System Configuration

1.

 Determine the dimensions of the coils or area to be irradiated.

2.

 Use the following guidelines to estimate the number of lamps 

needed for proper coverage.

Fresh-Aire UV offers a free system configuration consultation service for commercial 

projects. Contact Fresh-Aire UV for details.

UV Lamp Configuration Guidelines

• Maximum germicidal effectiveness is within an 18” radius from UV lamp center axis
• The optimal distance between UV lamp(s) and the irradiated surface is 12”
• The distance between stacked UV lamps should not exceed 35”
• The distance between end to end UV lamps should not exceed 12”
• The distance of UV lamp ends to the edge of irradiated surface should not exceed 6”

3.

 Before attaching the 

L-Brackets

 for mounting use the 

Optimal Irradiation 

Distance 

and

 Lamp Spacing 

diagrams to confirm that when installed the 

UV 

Lamps

 will be positioned properly. 

4.

  The 

APCO® Rack System

 can be configured to fit virtually any commercial/industrial 

HVAC application. Modules can be “daisy-chained” end to end or offset to achieve the 

desired width.

Height

Width

Depth

1. 

12” Lamp to Coil

18” UV Effective Radius

35” Lamp to 

Lamp

Coil

Optimal Irradiation Distance

12” Max. space between lamps

6” Max. space to end of coils

Single UVC/APCO module

Modules “daisy-chained” end to end

Multiple offset modules

Overlap lamps where necessary

Lamp Spacing

Rack Configurations

2