Technical data
29
Technical data
Detailed technical specifications can be found on the data sheet and in the
configuration manual. Download at:
https://www.inovolabs.com/infobereich/downloads/handbucher-datenblatter
.
Selected technical data at a glance
(Subject to technical changes at short notice.)
Housing
OEM wall mount housing, direct wall mounting
or
Mounting using wall brackets
(optional)
Dimensions
(Width × Height ×
Depth)
271 mm × 170 mm × 60 mm
Including cable glands:
271 mm × ca. 202 mm × 60 mm
Including cable glands and antenna socket:
271 mm × ca. 214 mm × 60 mm
Weight
approx. 1.3 kg
Power supply
110 - 240 V AC/50 - 60 Hz
Overcurrent protective device (PTC OCD), triggers at 2 A
3 screw terminals 1.5 mm
2
(L, N, protective conductor)
Prescribed protection
Circuit breaker of type max. 10 A, characteristic B, switching
capacity 6 kA
in the electrical system of the building
Fuse protection must be carried out in phase (L)
Prescribed
disconnection
Two-pole (L, N) disconnecting device with a minimum con-
tact distance of 3 mm in the electrical system of the building
Disconnecting device must be easy to access