2. No Signal
3. Alarm LED On
4. 4-20 MA at 0 ma
If IDD detector is disconnected, ALM LED will turn on, but to differentiate with ALARM Condition, WDT
On Self check Cycle failure, only ALM LED will turn on.
TROUBLESHOOTING
4.2
Self Check
Cycle Fail
ALM LED ON
IDD CK FAIL Message
IDD Signal Too High
(>3000) leading to Sensor
Saturation
Reduce Gain, Weight Factor,
Adjust sighting
Drop count (DO) too low Increase Dropout count value
towards Pickup count.
High Gain Value / Weight
Factor Value
Reduce Gain / WF Value
50VDC bias LED1
Steady ON during
Check-cycle
50 V bias voltage does
not go to 0 VDC during
self-Check duration
Replace IDDX
Contact Forney Support
Sensor
Disconnect
ALM LED ON
WDT LED Flashing
Loss of IDD Detector
Signal
Check wires on J1 Connector.
Check quick disconnect of IDD
detector is secure.
Check Detector cable wiring
for continuity.
Loss of 15VDC.
LED11 is Off.
Replace IDDX
25