Fonderie SIME RX 26 BF Installer'S Instructions Download Page 7

2.10

ELECTRICAL 

WIRING

If  you  must  replace  the  electric  power

cable supplied with the boiler, order it exclu-

sively from Sime.

The  power  supply  must  be  single-phase

230V  -  50  Hz  through  a  main  switch  pro-

tected by a fuse with a distance of at least

3 mm between contacts.

Use only class II room thermostats in com-

pliance with the EN 60730 regulations 

NOTE:  Device  must  be  connected  to  an

efficient eathing system. SIME cannot be

held liable  for damage to people or things

that is due to non-earthing of the boiler.

Always  turn  off  the  power  supply  before

doing any work on the electrical panel.

42

Fig. 7

2.10.1 Wiring diagram

KEY
A

Control box 

ER

Detection electrode

EA

Ignition electrode

EV1

Gas valve coil

EV2

Gas valve coil

V

Fan

PF

Smoke pressure switch

TS

Safety stat

SB

Cotrol box lock-out

TC

Boiler stat

M

Modulator

IG

Main switch

PI

C.H. pump

TA

Room stat

NOTE: Remove jumper 1-4 on the terminal board
while connecting the room thermostat (TA). 

Summary of Contents for RX 26 BF

Page 1: ...ype of gas supplied Check that the flue pipe for the outlet of the products of the combustion is unobstructed and or has been properly installed Make sure that any shutoff valves are open Make sure th...

Page 2: ...BF Heat output min nom kW 23 2 31 0 kcal h 19 950 26 660 Heat input min nom kW 26 2 34 0 kcal h 22 530 29 240 Cast iron sections n 4 Water content l 15 Power consumption W 155 Maximum water head bar...

Page 3: ...ty valve goes into action When sizing gas piping from the meter to the boiler take into account both the volume flow rates consumption in m3 h and the relative density of the gas in question The secti...

Page 4: ...The boiler is supplied with the connections required for coaxial ducts that can be turned in any direction The maximum horizontal length of the duct must not exceed 2 8 meters Maximum two extensions c...

Page 5: ...alculation in that the sum of the head losses of the single fittings is less than 6 00 mm H2O Intake Outlet 6 meter horizontal pipe 80 x 0 20 1 20 6 meter horizontal pipe 80 x 0 40 2 40 n 2 90 elbows...

Page 6: ...o 35 kW distances in mm A below openable window 600 B below ventilation opening 600 C below eaves 300 D below balcony 1 300 E from adjacent window 400 F from adjacent ventilation opening 600 G from ho...

Page 7: ...nected to an efficient eathing system SIME cannot be held liable for damage to people or things that is due to non earthing of the boiler Always turn off the power supply before doing any work on the...

Page 8: ...continuos spark ing even if the burner is on After 10 sec onds the sparking stops and so does the burner while the lock out lamp appears to be on It occurs if the phase and neutral position on the te...

Page 9: ...ating pressure values have been changed After have ultimated the conversion of the boiler please stick onto the casing panel the plate showing the relevant feeding gas which is included into the kit N...

Page 10: ...operation The fan works but with less revolutions and therefore it does not enable the flue gas pressure switch replace it The principal burner does not burn prop erly flame too high yellow flame Mak...

Page 11: ...e if it is lower than 1 bar When the operation is over close the fill up cock GAS CONVERSION If the gas that is to be used if different than the one that the boiler has been prearran ged for contact a...