FDA700 Rev160509
17
Figure 11. Delta Winding Connections
Delta Winding Connections
12-Pin Deutsch
Receptacle to
Gray Connector
Refer to Figure 7
From Generator
N C B A
N C B A
To Load
Current
Sensors
Voltage
Transformers
Recommended
Delta Circuit
Reference Wiring
A
B
C
N
120v
120v
240v
208v
240v
Note 1:
If the voltage reading needs
Calibration, adjust
AB (line-4),
BC (line-5),
CA (line-6).
Ref. OEM Calibration Guide
Note 2:
If the phase A & C is split for
Neutral, reverse the wiring for
phase B & C.
If the phase B & C is split for
Neutral, reverse the wiring for
phase A & C.