4
GB
External Switch
A float, pressure or any other external switch
can be
used to power the SubStart3P
®
. Remember to leave
the ON/OFF switch in the SubStart3P
®
in the ON po-
sition if an external control switch is used. Required
external switch contact rating: 400V/1A unipolar.
Managing ON/OFF switching activity
Your submersible electric motor accumulates a
certain amount of heat each time it is switched on. It
must run for a period of time during which it has the
opportunity to dissipate the heat. If too many starting
cycles are called for your motor and/or pump may be
damaged. Observe the starting specifications of the
motor.
Maintenance and service
The SubStart3P
®
is maintenance free and requires
no maintenance or service. The control box contains
no serviceable parts.
Trouble shooting
Condition / Fault
Cause / Remedy
Motor / pump does
not switch on
Loss of power -
check
supply voltage (Are other
appliances working? )
Damaged manual
motor starter -
contact
supplier
Overload tripped -
reset overload
Motor / pump does
not switch off
Damaged switch -
contact supplier
Motor / pump
switches on and off
repeatedly
Faulty pressure switch
or float switch
-
contact supplier
Overload trips
repeatedly
Pump locked
- debris
may have entered the
pump. Remove motor -
pump from the borehole
and clean pump
Cable damage -
the
drop cable may have
been damaged. Check
cable for damage.