Fonderie SIME RX 26 BF Installer'S Instructions Download Page 9

4.1

C.H. OUTPUT REGULATION

When  the  boiler  is  fuelled  with  natural  gas

(G20),  it  is  possible  to  change  the  maxi-

mum  pressure  value  according  to  the  dia-

gram  shown  in  fig.  13  in  order  to    adjust

C.H. output  to the thermal requirements of

the system.

If  the  pressures  need  to  be  corrected  fol-

low the indications in section 4.3.1. In order

to avoid the variation of the minimum pres-

sure lock the adjusting screw (2 fig. 11/a).

4.2

GAS VALVE 

(fig. 11)

The boilers are equipped standard with the

HONEYWELL VK 4105Q gas valve.

Gas  pressure  calibration  is  carried  out  by

SIME  on  the  production  line  and  foresees

the  minimum  C.H.output  at  23,2  kW  and

the maximum C.H.output at 31,0 kW.

If  the  pressures  are  checked  only  at  the

burner, connect the pressure gauge as indi-

cated in fig. 12. If corrections are required

refer to section 4.3.1.

4.3

GAS CONVERSION 

This  operation  must  be  performed  by

authorised  personnel  using  original  Sime

components. 

To convert from natural gas to LPG or vice

versa, perform the following operations:

– Close the gas cock.

– Replace  the  principal  nozzles  and  the  ø

10  aluminium  washers  included  in  kit

(use  a  12  wrench  in  order  to  carry  out

this operation).

At  start-up  change  the  starting  pres-

sure  (STEP)  of  the  gas  valve  by  posi-

tioning  the  index  of  the  screw  accord-

ing to the type of gas, as mentioned in

fig. 11.

– To  set  the  values  of  maximum  and  mini-

mum  gas  pressure,  follow  the  instruc-

tions given in section 4.3.1.

Seal  the  regulators  after  the  operating

pressure values have been changed.

– After  have  ultimated  the  conversion  of

the  boiler,  please  stick  onto  the  casing

panel  the  plate  showing  the  relevant

feeding gas which is included into the kit.

NOTE:  When  reassembling  components

which  you  have  removed,  replace  gas

seals;  test  all  gas  connections  after

assembly using soapy water or a product

made  specifically  for  the  purpose,  being

sure not to use open flame. 

4.3.1

Adjusting valve pressures

For  maximum  and  minimum  pressure  cali-

bration  follow  the  procedure  listed  below

(fig. 11/a):

– Connect  the  column  or  a  manometer  to

the  intake  downstream  of  the  gas  valve

(4 fig. 11).

Disconnect the valve VENT pressure test

point tube (5 fig. 11).

– Remove the cap (3) from the modulator.

– Place  the  boiler  stat  knob  at  the  maxi-

mum position.

– Turn on the boiler.

– Remember  that  rotating  clockwise  will

increase  pressure  while  rotating  anti-

clockwise will diminish it. 

– Check  the  gas  inlet  pressure  at  the  rele-

vant  pressure  test  point  (3  fig.  11)  with

the boiler running at the maximum output.

– Regulate the maximum pressure by turn-

ing  the  nut    with  a  fixed  wrench  (1)

searching  for  the  maximum  pressure

Table  3

,  or,  for  the  natural  gas  (G20),  if

44

4

USE AND MAINTENANCE

KEY
1

Maximum pressure adjusting nut

2

Minimum pressure adjusting screw

3

Plastic cap

Fig. 11/a

2

1

3

5

4

6

G20

G30-G31

Fig. 11

KEY
1

Modulator

2

EV1-EV2 coils

3

Pressure inlet upstream

4

Pressure inlet downstream

5

VENT pressure test point

6

STEP

Fig. 12

TABLE 3

Type of gas

Burner max. pressure

Burner min. pressure

mbar

mbar

Methane (G20)

12,0

7,1

Butane (G30)

28,1

17,8

Propane (G31)

35,9

17,8

SEALED CHAMBER

VENT PRESSURE TEST POINT

PRESSURE INLET DOWNSTREAM

MANOMETER

Summary of Contents for RX 26 BF

Page 1: ...ype of gas supplied Check that the flue pipe for the outlet of the products of the combustion is unobstructed and or has been properly installed Make sure that any shutoff valves are open Make sure th...

Page 2: ...BF Heat output min nom kW 23 2 31 0 kcal h 19 950 26 660 Heat input min nom kW 26 2 34 0 kcal h 22 530 29 240 Cast iron sections n 4 Water content l 15 Power consumption W 155 Maximum water head bar...

Page 3: ...ty valve goes into action When sizing gas piping from the meter to the boiler take into account both the volume flow rates consumption in m3 h and the relative density of the gas in question The secti...

Page 4: ...The boiler is supplied with the connections required for coaxial ducts that can be turned in any direction The maximum horizontal length of the duct must not exceed 2 8 meters Maximum two extensions c...

Page 5: ...alculation in that the sum of the head losses of the single fittings is less than 6 00 mm H2O Intake Outlet 6 meter horizontal pipe 80 x 0 20 1 20 6 meter horizontal pipe 80 x 0 40 2 40 n 2 90 elbows...

Page 6: ...o 35 kW distances in mm A below openable window 600 B below ventilation opening 600 C below eaves 300 D below balcony 1 300 E from adjacent window 400 F from adjacent ventilation opening 600 G from ho...

Page 7: ...nected to an efficient eathing system SIME cannot be held liable for damage to people or things that is due to non earthing of the boiler Always turn off the power supply before doing any work on the...

Page 8: ...continuos spark ing even if the burner is on After 10 sec onds the sparking stops and so does the burner while the lock out lamp appears to be on It occurs if the phase and neutral position on the te...

Page 9: ...ating pressure values have been changed After have ultimated the conversion of the boiler please stick onto the casing panel the plate showing the relevant feeding gas which is included into the kit N...

Page 10: ...operation The fan works but with less revolutions and therefore it does not enable the flue gas pressure switch replace it The principal burner does not burn prop erly flame too high yellow flame Mak...

Page 11: ...e if it is lower than 1 bar When the operation is over close the fill up cock GAS CONVERSION If the gas that is to be used if different than the one that the boiler has been prearran ged for contact a...

Reviews: