes with the cool gas returned through the suction line thus...

Page 14: ...410A equipment To prevent moisture absorption and lubricant contamination do not leave the refrigeration system open to the atmosphere longer than 1 hour Weigh in the refrigerant charge into the high...

Page 15: ...failure SealedRefrigerationSystemcontainsrefrigerant and oil under high pressure Proper safety procedures must be followed and proper protective clothing must be worn when working with refrigerants F...

Page 16: ...EZE HAZARD Proper safety procedures must be followed and proper protective clothing must be worn when working with a torch Failure to follow these procedures could result in moderate or serious injury...

Page 17: ...evaporator will not be encountered because the refrigerant will boil later if at all Gauges connected to system will usually have higher head pressure depending upon amount of over charge Suction pres...

Page 18: ...a partial restriction there may be gurgling sounds at the metering device entrance to the evaporator The evaporator in a partial restriction could be partially frosted or have an ice ball close to th...

Page 19: ...exists mechanically or electrically Single Phase Running and L R A Test NOTE Consult the specification and performance section for running amperage The L R A can also be found on the rating plate Sel...

Page 20: ...to determine why the compressor failed 19 Recommended procedure for compressor replacement 1 Be certain to perform all necessary electrical and refrigeration tests to be sure the compressor is actuall...

Page 21: ...ent The use of nitrogen requires a pressure regulator Follow all safety procedures and wear protective safety clothing etc Failure to follow proper safety procedures result in serious injury or death...

Page 22: ...ems Allow all items to dry thoroughly before reinstalling them ELECTRONIC ELECTRICAL MECHANICAL Periodically at least yearly or bi yearly inspect all control components electronic electrical and mecha...

Page 23: ...stem periodically at least yearly or bi yearly and clean of all obstructions and debris Clean both areas with an antibacterial and antifungal cleaner Rinse both items thoroughly with water and ensure...

Page 24: ...AMPS AMPS RUNNING AMPERAGE DRAW AMPS INDOOR TEMPERATURES INDOOR AMBIENT TEMPERATURE F RELATIVE HUMIDITY RH INDOOR COOL HEAT DISCHARGE AIR TEMPERATURE INDOOR F F RETURN AIR TEMPERATURE INDOOR F F OUTD...

Page 25: ...perative Problem Possible Cause Compressor runs continually Does not cycle off Excessive heat load Test cooling performance of unit Unit undersized Restriction in line Check for partially iced coil Ch...

Page 26: ...vide proper voltage Switch On Off inoperative Test for continuity Defective capacitor Test with analyzer replace if needed Compressor internal overload open Check voltage at compressor terminals If vo...

Page 27: ...r blower wheel housing Adjust fan blade or blower wheel clearance Compressor vibrating Check for deteriorated compressor grommets Replace as needed Loose cabinet parts improperly mounted components tu...

Page 28: ...ELECTROMECHANICAL CONTROL COOL ONLY MODELS SH15M30 A SH20M30 A 27...

Page 29: ...Room Air Conditioner that has been subject to a accident misuse flood fire or neglect b repairs or alterations outside of the Friedrich Authorized Dealer or Service Center so as to affect adversely it...

Page 30: ...ox 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 877 599 5665 x 846 FAX 210 357 4490 Email tac friedrich com www friedrich com Printed in the U S...

Page 31: ......

Page 32: ...n 4 10 FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in...

Reviews: