Arden 4200

17

EN

Type 

Output Voltage  Minimum 

area*

Control 

Start-up (E) 

When the unit is used for the first time or after 

a long period of non-use, smoke or an odour 

may result from dust or dirt which has collected 

on the element. This is completely normal and 

disappears after a short time. 

 

*

1

) 2 m and 2.5 m units can be connected with two 

power supplies. The 2.5 m unit has electric coils with two 

different outputs, and the coil to the left, on the horizontal 

unit, viewed from inside the premises, has the highest 

output.  

*) Dimensioning of external wiring shall comply with 

applicable regulations and local deviations may occur. 

Connecting the water coil (W) 

The installation must be carried out by an 

authorised installer. 

The water coil has copper tubes with 

aluminium fins and is suitable for connection 

to a closed water heating system. The heating 

coil must not be connected to a mains pressure 

water system or an open water system. 

Note that the unit shall be preceded by a 

regulating valve, see Frico valve kit.  

To access the connections the service hatch and 

intake grille must be opened. The water coil 

is connected via connections with dimensions 

DN20 (3/4’’), inside thread, inside the unit. 

Knockouts are placed on the top and the side of 

the unit. Hoses are mounted via cable glands at 

knockouts to protect the hose and prevent air 

leakage. See Fig. 6. Flexible hoses are available 

as accessories.  

Note! If you want to divide the output 

between two connection points, the series 

cabling must first be removed (ARFEC4220/25, 

2x400V3~). See wiring diagrams. 

 The largest cable diameter for the terminal 

block is 16 mm². The cable glands used must 

meet the protection class requirements. In the 

distribution board, it is to be indicated that ”the 

air curtains can be supplied from more than 

one connection”. 

Adjustment of the air curtain and airflow 

The direction and speed of the airflow should 

be adjusted considering the load on the 

opening. Pressure forces affect the airstream 

and force it inwards towards the premises 

(when the premises are heated and the 

outdoor air is cold).

The airstream should, therefore, be directed 

outwards to withstand the load. Generally 

speaking, the higher the load, the greater the 

angle required.

  

Basic setting fan speed 

The fan speed when the door is open is 

set using the control. Note that the airflow 

direction and the fan speed may need fine 

adjustment depending on the loading of the 

door.

  

Filter (W) 

The water coil is protected against dirt and 

blockage by an internal air filter which covers 

the coil face. 

Service, repairs and maintenance  

For all service, repair and maintenance first 

carry out the following:  

1. Disconnect the power supply. 

2. The service hatch is opened by loosening the 

snap fixings located on the bottom of the unit 

(turn 90°). See Fig. 3.

3. After service, repairs and maintenance close 

the service hatch and make sure that the 

snap fixings lock securely. 

NOTE: Care must be taken when 

connecting the pipes. Use a pipe 

wrench or a similar tool to grip the air curtain 

connections to prevent straining of the 

pipes and subsequent water leakage during 

connection to the water supply pipe-work. 

The connections to the heating coil must be 

equipped with shut off valves to allow trouble-

free removal.  

Water coil is equipped with a drain and a vent 

valve. 

Maintenance 

 Since fan motors and other components are 

maintenance-free, no maintenance other than 

cleaning is necessary. The level of cleaning can 

vary depending on local conditions. Undertake 

cleaning at least twice a year. Inlet and exhaust 

grilles, impeller and elements can be vacuum 

cleaned or wiped using a damp cloth. Use a 

Summary of Contents for Arden 4200

Page 1: ...Original instructions Arden 4200 16 EN 20 SE 25 NO 30 FR 35 DE 41 NL 46 ES 51 IT 56 PL 61 RU 67 FI DK 72...

Page 2: ...ten DE Le pagine introduttive contengono prevalentemente immagini Per le traduzioni dei testi scritti in inglese vedere le pagine nelle diverse lingue IT Pocz tkowe strony zawieraj g wnie rysunki T um...

Page 3: ...mm B mm ARFEC4210 1067 1020 ARFEC4215 1577 1520 ARFEC4220 2067 2020 ARFEC4225 2579 2520 Arden 4200 3 B A 1 m 4 x M8 1 5 m 4 x M8 2 m 6 x M8 2 5 m 6 8 x M8 803 851 851 296 53 90 218 29 29 71 56 218 29...

Page 4: ...884 851 71 56 218 1400 851 851 851 945 1198 1198 945 29 29 Arden 4200 4 Mounting on threaded bars outside the unit ARFEC4215 ARFEC4210 Top view ARFEC4220 ARFEC4225...

