-2- INSTALLATION INSTRUCTIONS

 

 

-2-1.   LINE PRESSURE

 

 

A 2-bar minimum pressure is absolutely necessary to provide a normal efficiency of the control valve. 

Maximum pressure must not exceed 8 bars, in order to prevent troubles on all installation. 

 

If necessary, a pressure regulator should be installed upstream to the system. 

 

If  water  line  is  shut  down,  take  care  to  prevent  any  depression  (negative  pressure),  which  could 

destroy the tank. Isolate the system with the bypass or with shut off valves on the inlet and outlet of the 
system. 

 

-2-2    ELECTRICAL SUPPLY

 

 

If  the  valve  is  powered  by  a  low  voltage  transformer,  make  sure  that  the  power  outlet  cannot  be 

switched off accidentally. Use only the power supply delivered with the valve. 

 

Make sure that the electrical line is protected by a suitable protection 

 

If  the  electrical  cable  or  the  transformer  housing  is  damaged,  it  must  be  replaced  by a  qualified 

person. 

 

-2-3    WATER SUPPLY

 

 

Existing water line  should be clean and neat, free from  lime scale and iron. It should comply with 

current  regulations.  Make  the  necessary  changes  to  prevent  troubles.  Connection  to  drain  should  not 
exceed 2 meters above the valve, and total length should not exceed 5 meters. 

 

It is strongly recommended to install a pre-filter upstream to the system. 

 

-2-4    BYPASS

 

 

It is strongly recommended to install a bypass on the system if the valve does not include one from 

manufacturing 

 

-2-5   TEMPERATURE

 

 

Air and water temperature should not exceed 45°C.Temperature should not fall below 1°C. Freezing 

can break or strongly damage the equipment and cause major water leaks. 

 

-2-6   INSTALLATION OF THE SYSTEM

 

 

Install the system and its brine tank, shielded from the rain and from an excessive humidity on a 

flat, solid, horizontal and smooth floor. 

 

Connection of equipment to water line should be done by a qualified person, according to current 

applicable regulations. 

 

During installation, brasing operations should be made with no equipment in place. Excessive heat 

can cause several damages to the equipment. 

 

The brine tank overflow outlet must be connected to the sewer system. 

 

 

 

 

 

 

 

 

15                                                                 04/04/18

Summary of Contents for INO20

Page 1: ...Model INO20 Time clock Metered SERVICE MANUAL 1 04 04 18...

Page 2: ...SCRIPTION EQUIPMENT ADJUSTMENTS P 14 2 INSTALLATION INSTRUCTIONS P 15 3 INITIAL SET UP P 16 4 USER INTERFACE P 18 5 TROUBLESHOOTING P 19 6 ERROR MESSAGES P 20 7 SPARE PARTS P 21 8 DIMENSIONS SPECIFICA...

Page 3: ...ty kg Regeneration Mode Adjustment Time clock days Metered immediate m Metered delayed m Other m Regeneration Type Down flow brining Up flow brining 1 Backwash min 1 Brining rinse min 2 Brining rinse...

Page 4: ...d be clean and neat free from lime scale and iron It should comply with current regulations Make the necessary changes to prevent troubles Connection to drain should not exceed 2 meters above the valv...

Page 5: ...3 INITIAL SET UP View Access to main features Mixing device B rine tube connexion Analysis taps Hard water inlet Treated water outlet Drain hose barb Bypass Lever 16 04 04 18...

Page 6: ...cure the assembly of the tube Tighten the clamp moderately to prevent over stress 3 6 Connect the brine tube to the valve Use a 9 52 3 8 OD tube Assembly with the quick connection system fitted on the...

Page 7: ...king stops after adjustment 4 2 DISPLAY THE REMAINING VOLUME METERED SYSTEM ONLY Press Next step to switch from time of day to remaining volume Press again to switch back 4 3 INITIATE A REGENERATION P...

Page 8: ...tore the power supply by a professional 4 Verify that the volume decreases when water is used flow indicator runs Verify cable connection and its state Clean up or replace the turbine 5 Contact your i...

Page 9: ...motor operation no short sircuit Drive force too high foreign material damaged part Inspect valve body drive force state of main seals spacers and piston foreign material Er21 to 29 blinking Valve op...

Page 10: ...Kj 34 Eo 521 25mm ou 569 27mm Verification Each year Replacement Every 5 years Inlet outlet seal kit Ref Kj 34 Eo 518 LR20 Alkaline batteries Ref Ba 20 D0 535 Replacement frequency 1 regeneration per...

Page 11: ...View remove screw to access the battery ies 9 DIMENSIONS SPECIFICATIONS SCA 19 STANDARD INO20 STANDARD 22 04 04 18...

Page 12: ...ompliant upon request Minimum pressure in service 2 Bar Maximum pressure in service 8 Bar Static maximum pressure 14 Bar Minimum temperature in service 1 C Maximum temperature in service 45 C except h...

Reviews: