Foster ECORPO G3 EP1/2H Service Manual Download Page 8

8

www.fosterrefrigerator.com

Service Level Parameters

M

nemomic

Description

MDL

Do not adjust

SPL

Minimum limit for SetPoint 
setting

SPH

Maximum limit for SetPoint 
setting

SP

Setpoint

 Temperature value to be maintained in the product

HY0

Thermostat OFF -> ON 
differential

 In Cooling Mode - ‘MDL’ = ‘HYS’

HY1

Do not adjust

CMD

Compressor start delay ‘run’ 
mode

The time between mains power being applied and the compressor starting when in ‘run’ 
mode (i.e. following a mains power cut)

CRT

Compressor rest time

Minimum time compressor is switched off following cycle operation (i.e. pull down, hot 
gas defrost)

CT1 Compressor output on time

Followed by ‘CT2’ when probe Ta (T1) is faulty

CT2 Compressor output off time

Followed by ‘CT1’ when probe Ta (T1) is faulty

PB

Do not adjust

IT

Do not adjust

DT

Do not adjust

CT

Do not adjust

AR

Do not adjust

CMS

Do not adjust

CRS

Do not adjust

CRD

Do not adjust

CDS

Do not adjust

CFF

Do not adjust

CSS

Do not adjust

CSO

Do not adjust

CST

Do not adjust

DFM

Defrost start mode
Defrost start mode

‘NON’ - defrost function is disabled - no defrosts will occur

‘TIM’ - Time. Defrosting occurs on a time base determined by ‘DFT’, accumulated only in 
run mode

‘FRO’ - Do not use

‘DoD’  - Do not use

‘TAD’ - Do not use

DFT

Time interval between defrosts When this time has elapsed since the previous defrost (in run mode), a new defrost cycle 

is initiated

DSP

Do not adjust

DST

Do not adjust

DMI

Do not adjust

DLI

Defrost end temperature

DTO Maximum defrost duration

DTY

Defrost type

‘OFF’ - Off cycle defrost (Compressor and Heater OFF)

‘ELE’ - Electric defrost (Compressor OFF and Heater ON)

‘GAS ‘ - Hot gas defrost (Compressor and Heater ON)

DSY

Defrost start synchronization

‘OFF’ - none. The defrost will occur without delay

‘LO’ - defrost start will be postponed to compressor cut-out (SOD = max delay)

HI’ - defrost start will be postponed to compressor cut-in (SOD = max delay)

SOD

Do not adjust

DPD

Evaporator pump down

At the beginning of defrost, defrost outputs (determined by ‘DTY’) are ‘OFF’ for ‘DPD’ 
seconds

DRN

Pause after defrost (evaporator 
drain down time)

DDM

Defrost display mode.

RT’ - the real / actual temperature

LT’ - the last temperature displayed before defrost initiation

SP’ - the setpoint value

dEF’ - ‘dEF’

Service Level Menu

To access service level menu, press button 3 then press and hold buttons 2 and 4 for 5 seconds and the display will show ‘MDL’.  Press button 3  to 

display the current value.  If it is required to amend the value use buttons 2 and 4 followed by button 3 to save the new value.

Summary of Contents for ECORPO G3 EP1/2H

Page 1: ...Service Manual EP1 2H EP1 2HRW EP1 2M EP1 2L EP1 3H EP1 3HRW EP1 3M EP1 3L EP1 4H EP1 4HRW EP2 2H EP2 3H Counters...

Page 2: ...your appliance Service Function Parameters Alarm Indicators Probe Data Relay Test Factory Reset Wiring Diagrams Maintenance Welcome to your interactive Foster service manual Here s how it works To re...

Page 3: ...the defrost process The worktop should not be sat or stood on Where the appliance is fitted with drawers these should not be used as a step to assist or gain height Where the appliance is fitted with...

Page 4: ...appliance produces warm air when operating normally and requires adequate ventilation The dimensions indicated are a minimum As the operating temperature has been pre set no adjustments are required A...

Page 5: ...ernal temperature and button 3 Icon Button 1 Compressor running 1 Information menu 2 Keypad locked 2 Increase value 3 Evaporator fans running 3 Standby Exit Confirm 4 Defrost in progress 4 Decrease va...

Page 6: ...store product on the base of the appliance please contact the Foster parts team to purchase the necessary shelf and spacers Always ensure air can circulate around through the stored product It is impo...

Page 7: ...e If it is required to amend the value use buttons 2 and 4 followed by button 3 to save the new value User Level Parameters Mnemonic Description SP Appliance Set Point Loc Keypad Lock tA Actual air pr...

Page 8: ...DFT accumulated only in run mode FRO Do not use DoD Do not use TAD Do not use DFT Time interval between defrosts When this time has elapsed since the previous defrost in run mode a new defrost cycle i...

Page 9: ...essor stop FT2 Timed fan stop When FT2 0 the fans remain on all the time FT3 Timed fan run When FT3 0 and FT2 0 the fans remain OFF all the time ATM Alarm threshold management NON all temperature alar...

Page 10: ...ler R1 Do not use R1F Do not use R1 Do not use FAN Output enabled for evaporator fan switching FAN Do not use DEF Output enabled for defrost switching DEF Do not use ALO Contacts open when an alarm co...

Page 11: ...ed rate of change toward setpoint actual value away from setpoint mathematical algorithm applied A E the AVG weighted average between TAir T1 and TEvaporator T2 probes T3 TAuxiliary T3 probe value whe...

Page 12: ...0 20 15 20 DTY OFF OFF OFF GAS GAS OFF ELE DSY OFF OFF OFF HI HI OFF HI SOD 10 5 5 5 5 5 5 DPD 0 0 0 0 0 0 0 DRN 60 0 0 90 90 0 90 INTEGRAL REMOTE Mnemonic Default High Temperature Counter Solid Doors...

Page 13: ...DI1 DOR NON NON NON NON NON NON D1A OPN OPN OPN OPN OPN OPN OPN LCM NON NON MAN NON NON NON NON SR1 NON FAN FAN FAN FAN FAN FAN SR2 NON NON LGT DEF DEF NON DEF RL2 NON 0 1 0 1 0 1 0 1 0 1 0 1 ACN 0 0...

Page 14: ...dealer or Foster Service tA Air probe has failed Call your authorised dealer or Foster Service to arrange for this to be replaced During this time the appliance cannot maintain an accurate temperature...

Page 15: ...522 113 347 117 294 25 84 823 87 559 90 374 20 66 27 68 237 70 255 15 52 229 53 65 55 104 10 41 477 42 506 43 557 5 33 147 33 892 34 651 0 26 678 27 219 27 767 5 21 63 22 021 22 417 10 17 643 17 926...

Page 16: ...ance Where this is not available please refer to the table below The information below is correct time of printing but is subject to change without prior notice EP1 2H 110gms EP1 2HRW 110gms EP1 2M 80...

Page 17: ...rameter DTO or the temperature set in parameter DLI is reached Where parameter TE is set to NO defrost will function on a time basis only Upon completion of the defrost cycle the appliance will resume...

Page 18: ...skets Door gaskets should be inspected periodically and cleaned where necessary with a warm damp cloth Do not use aggressive cleaning materials on the door gaskets Where door gaskets are damaged or no...

Page 19: ...19 G3 Counters Service Manual Wiring Diagrams EP1 2H EP1 2HRW EP1 3H EP1 3HRW EP1 4H EP1 4HRW Integral Condensing Unit...

Page 20: ...20 www fosterrefrigerator com EP1 2H EP1 2HRW EP1 3H EP1 3HRW EP1 4H EP1 4HRW Remote Condensing Unit...

Page 21: ...21 G3 Counters Service Manual EP1 2L EP1 3M EP1 3L Integral Condensing Unit...

Page 22: ...22 www fosterrefrigerator com EP1 2L EP1 3M EP1 3L Remote Condensing Unit...

Page 23: ...23 G3 Counters Service Manual EP2 2H EP2 3H Integral Condensing Unit...

Page 24: ...24 www fosterrefrigerator com EP2 2H EP2 3H Remote Condensing Unit...

Page 25: ...25 G3 Counters Service Manual...

Page 26: ...26 www fosterrefrigerator com...

Page 27: ...27 G3 Counters Service Manual...

Page 28: ...sterrefrigerator com Document ID code 00 570506 v2 By Appointment to Her Majesty Queen Elizabeth II Suppliers of Commercial Refrigeration Foster Refrigerator King s Lynn For service and spares For ser...

Reviews: