19
372001-24 Rev. B
intensity.
The IDD ANALOG OUTS screen shows the programmed values for the IDD analog output low and high
points. Plus, it displays the pick-up and dropout points that were just programmed in the last section for
reference. The Analog Output HI and LO will set the 0-10V and 4-20mA outputs and can be set to yield
the most information to almost nothing more than ON/OFF. To convey the most information, set the HI
to the actual high displayed on the IDD Signal screen and the low to a value lower than the dropout (DO)
F4 - OK
F2 - LO - type in “300”
F4 - OK
The 4-20 output is not to be considered a calibrated output, to this end the output scale from the
factory is set at a default value of 3000 well beyond the usable range. In order to acquire a reasonably
discrimination adjust these ranges as described above.