11
F. HORIZONTAL WALL VENT TERMINATION TYPE C11
Flue sizing:
·
Ø100/150 Connector on Appliance for Poujoulat PGI
concentric flue system.
·
Ø100/150 Adaptor for Metaloterm Ontop or Muelink
& Grol concentric flue systems.
·
Ø100/150 Maybe used Through-out
Flue Terminal:
·
Ø100/150
Maximum pipe extension, for outside wall (H).
Curvifocus = 3 X Vertical Pipe Rise (V) . For Ø100/150 flue.
Maximum Permissable run (H) see table below.
Vertical Flue Rise
(V) metres
Max. Horizontal Flue Run, (H) m
for Ø100/150 flue
0.5
1.5
1
3
1.5
4.5
2
6
2.5
7.5
3
9
3.5
10.5
4
12
4.5
12
5
12
5.5
12
6.5
12
7
12
7.5 and over
12
Minimum Vertical Flue Height: 0.5m
Flue Restrictors to be fitted:
·
V/H > 0.5, opening “R” = 75mm.
·
0.5 ≤ V/H ≤ 0.4, opening “R” = 65mm.
·
V/H < 0.4, opening “R” = fully open.
G. VERTICAL ROOF VENT TERMINATION C31
Flue sizing:
·
Ø100/150 Connector on Appliance for Poujoulat PGI
concentric flue system.
·
Ø100/150 Adaptor for Metaloterm Ontop or Muelink &
Grol concentric flue systems.
·
Ø100/150 Maybe used Through-out
Flue Terminal:
·
Ø100/150
Minimum Vertical Flue Height: 0.5m
Maximum Vertical Flue Height: 15m
Flue calculations when using elbows (0-90° permissible), total flue length
maximum = 15m and each bend will equate to ½m, Vertical rise (V) must
be at least twice the Horizontal run (R), i.e. V=2H (or H/V≤½).
Flue Restrictors to be fitted:
·
Ø100/150 Vertical Rise < 2m, Opening “R” = 75mm.
·
Ø100/150 Vertical Rise = 2-5m, Opening “R” = 55mm.
·
Ø100/150 Vertical Rise = 5-7m, Opening “R” = 65mm.
·
Ø100/150 Vertical Rise = 7-12m, Opening “R” = 85mm.
·
Ø100/150 Vertical Rise > 12m, Opening “R” = Fully Open.
H. FLUE RESTRICTOR IDENTIFICATION
NOTE: Fully open, dimension “R” = 95mm