QUICK INSTALLATION GUIDE (FHP)
17
•
Connect more than 3 aPower X units to the aGate X (Please consult FWH for
technical support).
T
here are two (2) pairs of lugs on the
backup load terminals
of the aGate X. When
connecting
more than 3 aPower X units to the aGate X, use one
(1) pair for the aPower X input from the
combiner box and one (1) for the backup main panel output.
WARNING:
The WAGO terminals of each aPower X can only be connected using
10AWG power wire.
aPower X 1
Connection
aPower X 2
Connection
aPower X 3
Connection
aPower X N(N≤15)
Connection
L1 L2
Ground
Neutral
…
Combiner box