background image

 
 

2

1. Introduction 

  Small, light-weight and compact 

  IGBT output bridge for high speed switching and low power consumption 

  Motor speed continuous - controlled from 0Hz to 125Hz (option - up to 500Hz) 

  Logic and analogue inputs for remote control 

  FRECON MINITERMINAL - control pod : combines keypad and display, operational functions of 

the drive can be changed from the keypad. 

  FRECON TELECONTROL: remote control and indication unit 

  External braking unit 

  External RFI filter 

 

2. General  characteristics 

Type:                                                                              FIA-L: 

18 

37 

55 

75 

110 

150 

220 

250 

Nominal motor rating

                                                      (kW) 

0,18 0,37 0,55 0,75  1,1  1,5  2,2  2,5 

Input:

                   

                             Voltage

 

1x 230V 

±

 10% 

                             Nominal current                                      (A) 

2,6 

4,4 

6,1 

7,0 

9,6 

12,2 

17,5 

20,0 

                             Frequency  

47 

÷

 63 Hz 

Output:               

  

                             Voltage

 

3 x 0 

÷

 input voltage 

                             Frequency  

÷

 125Hz, (with spec. SW up to 500Hz) 

                             Apparent power                                  (kVA) 

0,6 

1,0 

1,4 

1,6 

2,2 

2,8 

4,0 

4,5 

                             Overload  

150%, 30 sec 

                             Nominal current                                      (A) 

1,4 

2,4 

3,0 

4,0 

5,5 

7,0 

10,0 

11,3 

                             Modulation 

PWM - 18kHz 

                             V / f - characteristic 

adjustable 

Control: 

logic inputs - control switch or PLC output 

function

 - START/STOP, FORWARD/REVERSE 

analogue inputs: 0

÷

20mA (4

÷

20mA), 0

÷

10V (2

÷

10V), potentiometer (2

÷

20k

Ω

function

 - SPEED CONTROL 

Protections:               

  

                                       low voltage, overvoltage, overcurrent, I x t, short-circuit (phase-phase, phase-earth) 

 Environmental conditions:

  

                             Ambient temperature / Ambient humidity 

÷

 40

0

C / max. 90% (non condensing) 

                             Enclosure  

IP 00 or IP 20 or IP 54 

 Design criteria: 

                            Safety 

EN 61 010-1 / 95 

                            Electromagnetic compatibility - emission: 

EN 55 011/A1,B1;  EN 50 081-1, 2 (with external RFI filter) 

                                                                           - immunity: 

EN 50 082-1, 2 

Dimensions:

       Height                                              

  

    (mm) 

180 200 

(IP 20)                  Width                                                   (mm) 

153 

160 

                             Depth                                                  (mm)

 

97 145 

Weight:                                                                             

(kg)

 

1,3 2,5 

 

3. Description

 

 

 
 
 
 
 
 
 
 
 
 
 

 
 
 

status LED 
indication 

- power 
- failure

control and power 
cables lead-in 

heat sink 

FRECON MINITERMINAL 
connector 

Summary of Contents for FIA-L110

Page 1: ...CZECH REPUBLIC tel 420 241 71 32 44 45 fax 420 241 72 10 52 E mail info frecon cz http www frecon cz FRECON FIA L18 37 55 75 110 150 220 250 PROGRAMMABLE SPEED DRIVES FOR STANDARD AC INDUCTION MOTORS...

Page 2: ...before work may continue A period of five minutes must elapse after isolation to allow the internal capacitors to discharge fully Until the discharge period has passed dangerous voltages may be presen...

Page 3: ...W up to 500Hz Apparent power kVA 0 6 1 0 1 4 1 6 2 2 2 8 4 0 4 5 Overload 150 30 sec Nominal current A 1 4 2 4 3 0 4 0 5 5 7 0 10 0 11 3 Modulation PWM 18kHz V f characteristic adjustable Control logi...

Page 4: ...control power supply wiring and in certain internal parts of the drive are capable of causing severe electric shock and may be lethal WARNING Whenever the drive has been energised it must be isolated...

Page 5: ...andard cable to both the motor earth terminal and the drive earth terminal Installations with long cable runs to the motor i e above approx 30 m may need the addition of motor line chokes to prevent n...

Page 6: ...eter 2 20 k recommended value 10 k Logic inputs run stop control switch or PLC output forward reverse control switch or PLC output Input voltage min 15 VDC Input current approx 8 5 mA 24 VDC nominal 2...

Page 7: ...is set by parameter ACC refer to chapter 9 section 1 disconnect 24 V DC from the terminal 3 The motor will ramp or coast to a stop Deceleration is set by parameter DEC stopping mode is set by paramete...

Page 8: ...led and all parameter values can be changed from the keypad refer to user manual for the MINITERMINAL 8 Reset of the drive after a trip signal Two modes are available short time disconnecting of the d...

Page 9: ...age FOUT 6 8 FBAS U7 32 93 VMAX output voltage FOUT 7 8 FBAS CINP 0 1 2 3 reference input selection CSTP 0 1 stopping mode selection CRTR 0 1 reset mode selection SET support parameter for user set pr...

Page 10: ...the filter follow the instructions in FIG 4 FIG 4 The filter cubicle is necessary to install near of the drive NOTE Connections must be made with the short length of screened cables If these cables ar...