4. Mechanical installation 

4.1. Location 

       The installation must be located in a place free from dust

;

 corrosive vapours

;

 gases and all liquids. 

       Care must also be taken to avoid condensation of vaporised liquids, including atmospheric moisture. 

 

4.2. IP rating  

  

 IP 20 or IP 00 (e.g. location in a switchboard ) or IP 54 

 

4.3. Mounting 

  The unit must be mounted vertically, and sufficient clearance must be allowed around the unit to 

allow adequate flow of cooling air over the fins of the heat sink. A minimum of 50 mm is required 
above and below the unit, and some clear space should also be allowed at the sides and front. 

  Location within the cubicle (e.g. switchboard) without any ventilation of the air inside : 

  Heat can escape only by conduction through the skin of the cubicle, which is cooled by radiation to 

the external air. 

 

A minimum distance from the enclosure boundaries : 50 mm 

 

Heat dissipation power : approx. 4% of  the real  output power. 

 

5. Electrical installation 

 

SAFETY PRECAUTIONS 
DANGER:   The voltages present in the supply cables, the output cables and terminals, the control 
                     power supply  wiring and in certain internal parts of the drive are capable of causing 
                    severe electric shock and may be lethal ! 
 
WARNING:  Whenever the drive has been energised

;

 it must be isolated before work may continue. 

                    A period of five minutes must elapse after isolation to allow the internal capacitors to  
                    discharge fully. Until  the discharge period has passed dangerous voltages may be 
                    present within the drive. 
 
Persons supervising and performing electrical installation must  be suitably qualified and 
competent in these duties, and should be given the opportunity to study this manual before work is 
started. 

 

 

5.1. Power connections 

         CHECK THAT 

  the unit is disconnected from the input power before making connections to the terminals                            

- AC input power circuit breaker, installed upstream on the low voltage switchboard, is in "off" 
position 

 

5.1.1. Connection procedure

 

 FOR PROTECTION OF LIFE AND PROPERTY, EARTH WIRES SHOULD ALWAYS BE  

CONNECTED FIRST ! 

  remove the front panel that is secured with screws 

  connection cables should enter at the bottom 

  connect the 1 PHASE mains supply to the terminals  N

;

 L. 

  connect the motor terminals to the U, V, W terminals of the drive 

  refit the front panel 

 

Never connect the input power to the U, V, W terminals of the drive !!!

 

 
 
 
 
 
 
 
 
 

Summary of Contents for FIA-L110

Page 1: ...CZECH REPUBLIC tel 420 241 71 32 44 45 fax 420 241 72 10 52 E mail info frecon cz http www frecon cz FRECON FIA L18 37 55 75 110 150 220 250 PROGRAMMABLE SPEED DRIVES FOR STANDARD AC INDUCTION MOTORS...

Page 2: ...before work may continue A period of five minutes must elapse after isolation to allow the internal capacitors to discharge fully Until the discharge period has passed dangerous voltages may be presen...

Page 3: ...W up to 500Hz Apparent power kVA 0 6 1 0 1 4 1 6 2 2 2 8 4 0 4 5 Overload 150 30 sec Nominal current A 1 4 2 4 3 0 4 0 5 5 7 0 10 0 11 3 Modulation PWM 18kHz V f characteristic adjustable Control logi...

Page 4: ...control power supply wiring and in certain internal parts of the drive are capable of causing severe electric shock and may be lethal WARNING Whenever the drive has been energised it must be isolated...

Page 5: ...andard cable to both the motor earth terminal and the drive earth terminal Installations with long cable runs to the motor i e above approx 30 m may need the addition of motor line chokes to prevent n...

Page 6: ...eter 2 20 k recommended value 10 k Logic inputs run stop control switch or PLC output forward reverse control switch or PLC output Input voltage min 15 VDC Input current approx 8 5 mA 24 VDC nominal 2...

Page 7: ...is set by parameter ACC refer to chapter 9 section 1 disconnect 24 V DC from the terminal 3 The motor will ramp or coast to a stop Deceleration is set by parameter DEC stopping mode is set by paramete...

Page 8: ...led and all parameter values can be changed from the keypad refer to user manual for the MINITERMINAL 8 Reset of the drive after a trip signal Two modes are available short time disconnecting of the d...

Page 9: ...age FOUT 6 8 FBAS U7 32 93 VMAX output voltage FOUT 7 8 FBAS CINP 0 1 2 3 reference input selection CSTP 0 1 stopping mode selection CRTR 0 1 reset mode selection SET support parameter for user set pr...

Page 10: ...the filter follow the instructions in FIG 4 FIG 4 The filter cubicle is necessary to install near of the drive NOTE Connections must be made with the short length of screened cables If these cables ar...

Reviews: