Fral FDKA100.1 Use And Maintenance Manual Download Page 6

M.FDKA100-03  26/09/2017 

                                                                                                                                                                                                                                       
M.FDKA100.1-03  26/09/2017 

 

 

Warning

:  Never apply an external source of heat to melt ice off coil.   

 

Maintenance

 – Annual Inspection of Coils and drain line is required. 

 

1.

 

Unplug Unit 

2.

 

Filter may be cleaned by 

a.

 

Vacuuming 

b.

 

Washing with warm, soapy water. Rinse and shake dry. 

3.

 

Coils may be cleaned by 

a.

 

Vacuuming the external surfaces of coil 

b.

 

Blowing  compressed air  from behind coils.  Hold air nozzle 6” away from coil to  avoid 
damage.

 

 
Warning

:  Do not steam clean refrigerant coils. 

 

4.

 

Plug in Unit 

5.

 

Test Refrigerant Charge 

a.

 

Confirm compressor is running and allow to run for minimum of 15 minutes 

i.

 

If under 70°F, a layer of ice will form on evaporator coils 

ii.

 

If over 70°F, a layer of frost or water droplets will form on coil 

6.

 

Test Defrost System 

a.

 

Leave  unit  running  for  approximately  30  minutes  (45-55  minutes).    The  unit  should 
enter a defrost mode for approximately 5 minutes.  The unit will enter a defrost mode 
with the compressor operating and fan off to defrost the coil. If the unit will not defrost, 
either 

i.

 

Control board may be defective 

ii.

 

Bypass valve may be defective 

7.

 

After routine maintenance has been completed, return humidistat to desired setting. 

 
If any problems occur during routine maintenance, contact your contractor or the factory.

 

 

 

 

Summary of Contents for FDKA100.1

Page 1: ...M FDKA100 1 03 26 09 2017 DEUMIDIFICATORI DEHUMIDIFIERS FDKA100 1 MANUALE D USO E MANUTENZIONE USE AND MAINTENACE MANUAL M FDKA100 1 03 26 09 17...

Page 2: ...should be positioned with the sides against a wall and the inlet and discharge perpendicular to the wall Do not insert any objects into the inlet or discharge If service is required call a qualified t...

Page 3: ...to the room at a little bit higher temperature and lower Relative Humidity If the room temperature is lower than about 70 F the condensed moisture become ice In this case every roughly 30 minutes a de...

Page 4: ...mply press the POWER key and depending on the relative humidity set the machine starts working When the machine reaches the level of required moisture goes into stand by mode automatically stops but r...

Page 5: ...essary to make a cleaning of the warm heat exchanger condenser by using compressed air This operation must be done by a specialized technician This cleaning will improve the performances and the long...

Page 6: ...arge a Confirm compressor is running and allow to run for minimum of 15 minutes i If under 70 F a layer of ice will form on evaporator coils ii If over 70 F a layer of frost or water droplets will for...

Page 7: ...ard Defrosting Control System electronic Hot gas defrosting control system termost electronic Condensed Water Draining Pipe Connection 3 4 M Functioning Relative Humidity Range Temperature range 33 8...

Page 8: ...R PURPLE ORANGE WHITE BROWN BLUE BLUE FAN SOLEDOID VALVE ELECTRICAL BRIDGE 2 ELECTRICAL BRIDGE 3 BLU BLUE R G A E V PUMP T1 T2 T3 0105 UR BLUE POWER SUPPLY 115V 60HZ PCB 115V 60HZ TRANSFORMER 115V 220...

Page 9: ...a defect in workmanship or material These warranties do not apply for loss or damage caused by accident fire abuse misuse improper installation leaking modification misapplication weather freezing lac...

Page 10: ...also have other rights which vary from state to state Some states do not allow limitations on warranties or on remedies for breach In such states the above limitations may not apply to you FOR CANADIA...

Page 11: ...the unit to the condensate pump Dehumidifier Drain Fitting Level of Dehumidifier Drain Fitting drain drain Make sure no part of the hose is higher than the bottom of the drain fitting Note The drain...

Page 12: ...tting IMPORTANT The drain hose from dehumidifier to pump must run downward and stay below the level of dehumidifier drain fitting Tubing line from pump can run up to 20 feet upward and out into drain...

Reviews: