Type
Output*
7
[kW]
Airflow*
3
[m
3
/h]
∆
t*
5,7
[°C]
Water
volume
[l]
Sound
level*
4
[dB(A)]
Motor
[W]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
Weight
[kg]
ADCS17WL*¹
20
1500/3200
23/18
2,8
43/61
890
230V~
3,9
1700
85
ADCS22WL
29
2100/4400
24/19
3,6
44/62
1230
230V~
5,4
2200
110
ADCS25WL*²
33
2400/5000
24/19
4,0
45/63
1420
230V~
6,2
2450
125
*
1
) Available only for horizontal mounting.
*
2
) Available only for vertical mounting.
*
3
) Lowest/highest airflow of totally 5 fan steps.
*
4
) Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m². At
lowest/highest airflow.
*
5
)
∆
t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*
6
) Applicable at water temperature 80/60 °C, air temperature, in +18 °C.
*
7
) Applicable at water temperature 60/40 °C, air temperature, in +18 °C.
Protection class: IP20.
CE compliant.
Type
Output*
6
[kW]
Airflow*
3
[m
3
/h]
∆
t*
5,6
[°C]
Water
volume
[l]
Sound
level*
4
[dB(A)]
Motor
[W]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
Weight
[kg]
ADCS17WH*¹
26
1500/3200
31/24
2,8
43/61
890
230V~
3,9
1700
85
ADCS22WH
35
2100/4400
30/23
3,6
44/62
1230
230V~
5,4
2200
110
ADCS25WH*²
41
2400/5000
31/24
4,0
45/63
1420
230V~
6,2
2450
125
Technical specifications
2
Water heat - ADCS WH, coil for high temperature water (
≥
80 °C) (IP20)
2
Water heat - ADCS WL, coil for low water temperature (
<
80 °C) (IP20)
Summary of Contents for Thermozone AD Corinte W ADCS17WH
Page 1: ...AD Corinte W ADCS 16 SE 46 IT 28 RU 22 NO 25 FR 34 NL 37 ES 43 FI 19 GB 40 PL 31 DE 49 DK ...
Page 3: ...AD Corinte W ADCS 3 1 2 80 60 1 2 60 80 3 Ø22 Cu PH2 1 4 Fig 2 Fig 3 Ø22 Cu 2200 2450 500 350 ...
Page 4: ...AD Corinte W ADCS 4 1 2 3 4 5 6 7 8 9 10 A B C Fig 4 ...
Page 5: ...AD Corinte W ADCS 5 Fig 5 ...
Page 7: ...AD Corinte W ADCS 7 Fig 6c Fig 6d 360 243 Ø22 Ø10 15 5 10 Fig 7 80 35 ø12 180 35 25 40 ...