FP S-ENGuard Model series W640 / W667
14
KP1
Power
110 - 230 V DC
Power connection
(under the protective cover)
Pwr
Power LED (lights up red when mains voltage is ap-
plied)
LAN
Ethernet connection, RJ45 port with 2 LEDs
Green LED off = no connection
Lights up = connection established
Flashing = data transfer
Yellow LED off = 10 Mbit connection
Lights up = 100 Mbit connection
KX3
1-wire
1-wire interface (1-wire master for max. 30 sensors)
SIM unlock
Button to unlock the drawer for the SIM card
(model dependent)
Antenna
(on housing)
Connection for mobile communications antenna
(de-
pending on model)
USB1
USB2
2 USB host interfaces for connecting USB devices
(memory stick, WiFi stick)
PSU OCD
PTC overcurrent protection
KP2
Relay Out
Relay 1 (changeover contact) 240 V/5 A
KP4
Relay Out
Relay 2 (changeover contact) 240 V/5 A
KP3
Dig. IN
Digital input (Input 1) 240 V
KP5
Dig. IN
Digital input (Input 2) 240 V
KM1 COM3 M-Bus
M-Bus interface for 100 end devices
KX1
COM1 RS232
COM2 RS485
RS232 interface COM1
RS485 interface COM2, termination switchable via DIP
switch S1
S4
Reset button for manual restart (hardware reset, for de-
velopers only)
KX10
KX20
KX30
KX40
KX50
1× Expansion
Socket
Free sockets for S1 Expansion module
(5 pcs)
DBG
Serial debug interface for software developers