background image

DRAFT 24 Jul 2013 
 

 

Page 5 of 5 

In situations where it is not possible to sweep through the stove the installer will have 
provided alternative means, such as a soot door.  After sweeping the chimney the stove flue outlet and the 
flue pipe connecting the stove to the chimney must be cleaned with a flue brush. 

 
Periods of Prolonged Non-Use 

If the stove is to be left unused for a prolonged period of time then it should be given a thorough clean to 
remove ash and unburned fuel residues. To enable a good flow of air through the appliance to reduce 
condensation and subsequent damage, leave the air controls fully open. 
 

Extractor fan 

There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit 
smoke and fumes into the room. 
 

Aerosol sprays 

Do not use an aerosol spray on or near the stove when it is alight. 
 

Use of operating tools 

Always use the operating tools provided when handling parts likely to be hot when the stove is in use. 
 

Chimney Fires 

If the chimney is thoroughly and regularly swept, chimney fires should not occur.  However, if a chimney fire 
does occur turn off the stove immediately and isolate the mains electricity supply (if applicable), and tightly 
close the doors of the stove.  This should cause the chimney fire to go out. If the chimney fire does not go 
out when the above action is taken then the fire brigade should be called immediately. Do not relight the 
stove until the chimney and flueway have been cleaned and examined by a professional. 
 

Permanent air vent 

The stove requires a permanent and adequate air supply in order for it to operate safely and efficiently. 
In accordance with current Building Regulations the installer may have fitted a permanent air supply vent into 
the room in which the stove is installed to provide combustion air. This air vent should not under any 
circumstances be shut off or sealed. 
 
 

USER OPERATING INSTRUCTIONS 

 
Please read the important notices given above before referring to the main instruction book for detailed 
operating instructions. 
 
 

Recommended fuels: 

Please note that HETAS Ltd Appliance Approval only covers the use of wood logs on this appliance.  HETAS 
Ltd Approval does not cover the use of other fuels either alone or mixed with the recommended fuels listed 
above, nor does it cover instructions for the use of other fuels. The stoves have a refuelling interval of 0.75h to 
achieve the nominal rated output. Wood logs should be seasoned with a moisture content of around 20%.  
 

De-Ashing: 

It is important that you empty the ash pan at regular intervals and dispose of ash in a safe and 
environmentally friendly manner. Always use the operating tools provided and replace the ashpit cover 
correctly. DO NOT allow ash to build up underneath the bed as this may cause damage to the grate. 
 

Spare Parts: 

For more information on obtaining spare parts, please contact the manufacturer directly using the contact in the 
main stove brochure. 
 
 
 

Summary of Contents for Montfort MK2

Page 1: ...appliance Installation instructions Operating instructions Spare parts Warranty certificate Document n 1295 10 20 03 2012 Technical manual to be saved by the user for future reference Parc d activit s...

Page 2: ...Building Control approval or is installed by a Competent Person registered with a Government approved Competent Persons Scheme HETAS Ltd operate such a Scheme and a listing of their Registered Compete...

Page 3: ...for solid fuel must be used in accordance with Building Regulations Approved Document J Any existing chimney must be clear of obstruction and have been swept clean immediately before installation of...

Page 4: ...iance with a permanently open air vent in compliance with ventilation requirements stated in Approved Document J Please reference ADJ for further guidance Connection to chimney Stoves may have a choic...

Page 5: ...ove have been carried out correctly and that the chimney has been swept clean is sound and free from any obstructions As part of the stoves commissioning and handover the installer should have shown y...

Page 6: ...gade should be called immediately Do not relight the stove until the chimney and flueway have been cleaned and examined by a professional Permanent air vent The stove requires a permanent and adequate...

Page 7: ...p 8 Cleaning p 8 Maintenance of the chimney p 8 Maintenance of the stove p 8 Recommendations p 9 Trouble shooting p 10 FRANCO BELGE congratulates you on your choice FRANCO BELGE guarantees the quality...

Page 8: ...of the combustion chamber FUEL WOOD Reference 134 05 02 Nominal heat output kW 5 Chimney draft required Pa 12 Hearth dimensions width mm 335 depth mm 205 height mm 250 Log dimensions lenght maxi cm 2...

Page 9: ...asons The installation must be carried out according to the standards and the Building Regulations It is the installer responsability to ensure that the manufacturer s intructions are complied with 2...

Page 10: ...l Building Inspector The flue must be in good condition and must provide sufficient draught The flue must be suitable for the installation of solid fuel burning appliances and comply with Current Buil...

Page 11: ...ls have been removed and are not blocking any of the air passages Check that all removable internal components are correctly installed as they May have moved in transit Note all gaskets glass fiber ro...

Page 12: ...Montfort Mk2 Model 1340502 Technical manual 1295 7 Figure 5 Replacing the parts Figure 5a Figure 5b Figure 5c Figure 5d...

Page 13: ...se of the fume emission has been identified and corrected If necessary seek expert advice Note It is recommended to use a fireguard in the presence of children and also in the presence of old and or i...

Page 14: ...g Figure 6 Slide the secondary air inlet B1 to the right Open the primary air inlet C1 Lay firelighters or rolled up newspapers on the grate with a reasonable quantity if necessary of dry kindling woo...

Page 15: ...ny water splashes or condensation marks these should be cleaned off before they have chance to dry out Ensure that the fuel retainer is installed correctly fig 8 Check that there are no obstructions b...

Page 16: ...uously burn small wood sticks bundles carpentry offcuts plywood pallets etc Smokes when lighting up Flue duct is cold Burn paper and kindling wood to increase heat Room is in decompression negative pr...

Page 17: ...e A B C D E F 04 22 262612 Heat shield A B C D E F 01 23 265607 Knob A B C D E F 01 24 270412 Air control flap A B C D E F 01 25 300118 EF Leg A 04 25 300118 77 Leg B 04 25 300118 RJ Leg C 04 25 30011...

Page 18: ...1340502 Technical manual 1295 13 Figure 8 Stove exploded view 36 48 20 30 41 1 24 35 3 50 43 52 9a 42 38 51 28 31 47 12 44 45 19 37 34 3 22 33 26 39 25 15 23 46 40 11 27 10 9b 8 21 21 49 13 4 32 5 5 1...

Page 19: ...upplementary plate A B C D E F 01 43 352168 EF Top plate A 01 43 352168 77 Top plate B 01 43 352168 RJ Top plate C 01 43 352168 RP Top plate D 01 43 352168 RH Top plate E 01 43 352168 MK Top plate F 0...

Page 20: ...Montfort Mk2 Model 1340502 Technical manual 1295 15 Notes...

Page 21: ...ostly vis vis the price of the appliance the decision to replace or repair the appliance will be taken by the vendor Our guarantee is for 2 two years for all appliances with the exception of closed co...

Reviews: