3. Selection of the power generator. 

 

 

If this happens, wait for a while, eliminate the cause 
of  the  overload,  then  reconnect  the  switch  by 
pressing it.

 

The  switches  are  selected  according  to  the  technical 

parameters  of  the  generator;  if  you  need  to  replace 
them in  case  of  damage,  use  only original  parts of with 
identical current ratings.

 

 

SELECTING PROPER POWER GENERATOR 

FOR THE RECEIVER 

Devices with electric motors.

 

Star connection 

- power of the power generator 

may be up to 3 times higher than the rated power 
of the receiver. 

Delta connection 

- power of the power 

generator may be up to 9 higher than the rated 
power of the receiver.  

Star / delta connection (softstart)

- the power 

of the generator, up to 3 times higher than the 
rated power of the receiver.

 

With inverter

, the power of the generator - up to 

1.5 times higher than the rated power of the 
receiver.  

Commutator connections (power tools) 

- the 

power of the generator at least 1.2 times higher 
than the rated power of the receiver.

 

Heating equipment

 

Power of the generator at least 1.2 times higher 
than the rated power of the receiver.

 

Lighting

 

Incandescent - power of the generator is up to 
1.2 times higher than the rated power of the 
heaters.

 

Sodium - power of the generator is up to 5 times 
higher than the rated power of the bulb.

 

UPS

 

Power  of  the  generator  up  to  1.7  times  larger 
than the power rating of connected receivers.

 

 

Electronic devices

 

Power  of  the  generator  at  least  1.2  times  larger 
than the rated power of receivers.

 

 

NOTE: In order to accurately select the 
power generator for the receiver, a 
qualified electrician must perform 
electrical measurements of the electrical 
switchboard, at the start-up of the device.

 

 
Voltage of idle gear of generators is max. 253 V. 
At  the  rated  load,  the  voltage  should  not  fall 
below 207 V.

 

 

NOTE:  Receivers  sensitive  to  too 
low  or  too  high  voltages  may  be 
damaged  when  powered  from 
power generating sets.

 

ENVIRONMENTAL PROTECTION

 

 Symbol  indicating  the  selective 
collection  of  waste  electrical  and 
electronic 

equipment. 

Used 

electrical  appliances  are  secondary 
raw materials 
-  do  not  dispose  of  them  with 

household  waste,  as  they  contain  substances 
harmful to human health and the environment!

 

Actively  help  to  responsibly  manage  natural 
resources  and  protect  the  environment  by 
passing the used device to the point dedicated for 
used  electric  appliances.  To  reduce  the  waste 
amount,  it  is  necessary  to  reuse,  recycle  or 
recover materials in a different form.

 

10.

 

Summary of Contents for FH 9000

Page 1: ...FH9220W FH9540TR FH9540TRA FH9540TRE FH9540 BRIGGS FV10001CRA FV10001TE FV10001TRA FV10001TRE FV10300TWE FV10300WE FV11300TWE FV11001CRA FV11001TE FV11001TRA FV11001TRE FV13000CRA FV13000TE FV13000TR...

Page 2: ...illegible or destroyed contact your Authorized Dealer of FOGO Sp z o o in order to replace them with new ones We strongly recommend carefully reading and understanding the safety rules included in ou...

Page 3: ...generator it is essential to read these instructions The buyer of the power generator must ensure that this manual is always available for its operator and that every user reads the manual before sta...

Page 4: ...Delivery unloading storage 11 5 Disposal 11 6 Operation 13 Starting 13 Stopping 17 7 Repair maintenance 19 List of maintenance operations 19 Maintenance methods 19 Faults 22 8 Maintenance 23 List of s...

Page 5: ...t breaker electric starter and the battery The optional accessories include working hour meter grounding set transport kit a hose for the exhaust system welding wires units with a welding module autom...

Page 6: ...peration The drive from the engine is transmitted through a tapered connection and threaded rod Alternator housing is made of light aluminium alloys Winding of the rotor and stator is insulated with a...

Page 7: ...of the generator Cooling in these alternators is carried out by forced air circulation in slots outside the alternator 4 6 safe 8 9 10 11 12 MARKING OF THE POWER GENERATOR 2 1 13 14 DESCRIPTION OF THE...

Page 8: ...uirements for explosion protection Do not fill the fuel tank while the engine is working RISK OF EXPLOSION Do not start the power generator in case of fuel spillage Restarting is permitted after remov...

Page 9: ...rts Damage to the power cord increases the RISK OF ELECTRIC SHOCK If you work outside enclosed rooms use extension cords intended for use outdoors Using suitable extension cords reduces the RISK OF EL...

Page 10: ...tor in conditions different than the nominal conditions Rated power is specified for specific operational conditions atmospheric pressure of 1 bar air temp of 20 C air humidity of 60 Power drop caused...

Page 11: ...rator is up to 1 2 times higher than the rated power of the heaters Sodium power of the generator is up to 5 times higher than the rated power of the bulb UPS Power of the generator up to 1 7 times la...

Page 12: ...ower generator against dust and corrosion clean the power generator from any dirt Detailed recommendations are presented in manuals provided by manufacturers of the engine alternator and other essenti...

Page 13: ...ous waste includes used objects solids and liquids other than wastewater generated in households commercial facilities unsuitable for the place and time in which they have been generated and burdensom...

Page 14: ...1 Oils shown in Table may be used if the average ambient temperature is within the indicated range For Briggs Stratton Vanguard SE SF SG SAE30 oils may be used Tab 2 Depending on the temperature for...

Page 15: ...e of 12V and a capacity of at least 18Ah built in and non built in single cylinder generators 30Ah non built in two cylinder generators 35Ah built in two cylinder generators Connecting the battery to...

Page 16: ...connection of the battery with faulty reversed polarity will automatically switch off the engine in Honda engines The green indicator in the switch indicates that the switch is turned off Remove the...

Page 17: ...tch engages with the attaching basket located placed on the engine flywheel Vigorously pull the cord If the start up fails repeat until it is successful If the starter cord is pulled by engaging clutc...

Page 18: ...il fuel mixture may overflow the piston and immobilize the engine In such cases remove the spark plug drain oil clean the combustion chamber with compressed air and change the oil VANGUARD CAUTION Whe...

Page 19: ...mum welding current only for a few minutes then it should be left to cool down see the table on the control panel therefore if the work with high welding currents triggers the thermal switch welding s...

Page 20: ...tic conditions especially at high humidity it is recommended to measure the insulation resistance of the alternator using a megohmmeter of 500 V The insulation resistance should be not less than 1 M I...

Page 21: ...er with a new one Replacing the oil filter only the power generators with VANGUARD two cylinder engines Replace the oil filter every 100 operating hours or every season Before installing the new filte...

Page 22: ...g agent and allow drying Cleaning the fuel sump MITSUBISHI engines Set the fuel valve at OFF position closed Remove the fuel sump together with the sealing O ring a fine mesh is installed above it to...

Page 23: ...load 1 The capacitance of the capacitor is too high 2 Excessive engine speed 3 Damaged excitation system 1 Check and replace if necessary 2 Report to the Servicing Department 3 Report to the Servicing...

Page 24: ...vities Engine speed control this activity must be performed by an authorized workshop service Checking the fuel system action performed in an authorised workshop MITSUBISHI FOGO DEFECTS National servi...

Page 25: ...falling very quickly sometimes even after 2 3 weeks Do not use fuel older than 1 month Store a minimum amount of fuel required For a very long storage 1 Drain the fuel from the carburettor to a suitab...

Page 26: ...n metal parts of the power generator It is also recommended for power generators equipped with other types of electrical protection Hose for exhaust system required when working indoors or on a vehicl...

Page 27: ...10 Repair log book 26 REPAIR ORDER NO RECEIPT DATE DATE OF RETURN DESCRIPTION OF FAILURE REPAIR COMMENTS...

Page 28: ...park plugs motor oil Only proper inspections ensure the correct functioning of the device Company selling the power generator Indication of working time counter Description of the fault If the power g...

Page 29: ...park plugs motor oil Only proper inspections ensure the correct functioning of the device Company selling the power generator Indication of working time counter Description of the fault If the power g...

Page 30: ...ion Type Engine No Power generator No Inspection Interval Counter indication Materials Part No Materials Part No Oil Oil Oil filter Oil filter Air filter Air filter Fuel filter Fuel filter Additional...

Page 31: ......

Page 32: ...which will be described in future versions of the manual by the services responsible for the change If you find any transcription errors or inconsistencies in the manual plese report them using the en...

Reviews: