41
Parameter
Settable values
Default values
notes
P0 - TSP0
Boiler type selection
0, 1, 2, 3, 4, 5, 6, 7
1
0 = 12 kW natural gas; 1 = 24 kW natural gas;
2 = 28 kW natural gas; 3 = 24 kW propane;
4 = 28 kW propane; 5 = 12 kW propane;
6 = 32 kW natural gas; 7 = 32 kW propane.
P3 - TSP3
Boiler type selection
1 ÷ 3
1
1 = combi instantaneous, 2 = heating only,
3 = with water cylinder
P4 - TSP4
Fan speed at burner maximum output
Value of P5 ÷ 250
Hz
199
187 = 12 kW natural gas; 199 = 24 kW natural gas;
201 = 28 kW natural gas; 192 = 24 kW propane;
198 = 28 kW propane; 185 = 12 kW propane;
210 = 32 kW natural gas; 205 = 32 kW propane.
P5 - TSP5
Fan speed at burner minimum output
25 ÷ 120 Hz
42
39 = 12 kW; 42 = 24 kW; 40 = 28 kW; 43 = 32 kW
P6 - TSP6
Fan speed at ignition power
25 ÷ 160 Hz
58
48 = 12 kW; 58 = 24 kW; 60 = 28 kW; 76 = 32 kW
P7 - TSP7
Fan speed at heating maximum output
10 ÷ 100%
88
75 = 12 kW; 88 = 24 and 32 kW; 87 = 28 kW
P8 - TSP8
Negative ramp start minimum speed
P5 ÷ P6
56
56 = 12 and 24 kW; 60 = 28 kW and 32 kW
P9 - TSP9
Negative ramp time
0 ÷ 30 (1 = 10 sec.)
18 (180 sec.)
18 = 12, 24 and 32 kW; 25 = 28 kW
P10 - TSP10
Heating output curves
0 ÷ 3
1.5
P11 - TSP11
Heating thermostat timing
0 ÷ 10 min.
4
P12 - TSP12
CH power rising ramp timer
0 ÷ 10 min.
1
P13 - TSP13
Timing of post-circulation, heating, anti-freeze, flue
cleaning adjustable
30 ÷ 180 sec.
30
P14 - TSP14
Setting of DHW standard or solar thermostats
0 ÷ 1
0
0 = normal
1 = solar
P15 - TSP15
Anti water hammer delay settable
0 ÷ 3 sec.
0
P16 - TSP16
Ambient thermostat reading delay / OT
0 ÷ 199 sec.
0
P17 - TSP17
Multifunction relay setting
0 ÷ 3
0
0 = shutdown and failure; 1 = remote relay / TA1;
2 = solar relay; 3 = TA2 request
Solar par
amet
ers (with P17=2 or with supplemen
tar
y boar
d)
P18 - TSP18
Solar plant type selection
0 ÷ 1
0
0 = solar valve; 1 = solar pump
P19 - TSP19
Water cylinder set-point setting
10 ÷ 90 °C
60 °C
only with P18 = 1
P20 - TSP20
∆T ON (diff. solar pump ignition)
1 ÷ 30 °C
6 °C
P21 - TSP21
∆T OFF (diff. solar pump shutdown)
1 ÷ 30 °C
3 °C
P22 - TSP22
Maximum collector temperature
80 ÷ 140 °C
120 °C
P23 - TSP23
Minimum collector temperature
0 ÷ 95 °C
25 °C
P24 - TSP24
Solar collector anti-freeze
0 ÷ 1
0
0 = anti-freeze not enabled; 1 = anti-freeze enabled
(only with P18 = 1)
P25 - TSP25
Solar load forcing
0 ÷ 1
0
0 = automatic operation; 1 = always enabled
P26 - TSP26
Enabling of Water cylinder cooling
0 ÷ 1
0
0 = disabled; 1 = enabled
(only with P18 = 1)
P27 - TSP27
Heating timer reset temperature
20 ÷ 78 °C
P10 < 1 (low temp.) = 20 °C
P10 > 1 (high temp.) = 40 °C
P29 - TSP29
Setting of default parameters (except P0, P1, P2, P17)
0 ÷ 1
0
0 = OFF; 1 = default
Displa
y only
P30
External temperature
only with external probe connected
P31
Flow temperature
P32
Nominal calculated flow temperature
only with external probe connected
P33
Set point of zone 2 flow temperature
only with at least one zone board connected
3.2.15.
TSP parameters that can be set from interface or Remote Control