  MOUNT SINK 

Hang sink onto wall brackets 

and level the sink by eye. (Final 

levelling will take place after water 

flow is activated.

4

4

  INSTALL THE WASTE FITTING INTO THE SINK. 

a.  Disassemble the waste fitting.
b.  Slide the waste body and upper gasket into the sink hole.
c.  Thread the lock nut onto the body.
d.   Tighten into place.
e.  Insert the tailpiece into the tailpiece nut.
f.  Insert the tailpiece gasket into the tail
g.   Tighten the tailpiece assembly onto the waste body. 
h.  Connect a standard p-trap (provided by others). The amount of space is limited to install the shroud. We recommend a 1 piece 

tubular trap without a cleanout plug on the bottom the trap.

 

5

5

    ELECTRICAL CONNECTIONS  

Check local codes for compliance prior to making any electrical connections. 

The water tight fittings have an alignment feature. Gently push the fittings together rotating until they engage. Little to no force 

should be required to do so. Once fitted together, lock together by threading the locking rings. 

The connections are colour coded. 
a.  Connect the blue banded wires together (electrolytic generator)
b.  Connect the yellow banded wires together (IR sensor)
c.  Connect the red banded wires together (water LED) 
d.  Plug in the transformer to the black wire and plug into the GFI receptacle. 
e. Optional battery backup AT00-024 (white banded) cable

EN

Summary of Contents for HWSS2321W-00

Page 1: ...INFECTION CONTROL WASH BASIN ...

Page 2: ...ste treatment Medi flo is designed for hand washing only and is not to be used as a drinking source to wash instruments or bedpans etc Recommended for areas with normal water conductivity above 75 TDS total dissolved solids If unaware of your local water conductivity please contact customer service and this can easily be determined for you before you install the product Medi flo is recommended to ...

Page 3: ... Location 17 5 8 448 mm 1 1 2 Waste Location FINISHED FLOOR Ø1 Ø25 mm 2 51 mm 3 1 2 89 mm 7 178 mm 31 9 16 801 mm 3 1 4 83 mm 3 7 8 98 mm WALL OPENINGS LAYOUT 21 1 4 539 mm 8 11 16 220 mm 10 3 8 263 mm Opening for rough in box 32 13 16 833 mm 2 2 2 2 EN No tools Hand tighten ...

Page 4: ...pace is limited to install the shroud We recommend a 1 piece tubular trap without a cleanout plug on the bottom the trap 5 5 ELECTRICAL CONNECTIONS Check local codes for compliance prior to making any electrical connections The water tight fittings have an alignment feature Gently push the fittings together rotating until they engage Little to no force should be required to do so Once fitted toget...

Page 5: ... as follows IR sensor will see a users hand This will trigger the water flow LED and the electrolytic generator will turn on When the user removes their hands to lather the water flow will turn off however the electrolytic generator will stay on for 20 seconds unless programmed otherwise The electrolytic generator is self programming based on local water conductivity If conductivity is in normal r...

Page 6: ...trolytic generator is not seen running 1 Check cable connection 2 Ensure water is not distilled or R O filtered TDS 50 Water output is too high 1 Adjust shut off valve installed in 3 8 line 2 Faulty flow control regulator found in brass output port of the solenoid valve Water output is too low 1 Faulty flow control regulator found in brass output port of the solenoid valve 2 Obstruction on dirt st...

Page 7: ... or by sending in a sample of 250ml minimum to our customer service Tests such as ORP and Indigo may not give valid readings due to hydrogen interference temperature water composition and PH Subtract the reading obtained from straight tap water to remove any reading from chlorine The default operation of the electrolytic generator is to run a charge cycle after every use Target canister charge is ...

Page 8: ... 00 Medizmi102218 V15 EN EN WARRANTY If inspection the product confirms that it is defective in materials or workmanship Franke Kindred Canada Ltd will at their choosing repair or exchange the product during the following periods Sink waste fitting and shroud 2 years Water controls and electronics 1 year NOTE In the event of a limited warranty claim proof of purchase date will be required ...

Reviews: