Controller Menu’s

The controller contains 2 menu levels, user level and service level.

User Level Menu

To access user level settings, press button 3 and then press button 1.  The display will show ‘SP’.  Use buttons 2 and 4 to display the parameter 

required.  Press button 3  to display the current value.  If it is required to amend the value use buttons 2 and 4 followed by button 3 to save the new 

value.

User Level Parameters

M

nemonic

Description

SP

Appliance Set Point

Loc

Keypad Lock

tA

Actual air probe value

tE

Actual evaporator probe value (Not enabled on all models)

tLo

Minimum air temperature during previous 24 hours

tHi

Maximum air temperature during previous 24 hours

dEF

Time until next scheduled defrost.  Displayed in tenths of hours.  For example 05.4 = 5 hours 40 minutes

tdy

Display resolution

Service Function

2

Summary of Contents for ECORPO G3 EP1/2H

Page 1: ...Service Manual EP1 2H EP1 2HRW EP1 2M EP1 2L EP1 3H EP1 3HRW EP1 3M EP1 3L EP1 4H EP1 4HRW EP2 2H EP2 3H Counters...

Page 2: ...your appliance Service Function Parameters Alarm Indicators Probe Data Relay Test Factory Reset Wiring Diagrams Maintenance Welcome to your interactive Foster service manual Here s how it works To re...

Page 3: ...the defrost process The worktop should not be sat or stood on Where the appliance is fitted with drawers these should not be used as a step to assist or gain height Where the appliance is fitted with...

Page 4: ...appliance produces warm air when operating normally and requires adequate ventilation The dimensions indicated are a minimum As the operating temperature has been pre set no adjustments are required A...

Page 5: ...ernal temperature and button 3 Icon Button 1 Compressor running 1 Information menu 2 Keypad locked 2 Increase value 3 Evaporator fans running 3 Standby Exit Confirm 4 Defrost in progress 4 Decrease va...

Page 6: ...store product on the base of the appliance please contact the Foster parts team to purchase the necessary shelf and spacers Always ensure air can circulate around through the stored product It is impo...

Page 7: ...e If it is required to amend the value use buttons 2 and 4 followed by button 3 to save the new value User Level Parameters Mnemonic Description SP Appliance Set Point Loc Keypad Lock tA Actual air pr...

Page 8: ...DFT accumulated only in run mode FRO Do not use DoD Do not use TAD Do not use DFT Time interval between defrosts When this time has elapsed since the previous defrost in run mode a new defrost cycle i...

Page 9: ...essor stop FT2 Timed fan stop When FT2 0 the fans remain on all the time FT3 Timed fan run When FT3 0 and FT2 0 the fans remain OFF all the time ATM Alarm threshold management NON all temperature alar...

Page 10: ...ler R1 Do not use R1F Do not use R1 Do not use FAN Output enabled for evaporator fan switching FAN Do not use DEF Output enabled for defrost switching DEF Do not use ALO Contacts open when an alarm co...

Page 11: ...ed rate of change toward setpoint actual value away from setpoint mathematical algorithm applied A E the AVG weighted average between TAir T1 and TEvaporator T2 probes T3 TAuxiliary T3 probe value whe...

Page 12: ...0 20 15 20 DTY OFF OFF OFF GAS GAS OFF ELE DSY OFF OFF OFF HI HI OFF HI SOD 10 5 5 5 5 5 5 DPD 0 0 0 0 0 0 0 DRN 60 0 0 90 90 0 90 INTEGRAL REMOTE Mnemonic Default High Temperature Counter Solid Doors...

Page 13: ...DI1 DOR NON NON NON NON NON NON D1A OPN OPN OPN OPN OPN OPN OPN LCM NON NON MAN NON NON NON NON SR1 NON FAN FAN FAN FAN FAN FAN SR2 NON NON LGT DEF DEF NON DEF RL2 NON 0 1 0 1 0 1 0 1 0 1 0 1 ACN 0 0...

Page 14: ...dealer or Foster Service tA Air probe has failed Call your authorised dealer or Foster Service to arrange for this to be replaced During this time the appliance cannot maintain an accurate temperature...

Page 15: ...522 113 347 117 294 25 84 823 87 559 90 374 20 66 27 68 237 70 255 15 52 229 53 65 55 104 10 41 477 42 506 43 557 5 33 147 33 892 34 651 0 26 678 27 219 27 767 5 21 63 22 021 22 417 10 17 643 17 926...

Page 16: ...ance Where this is not available please refer to the table below The information below is correct time of printing but is subject to change without prior notice EP1 2H 110gms EP1 2HRW 110gms EP1 2M 80...

Page 17: ...rameter DTO or the temperature set in parameter DLI is reached Where parameter TE is set to NO defrost will function on a time basis only Upon completion of the defrost cycle the appliance will resume...

Page 18: ...skets Door gaskets should be inspected periodically and cleaned where necessary with a warm damp cloth Do not use aggressive cleaning materials on the door gaskets Where door gaskets are damaged or no...

Page 19: ...19 G3 Counters Service Manual Wiring Diagrams EP1 2H EP1 2HRW EP1 3H EP1 3HRW EP1 4H EP1 4HRW Integral Condensing Unit...

Page 20: ...20 www fosterrefrigerator com EP1 2H EP1 2HRW EP1 3H EP1 3HRW EP1 4H EP1 4HRW Remote Condensing Unit...

Page 21: ...21 G3 Counters Service Manual EP1 2L EP1 3M EP1 3L Integral Condensing Unit...

Page 22: ...22 www fosterrefrigerator com EP1 2L EP1 3M EP1 3L Remote Condensing Unit...

Page 23: ...23 G3 Counters Service Manual EP2 2H EP2 3H Integral Condensing Unit...

Page 24: ...24 www fosterrefrigerator com EP2 2H EP2 3H Remote Condensing Unit...

Page 25: ...25 G3 Counters Service Manual...

Page 26: ...26 www fosterrefrigerator com...

Page 27: ...27 G3 Counters Service Manual...

Page 28: ...sterrefrigerator com Document ID code 00 570506 v2 By Appointment to Her Majesty Queen Elizabeth II Suppliers of Commercial Refrigeration Foster Refrigerator King s Lynn For service and spares For ser...

Reviews: