INSTALLATION
Material Required
• Neoprene grommet, 2½”, 3¼”, 4½” or 5½" as required.
• Cold galvanized paint.
• Touchup spray paint, champagne, P/N 044-03504-000 (for
outdoor unit exterior only).
• Caulk, P/N 013-03317-050 aluminum gray or 013-03317-
040 for outdoor units with champagne paint.
• X-acto
®
knife.
• Clean up supplies.
Procedure
See Figure 37 - Penetration Details.
1. Make sure any components; bulkheads or other
obstructions are disconnected from panel inside and out.
2. Layout location and dimensions of hole opening to be cut.
Do this on both sides of double wall panels.
3. Carefully cut correct hole size for the application in panel,
ensuring cuts on both sides line up and a smooth clean cut is
made.
4. Paint raw edges of sheet metal with cold galvanized paint.
5. Select appropriate grommet for new panel hole and cut
out appropriate hole diameter for penetration with an X-acto
knife.
6. After paint dries, Install grommet into panel hole opening.
7. Apply sealant all around new hole opening behind lip of
grommet, on both sides of panel.
8. Run pipe or conduit through grommet and make
appropriate connections.
9. All modified panels must provide integrity equal to original
equipment specifications.
10. Reconnect any components, bulkheads or other fixtures
that were disconnected from panel in step # 1.
11. Thoroughly clean up inside and outside air unit.
Figure 37 – Penetration Details
PART
PART NUMBER
Caulking Gray
013-03317-050
Champagne
013-03317-040
Champagne
Touch-up
Spray Paint
044-03504-000
WATER & STEAM COILS
NOMINAL
ESCUTCHEON
PIPE
DIMENSIONS
SIZE
O.D.
I.D.
0.50
3.0
0.550
0.75
3.0
0.815
1.00
3.0
0.815
1.50
6.0
1.400
2.00
6.0
1.875
2.50
6.0
2.375
3.00
6.0
3.000
4.00
7.0
4.000
DX/REFRIGERANT COILS
ESCUTCHEON
CONNECTION
DIMENSIONS
SIZE
O.D.
I.D.
0.500
3.0
0.175
0.625
3.0
0.550
0.875
3.0
0.550
1.125
3.0
0.815
1.375
3.0
1.000
1.625
6.0
1.315
2.125
6.0
1.875
2.625
6.0
2.375
3.125
6.0
2.875
ESCUTCHEON
JCI PART NO.
O.D.
I.D.
THICKNESS
028 14910 001
3.0
0.175
0.125
028 14910 002
3.0
0.550
0.125
028 14910 003
3.0
0.815
0.125
028 14910 004
3.0
1.000
0.125
028 14910 005
6.0
1.315
0.125
028 14910 006
6.0
—
0.125
028 14910 007
6.0
1.400
0.125
028 14910 008
6.0
1.875
0.125
028 14910 009
6.0
2.375
0.125
028 14910 010
6.0
2.875
0.125
028 14910 011
6.0
3.000
0.125
028 14910 012
7.0
4.000
0.125
WARNING
Use only metal cutting hole saws and/or blades
to make penetrations through panels. Never use a
cutting torch due to foam insulation.