background image

The gap between the spark electrode and the pilot should be 3.5 - 4.5mm to produce a good

spark. 

There should be no need to adjust this. If under any circumstances the electric spark fails, the

pilot may be lit manually by proceeding with the ignition sequence as previously described, and

after turning the control knob through the spark position, the knob should be held in and the

pilot lit with a taper.

Release the pressure test point screw, and attach a pressure gauge. Light the fire on

the HIGH setting. To commission the appliance, the operating pressure must be in

accordance with the figures stated in section 2.0 of these instructions. The fire is

factory set to achieve the correct flow rates at the specified inlet pressure. 

Any significant variation in the inlet pressure could indicate a supply problem. If the

inlet pressure is too high, the gas supply meter/governor may be set incorrectly.

This should be checked with the fire running and if necessary reset by the gas sup-

plier.  If the inlet pressure is too low, then check the meter/governor pressure with

the appliance running.  If this is less than the inlet pressure stated in section 2.0 of

these instructions it will need to be reset by the gas supplier.  If the inlet pressure

is too low, but the meter/governor pressure is acceptable, then a problem in the

supply pipework is to be suspected.  Upon satisfactory checking of the inlet pres-

sure, turn the fire off, disconnect the pressure gauge and refit the test point screw.

Light the fire and check for gas soundness. In the event that the inlet pressure is not in accordance with the figures stated in the data

section of these instructions, the appliance must not be commissioned, and the problem investigated and rectified.

This fire is fitted with a flue spillage safety device (ODS). If the fire shuts down during use for no apparent reason then several things

may be suspected. If a door or window has been opened creating a draught, then pilot disturbance is the problem, and removal of the

draught should resolve this. If a grommet seal has been left out of the firebox (if fitted) then this also will also cause intermittent shut-

down. The gas pressure reaching the fire must also be checked. The thermocouple connection into the back of the gas control valve may

also have worked loose during installation, simply tighten to remedy if this is the case.

If pilot disturbance is not the cause, then the ODS safety system may be in operation. Switch the appliance OFF, check the flue and carry

out any remedial work required. Re-light the fire and carry out a spillage test. DO NOT allow the appliance to be used if it continues to

fail a spillage test.

The aeration hole of the pilot must be carefully cleaned out on each annual service to ensure continued function of the ODS.

The spillage monitoring system shall not be adjusted, modified, or put out of operation by the installer. Any spare parts fitted MUST be

of a type supplied for the purpose by the appliance manufacturer.

If the fire is not spilling, then further guidance should be sought, using the Troubleshooting section as a guide.

Close all doors and windows to the room containing the appliance. Let the fire run on HIGH for five minutes. Take a smoke match, light

it, and using a smoke match tube, hold it at the top edge of the fire opening, 25mm down and 25mm in. Starting 50mm in from either

side, run the smoke match across the opening. All the smoke should be drawn away up the flue. Any smoke returning into the room indi-

cates that spillage is occurring. If the initial spillage test fails, run the fire for a further 10 minutes and repeat the test. When the test has

been completed satisfactorily, repeat with any extractor fans in the premises running on the highest setting, and any communicating doors

open. Finally, repeat with all doors open.

NOTE: If spillage is still indicated after undertaking all of the above, there may be a fault in the flue, or insufficient ventila-

tion is present. If the problem cannot be rectified immediately, then expert advice should be sought. Inform the user, disconnect the

fire, and attach an explanatory label.

12.0 SPARK GAP

12.1 OPERATING PRESSURE

 

    FIN:

A

   

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

   

 

 

 

 

 

Figure 5

Spark gap

 

    FIN:

A

   

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

   

 

 

 

 

 

Figure  5

6

'

2013 Focal Point Fires plc.

12.2 FLUE SPILLAGE MONITORING SYSTEM

12.3 TESTING FOR SPILLAGE

Match

Crimp

Tube

Figure 6 : Cross section of smoke match tube

Make a smoke match tube from 10mm diameter

tube. Seal off one end and crimp the tube to pre-

vent the smoke match from sliding down inside.

Spillage test - Figure 7

A.25mm down from top of

opening

B.  25mm  in  from  front  of

opening.

C.  Disregard  outer  50mm

either  side  of  fireplace

opening

C

C

B

A

Fireplace Opening

Smoke Match

In Tube

Figure 7

Summary of Contents for HANNINGTON

Page 1: ...oint Fires plc You are not per mitted to copy or adapt any of the content without the prior written permission of Focal Point Fires plc INTHE UK ALWAYS USE A GAS SAFE REGISTERED ENGINEERTO INSTALL REP...

Page 2: ...onsiders all surfaces as working surfaces with the exception of the control knob and ash pan door As with any gas fire a fire guard complying with BS 8423 must be used in presence of pets children and...

Page 3: ...e with an inset Decorative Fuel Effect Fire BS5871 part 3 contains further details The fireplace opening should be inspected and repairs made where nec essary Any chair brick may be left in place The...

Page 4: ...to unpack or install this appliance Remove the box containing the firefront and the bag containing the coals Remove the cardboard packing pieces and any bags contain ing other fittings or parts Remove...

Page 5: ...e main burner control shown in figure 3 on left hand side of control valve knob fully anti clockwise Turn ignition knob shown on right hand side of control valve slightly left towards the ignition pos...

Page 6: ...to the back of the gas control valve may also have worked loose during installation simply tighten to remedy if this is the case If pilot disturbance is not the cause then the ODS safety system may be...

Page 7: ...with smoke pellet for correct operation 7 Strip off the burner pipes and clean thoroughly 8 Clean out the injector and pilot assembly DO NOT attempt to dismantle the pilot unit 9 Ensure the injector...

Page 8: ...rthing to metal work reset gap correctly Blocked pilot clean out internally Pilot lights but then goes out Severe restriction in gas supply clear obstruction Faulty thermocouple replace pilot unit Hol...

Page 9: ...The fire is only suitable for use with the gas type for which it is supplied This appliance is fitted with a flue blockage safety device which will shut down the fire if abnormal flue conditions occur...

Page 10: ...lowing the instructions given in the Installation section The Installation instructions carry full servicing details for the use of the installer If debris from the flue or other foreign matter is fou...

Page 11: ...ontrol valve slightly left towards the ignition position until reaching the stop press down and hold for 5 seconds only pilot gas is flowing Continue pressing down the knob while turning further to th...

Page 12: ...should sit snugly behind the back edge of the burner rails as shown in figure 7 Do not fit the matrix on top of the burner rails 2 Position the front coal strip as shown in figure 8 The rear edge of...

Page 13: ...of the fuel matrix 6 Finally take the two remaining coals and place at the back of the fuel matrix in the centre as shown in figure 12 Adding these coals should complete the appearance of the fuel be...

Page 14: ...take another two pebbles and place behind the second row of pebbles next to each other in the centre of the fuel bed as shown in fig ure 16 The pebbles may be orientated as desired to achieve a reali...

Page 15: ...al ly as shown in figure 21 ensuring correct orientation The base of this log must rest securely on the front log strip Take one of the smaller logs numbered 14 and position in between the two vertica...

Page 16: ...f handset and insert 1 x PP3 9 volt battery Replace cover Before carrying out any of the following operations ensure that the fire is OFF and completely cold Appliance Ensure appliance is off and cool...

Page 17: ...nditions for your product have been met then please submit the following information for the attention of the 3G Service Department to the address below Alternatively you can email or fax Please note...

Reviews: