5
Sight Glass Installation
1.
The sight glass allows safe viewing of the UV light system when in operation. Find a
suitable location such as a door to the HVAC system for the sight glass.
2.
Drill a 1” hole and press the base of the sight glass through it.
6
Power-up System
Caution: UV-C light
that can cause
Serious Eye Burns
and
Temporary Blindness,
Ensure all access panels have been replaced
and doors closed before powering-up the system.
Turn on the main power then switch on the UV light power supply(s). Use the sight glass to confirm that the UV Lamp(s) is
operating.
7
UV System Maintenance
Periodically wipe the UV lamps with a clean cloth or alcohol swab to remove any accumulated dust or dirt. This should be
performed at least every 6-9 months or during routine maintenance intervals. Fouling could occur if lamps are installed under
chilled water lines. Wipe clean or install optional shield.
8
UV
Lamp Replacement
Fresh-Aire UV® lamps are rated for either one or two years
germicidal effectiveness. The lamps will continue to glow
after they have passed their rated life span but their germ-
killing effectiveness diminishes with time so they must be
replaced on schedule for the system to function properly.
Contact your local dealer for replacement lamps.
Important!
Use only Fresh-Aire UV® replacement lamps. Use of replacement lamps from other manufacturers voids the warranty.
9
Trouble Shooting
Problem
Solution
UV Lamp(s) Not Lighting
1. Check that power is applied.
2. Check that the unit is turned ON.
3. Ensure the remote lamp cables are properly connected.
4. Check the fuse. Replace only with same size and type.
5. Reset power switch on power supply (off then on).
6. Install New UV Lamp(s).
7. Consult Factory.
UV Lamp(s) Flickering
1. UV Lamp(s) have reached end of effective service life. Install new lamp(s) of
same type.
2. If unit is new, check remote cables to ensure they are properly connected.
3. Reset power switch on power supply (off then on).
4. If new lamps still flicker, consult factory.
UV Lamps Have burned Out Prematurely
1. Consult Factory.
Power Supply Will Not Light UV Lamps
even after new lamps are installed
1. Consult Factory.
2. External power suppressor may be needed if power surges occur.
Part# TUVCL-100
1 Year Effective Lamp Life
Part# TUVCL-100HO High Output - 1 Year Effective Lamp Life
Part# TUVCL-200
2 Year Effective Lamp Life
Part# TUVCL-160
60” 1 Year Effective Lamp Life
Part# TUVCL-260
60” 2 Year Effective Lamp Life
5