Page 5: ...Arden 4200 5 Fig 1b Mounting on threaded bars outside the unit Mounting on threaded bars outside the unit Fig 1a Mounting brackets on delivery ARFEC4220 ARFEC4225...

Page 6: ...56 430 56 430 56 291 291 994 411 368 754 666 666 484 218 71 56 291 292 828 339 828 742 742 397 723 340 723 29 29 Arden 4200 6 Mounting on threaded bars inside the unit ARFEC4215 ARFEC4210 Top view AR...

Page 7: ...Arden 4200 7 1 m 4 x M8 1 5 m 4 x M8 2 m 6 x M8 2 5 m 6 8 x M8 Fig 2 Mounting on threaded bars inside the unit Mounting on threaded bars inside the unit...

Page 8: ...elivery Fig 6 Hoses are mounted via cable glands at knockouts to protect the hose and prevent air leakage Fig 5 Pierce the gland with a screwdriver before entering the cable 90 AR Service hatch Servic...

Page 9: ...18066 PA34VD20 ARFEC4220 6 pcs 18067 PA34VD30 ARFEC4225 8 pcs 237568 FH1020 ARFEC4200W 2 pcs L 1 m 17597 DTV200S ARFEC4200W 88060 AR42XTT10 ARFEC4210 H 130 210 mm 88061 AR42XTT15 ARFEC4215 H 130 210...

Page 10: ...695 FCOTX 39x39x23 mm 74699 FCLAP 89x89x26 mm 74702 FCWTA for water heated units 17495 FCDC 74718 FCBC05 5 m 74719 FCBC10 10 m 74720 FCBC25 25 m 74721 FCSC10 10 m 74722 FCSC25 25 m 74703 FCTXRF for FC...

Page 11: ...ND 0 10V PWM Alarm Sensor I1 I2 O1O2 A1 A2 GND GND B1 B2 D1 D2 ON OFF Termination M M M PE 12V HI LO GND 12V HI LO BUS 1 BUS 2 GND 3510 2 Motors 3515 3 Motors 3520 4 Motors 3525 5 Motors 4210 5010 3 M...

Page 12: ...WM Alarm Sensor I1 I2 O1O2 A1 A2 GND GND B1 B2 D1 D2 ON OFF Termination PAFEC ARFEC 4210E 4215E N L3 L2 L1 M M M Inlet sensor H1 H2 N 230V IN L PE N Heating Trafo N Motor 230V L PE 12V HI LO GND 12V H...

Page 13: ...r GND 0 10V PWM Alarm Sensor I1 I2 O1O2 A1 A2 GND GND B1B2 D1 D2 ON OFF Termination M M K2 K1 M Inlet sensor H1 H2 N 230V IN L PE N Heating Trafo N Motor 230V L PE 12V HI LO GND 12V HI LO BUS 1 BUS 2...

Page 14: ...r I1 I2 O1O2 Inlet sensor A1 A2 GND GND B1 B2 D1 D2 ON OFF Termination M M M PE Actuator 24V WTA 12V HI LO GND 12V HI LO BUS 1 BUS 2 E1 E2 GND Outlet sensor 3510 2 Motors 3515 3 Motors 3520 4 Motors 3...

Page 15: ...Motor W Amperage motor A Voltage V Amperage A heat Weight kg 230284 ARFEC4210E12 3 9 7 8 12 1300 2500 27 10 74 41 58 505 3 2 400V3 16 9 53 230288 ARFEC4215E18 6 0 12 18 1950 3650 28 15 76 43 60 675 4...

Page 16: ...d prevent it being fully opened The unit is ready for suspension with threaded bars on its outside The threaded bars can also be fixed on the inside of the unit e g when mounted on a solid suspended c...

Page 17: ...ble glands used must meet the protection class requirements In the distribution board it is to be indicated that the air curtains can be supplied from more than one connection Adjustment of the air cu...

Page 18: ...is located in the terminal box Fig 4 2 Mark and disconnect the cables to the PC board 3 Remove the screws securing the board and lift out 4 Install the new PC board as above in reverse order brush whe...

Page 19: ...otection should be used Keep the areas around the air intake and exhaust grilles free from possible obstructions The unit must not be fully or partially covered as overheating can result in a fire ris...

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ...AB Tel 46 31 336 86 00 Industriv gen 41 SE 433 61 S vedalen mailbox frico se Sweden www frico net For latest updated information and information about your local contact www frico net Art no 247063 2...

Reviews: