72
Applying measurement current
The EM-PQ2500 is designed for the connection
of ../1A and ../5A current converters.
Only AC currents, and not DC currents, can be
measured using the current measurement in-
puts.
Short-circuit all current converter outputs ex-
cept one. Compare the currents displayed by
the EM-PQ2500 with the applied current.
The current displayed by the EM-PQ2500 must
match the input current under consideration of
the current converter transfer relation.
The EM-PQ2500 must display approx. zero
amperes in the short-circuited current measu-
rement inputs.
The current converter ratio is set to 5/5A in the
factory and may have to be adapted to the cur-
rent converter used.
Warning!
Voltages and currents outside of the
authorized measurement range can
destroy the device.
m
Voltages are shown with long pointers in the
pointer diagram, and currents with shorter
pointers.
Current
Voltage
Initialization
Sign
Reactive power
•
positive (+) with inductive load,
•
negative (-) with capacitive load.
Phase angle (U/I)
•
positive (+) with capacitive load,
•
negative (-) with inductive load.