QUICK INSTALLATION GUIDE (FHP)
12
•
Communications connection between the aGate X and the aPower X
When the length of the communications cable between the aGate X and the aPower X is less
than 98ft (30m), a communications cable can be used to connect.
Both the communications cable connection and 20V power supply must be used in
conjunction when the communications cable length between aGate X and aPower X is longer
than 98ft (30m).
WARNING:
When more than one aPower X unit work in parallel mode, it is necessary to remove
the excess matching terminals from all aPower X units along the loop except for the
matching terminal on the last aPower X.
NOTE:
➢
If the
communications
cable shares the same conduit with power wires, please
use a Type
600V TC
insulated
communication
cable (with metal connector).
➢
When the system needs to be connected to the 20V power
supply
, the terminal does not need to be removed. Just
press the orange switch of the port, insert the prepared
wire, and then release the switch to complete the wiring.
aPower X 1
Connection
aPower X 2
Connection
aPower X N (N≤15)
Connection
CAN OUT
EMS
- +
20V power
supply
Communications
cable
…
WARNING:
➢
The
communications
cable
according to 568B.
➢
Test with a wire tracker to ensure
that the
communications
cable is
error-free
.
Before testing the cable
using the
wire tracker
, ensure that
both ends of the communication
cable are not connected to the
device.