9
Description
Features
•
Front board installation, 144x144mm,
•
Working temperature range -10°C .. +55°C,
•
Colour graphic display 320x240, 256 colours, 6 keys,
•
8 digital inputs, 5 digital outputs,
•
16Bit A/transformer, data memory 256MByte Flash, SDRAM 32Mbyte,
•
Continuous scanning of voltage and current measurement inputs with 20kHz,
•
Frequency range of fundamental oscillation 40Hz .. 70Hz
•
4 voltage measurement inputs, 4 current measurement inputs,
•
Measurement in TN and TT networks,
•
RS485: Profibus DP/V0, Modbus RTU, Modbus-Master,
•
Ethernet: Web-Server, EMAIL, BACnet (Option),TCP/IP, EMAIL (SMTP), DHCP-Client (BootP),
Modbus/TCP, Modbus RTU over Ethernet, FTP, ICMP (Ping), NTP, TFTP, SNMP.
•
Detection of transients >50µs and storage with up to 16000 scanning points,
•
Detection of more than 800 measurement values,
•
Measurement of harmonics 1 to 40, for
- Uln, I, P (ref/supply) and
- Q (ind/cap),
•
Programming own applications in Jasic.