Arden 4200
16
EN
Installation and operating instructions
General Instructions
Read these instructions carefully prior to
installation and use. Keep this manual for
future reference.
The product may only be used as set out in
the assembly and operating instructions. The
guarantee is only valid should the product be used
in the manner intended and in accordance with
the instructions.
Application
Arden 4200 is an air curtain for recessed
mounting. Recommended installation height
4,2 m. The air curtain is available without heat,
with electrical heating and with water heating.
Protection class: IP20.
Operation
Air is drawn in from underneath and blown
downwards shielding the door opening and
minimizing heat loss. To achieve the optimum
curtain effect the unit must extend the full
width of the opening.
The grille for directing the outlet air is
adjustable and is normally angled outwards to
achieve the best protection against incoming
air.
The efficiency of the air curtain depends on
the air temperature, the pressure differencial
across the doorway and any wind load.
NOTE! Negative pressure in the building
considerably reduces the efficiency of the air
curtain. The ventilation should therefore be
balanced.
Mounting on threaded bars inside the unit
See pages 6-7.
1.
Hang on threaded bars (M8) according to fig.
2 (accessory).
2. Adjust the height using the lower nut so that
the frame is level with the ceiling. Lock using
the upper nut.
Mounting
The air curtain is installed horizontally with
the outlet air grille facing downwards as close
to the door as possible, concealed in the false
ceiling. The only visible part of the unit is the
underside which is level with the ceiling. The
product must be mounted in such a way to
allow future service and maintenance. The
service hatch must be accessible, nothing
should prevent it being fully opened.
The unit is ready for suspension with
threaded bars on its outside. The threaded bars
can also be fixed on the inside of the unit e.g.
when mounted on a solid suspended ceiling.
For the protection of wider doorways, several
units can be mounted in series alongside each
other. Minimum distance from outlet to floor
for electrically heated units is 1800 mm.
Mounting on threaded bars outside the unit
See pages 4-5.
1.
The mounting brackets are fixed to the unit
during transport. Loosen these, turn them
around and screw into place on the unit
according to fig. 1a.
2.
Hang on threaded bars (M8) according to fig.
1b (accessory).
3. Adjust the height using the lower nut so that
the frame is level with the ceiling. Lock using
the upper nut.
Electrical installation
The installation, which should be preceded by
an isolator switch with a contact separation
of at least 3 mm, should only be wired by a
competent electrician and in accordance with
the latest edition of IEE wiring regulations.
The air curtain has an integrated PC board
which is connected to the selected external
control system FC. FC must be ordered
separately. The PC board is accessed via cable
glands on the side or the top of the unit. FC is
supplied pre-programmed. Communication-
and sensor cables are connected to the PC
board.
Should more than one air curtain be
controlled by a single FC, an additional
communication cable FCBC per unit will be
required. See manual for FC.
Unit without heating or with water heating
The unit is connected via the cable gland on
one side of the unit or its top. Pierce the gland
with a screwdriver before entering the cable.
See Fig. 5. Control is supplied by 230V~ to the
PC board.
Unit with electrical heating
The unit is connected via the cable gland on
one side of the unit or its top. Pierce the gland
with a screwdriver before entering the cable.
See Fig. 5. Control is supplied by 230V~ to
the PC board. The power supply for heating
(400V3~) is connected to the terminal block in
the terminal box.