12

Reserved to qualified operators

FAULTS AND REMEDIES

EN

Warning! The operations should be carried out by a qualified professional.

8.1  DIAGNOSIS AND OPERATING ANOMALIES

This section includes the typical anomalies that could occur.

Many of these problems are not caused by the cooler, but they could be brought about by the electricity supply or by an incorrect use of the water cooler.

In the ANOMALY column, the problems report by the customer are listed.

In the POSSIBLE CAUSES column, the “probable reasons” behind the problem are listed.

In the INTERVENTION column, the corresponding corrective action is listed.

8.2  COOLING SYSTEM

anoMaly

PossiBle cause

interVention

The compressor will not start.

Power failure.

Check that there is voltage in the plug.

Thermostat on the off position, or set to the 

minimum.

Adjust the thermostat position.

Faulty thermostat.

Replace the thermostat.

The over-load protection of the compressor is 

faulty.

Replace it.

The starting relay is faulty.

Replace it.

The starting capacitor is faulty.

Replace it.

The compressor is faulty

Replace it.

The water is could but the appliance is operat-

ing excessively or non-stop.

Little ventilation.

Place the appliance away from the wall.

The condenser is dirty or covered.

Clean the condenser or free it of its obstacles.

The thermostat is on maximum could position.

Adjust it.

The room temperature is heigher than 32°C.

It is normal that the appliance works at a con-

tinuously high room temperature.

The compressor works continuously, but the 

water is not cold.

Gas leak from the cooling system.

Contact a specialised technician (Refrigerationist).

The compressor is faulty.

Replace the compressor.

COOLING SYSTEM
Too much noise coming from the appliance, but 

it is working normally.

The machine is not levelled.

Level the appliance using the adjustable feet.

A few pipes are touching some parts inside the 

appliance, thus causing it to vibrate.

Adjust the position of the pipes, making sure 

they do not touch any other parts.

Could water comes out slowly or not all.

Low pressure of the inlet water.

Take steps to increase the pressure (autoclave).

Faulty solenoid valve.

Replace it.

Clogged water filter.

Replace it.

The temperature adjuster is faulty and causes 

complete freezing of the ice compartment.

Make the ice melt.

Replace the temperature adjuster.

Qualified operator service:

The dealer / Installator has to mark this square for the service.

Franke Sissons Ltd.

Carrwood Road, Sheepbridge,

Chesterfield, S41 9QB

Telephone: 01246 450255

Fax: 01246 451276

E-mail: [email protected]

Summary of Contents for ANMX 308 ANMX 309

Page 1: ...EN COD 5561499 REV 1 10 2016 ANMX 308 ANMX 309 ANMX 311 ANMX 312 Installation use and maintenance handbook ANMX ...

Page 2: ...s such as alcohol or diluents Do not install the machine in excessively damp and dusty places ex posed to direct sunlight outdoors or near to heat sources Machine in stallation in these places could cause fires or electric shocks The appliance is not suitable for use in open places Duringconnectionoftheappliancetothemainswatersupply allpre existing tubes gaskets and joints placed between the appli...

Page 3: ...ed information about treatment recovery and recycling of this product please contact your local city office your household waste disposal service or the shop where you purchased the product EN Place the appliance in its installation site chap 5 INSTALLATION Cut straps R and remove carton C polystyrene F and external plastic bag S Do away with plastic bags S and polystyrene Fimmediately as they are...

Page 4: ...ies and public places The machine must be connected to a source of potable water and fitted with spe cial filtering kits The machine must be installed in a room where the environmental conditions are as specified in the chapter TECHNICAL CHARACTERISTICS 1 G61 valve ANMX 309 312 2 G62 valve 3 Door closure 4 Door 5 Water filter 6 Water inlet ø8 mm 7 Power connection 8 Water outlet 9 Temperature cont...

Page 5: ... 25 6 6 25 6 6 Water outlet temperature C F 8 12 46 53 8 12 46 53 Compressor HP 1 6 1 6 Rated input Watt 190 190 Packing dimensions mm 40x42x106 V 0 18 51x44 5x67 V 0 18 Net weight kg Ibs 29 63 9 26 57 3 Gross weight kg Ibs 31 68 3 27 59 5 Charge FREON R134A g oz 100 3 5 100 3 5 4 1 CONDITIONS OF THE SURROUNDINGS ANMX 308 309 ANMX 311 312 6 ...

Page 6: ...6 HANDBOOK SECTION II Reserved to qualified operators ...

Page 7: ...ular material wood plaster property screws are required Look for them in a dedicated shop Apply the bracket to the wall Fig 6 6 Positioning the cooler to the wall keep the bracket in contact with the open ing A on the rear side of the cooler Fig 6 7 EN Place the appliance in the desired point of installation away from heat sources and protected from direct sunrays Adjust foot 1 to level the applia...

Page 8: ...ermined location The water flow is regulated by manipulating screw S turning it clockwise will decrease the flow anticlockwise movement will increase it 5 3 WATER CONNECTION TO THE MAINS Before making the water connection make sure the mains water pressure EN is between 1 and 3 bars If the mains water pressure exceeds 3 bars predispose a pressure re ducer capable of reducing the latter to the 1 3 ...

Page 9: ...n water is clean and it comes from the tray that collects any dripping during dispensing Connect the drain pipe ext ø24mm to a drain with a drain trap If necessary cut the pipe so as to avoid constrictions or backflow problems EN 5 5 HYGIENIC CLEANING Once you have checked that the appliance operates correctly proceed with the internal cleaning and hygienic cleaning phase as described in chap 6 5 ...

Page 10: ...d alkali corrosive substances disposable gloves must be used as well as glasses to protect your eyes When this hygienic cleaning is carried out you must keep to the product reaction times percentages of hygienic detergent and quantity of water necessary for rinsing Warning If the appliance is equipped with a chlorine filter proceed as follows Remove the filter cartridge and fit on the false cartri...

Page 11: ... Front door Put the lever in vertical position to stop the water Fig 17 1 Turn cartridge slowly until it stops Fig 17 2 Pull used cartridge straight down and extract from the cooler Fig 17 2 17 3 EN There may be a small amount of water during cartridge removal Push the new cartridge into filter head and turn until it stops Fig 17 4 Turn the lever in horizontal position and check if there re water ...

Page 12: ...Place the appliance away from the wall The condenser is dirty or covered Clean the condenser or free it of its obstacles The thermostat is on maximum could position Adjust it The room temperature is heigher than 32 C It is normal that the appliance works at a con tinuously high room temperature The compressor works continuously but the water is not cold Gas leak from the cooling system Contact a s...

Reviews: