20
FUNCTION
POSSIBLE CAUSE
REMEDY
3
Spark will occur
each second.
No
Ignition components not operating properly.
Check connection between cable & IGNelectrode.
See wiring diagram, p. 23.
Check IGN-electrode spark gap.
See wiring diagram, p. 23.
Check IGN-electrode.
See wiring diagram, p. 23.
Check IGN-cable for damage.
See wiring diagram, p. 23.
Increase distance between IGN-cable and all
metal parts. Shorten IGN-cable if possible or
cover, e.g. silicon hose.
See wiring diagram, p. 23.
No
IGN-sequence stops, no pilot flame. No reaction
to transmitter command. (Controller crashes.)
Press RESET button.
See “Setting the Electronics Code” p. 3.
Add ground wire between pilot burner and valve.
See wiring diagram, p. 23.
Do not coil the IGN-cable.
Shorten IGN-cable if possible (no longer than 900 mm).
See wiring diagram, p. 23.
No
IGN-sequence stops, no pilot flame.
Transmitter command is possible.
Replace receiver batteries with 1.5V “AA” quality
alkaline batteries.
OK