8. Troubleshooting
8.2 Troubleshooting Signal Quality
TIP
If the described options do not help to fix the problem:
u
Contact fos4X Support. See
Table 44: Troubleshooting Signal Quality
Signal Quality
Status codes
Solution
Temperature Low
or
Temperature High
u
Make sure to operate
within specification. See
Environmental Conditions,
page 15
Signal Level Low
or
Signal Level High
u
Clean the optical connectors.
See
.
u
Reboot the Blackbird OECD.
Turn the power supply off and
on.
Signal Warning
Wavelength Low
or
Wavelength High
u
Make sure that connected
sensors are within the
measuring range. See
Measurement and Sensors,
page 13
u
Make sure that only permitted
sensors are connected. See
Measurement and Sensors,
page 13
Temperature Too
Low
or
Temperature Too
High
u
Make sure to operate
within specification. See
Environmental Conditions,
page 15
Signal Error
Signal Level Too
Low
or
Signal Level Too
High
u
Clean the optical connectors.
See
.
u
Reboot the Blackbird OECD.
Turn the power supply off and
on.
64 / 83
MDE1117_4-10_1.3.x_5.0_Blackbird
OECD_(6Ch, CNO)-en-us
© fos4X 2020