background image

www.fmiproducts.com

126333-01A

7

DETERMINING FRESH-AIR FLOW 

FOR HEATER LOCATION

Determining if You Have a Confined or 

Unconfined Space

Use this work sheet to determine if you have 

a confined or unconfined space.

Space:

 Includes the room in which you will 

install heater plus any adjoining rooms with 

doorless  passageways  or  ventilation  grills 

between the rooms.

1.  Determine the volume of the space (length 

x width x height).

 

Length x Width x Height = ______cu. ft. 

(volume of space)

 

Example:

 Space size 22 ft. (length) x 18 

ft. (width) x 8 ft. (ceiling height) = 3168 cu. 

ft. (volume of space)

 

If additional ventilation to adjoining room 

is supplied with grills or openings, add the 

volume of these rooms to the total volume 

of the space. 

2.  Multiply the space volume by 20 to deter-

mine the maximum Btu/Hr the space can 

support.

 

 _____ (volume of space) x 20 = (Maxi-

mum Btu/Hr the space can support)

 

Example:

 3168 cu. ft. (volume of space) x 

20 = 63,360 (maximum Btu/Hr the space 

can support)

3.  Add the Btu/Hr of all fuel burning appli-

ances in the space.

 

Vent-free heater 

 _______ Btu/Hr

 

Gas water heater* 

 _______ Btu/Hr

 

Gas furnace 

 _______ Btu/Hr

 

Vented gas heater 

 _______ Btu/Hr

 

Gas fireplace logs 

 _______ Btu/Hr

 

Other gas appliances* + ______ Btu/Hr

 Total 

= ______ Btu/Hr

  * Do not include direct-vent gas appli-

ances.  Direct-vent  draws  combustion 

air from the outdoors and vents to the 

outdoors.

 

Example:

 

Gas water heater 

 _________ Btu/Hr

 

Vent-free heater 

+ ________ Btu/Hr

 Total 

= ________ Btu/Hr

AIR FOR COMBUSTION AND VENTILATION

Continued

4.  Compare the maximum Btu/Hr the space 

can  support  with  the  actual  amount  of 

Btu/Hr used.

 

 _________ Btu/Hr (maximum the space 

can support) 

 

 _________ Btu/Hr (actual amount of 

 

 

Btu/Hr used)

 

Example:

 63,360 Btu/Hr (maximum the 

space can support) 

 

 

79,000 Btu/Hr (actual amount 

of Btu/Hr used)

The space in the above example is a confined 

space because the actual Btu/Hr used is more 

than the maximum Btu/Hr the space can sup-

port. You  must  provide  additional  fresh  air. 

Your options are as follows:
A.  Rework  worksheet,  adding  the  space 

of an adjoining room. If the extra space 

provides  an  unconfined  space,  remove 

door to adjoining room or add ventilation 

grills between rooms. See 

Ventilation Air 

From Inside Building

, page 8.

B.  Vent room directly to the outdoors. See 

Ventilation Air From Outdoors

, page 8.

C.  Install  a  lower  Btu/Hr  heater,  if  lower 

Btu/Hr size makes room unconfined. 

If the actual Btu/Hr used is less than the 

maximum Btu/Hr the space can support, the 

space is an unconfined space. You will need 

no additional fresh air ventilation. 

 WARNING: If the area in which 

the heater may be operated does 

not meet the required volume for 

indoor combustion air, combus

-

tion and ventilation air shall be 

provided by one of the methods 

described in the 

National Fuel 

Gas Code, ANSI Z223.1/NFPA 54, 

the

 International Fuel Gas Code,

 

or applicable local codes.

40,000
39,000
79,000

Summary of Contents for (V)BFBF36 series

Page 1: ...th the decorative type unvented room heater for the minimum fireplace size requirement DO NOT INSTALL AN APPLIANCE IN THIS FIREBOX UNLESS THIS FIREBOX MEETS THE MINIMUM DIMEN SIONS REQUIRED FOR THE INSTALLATION This firebox has been tested and approved under ANSI Z21 91 for use with any ANSI Z21 11 2 approved gas logs INSTALLER Leave this manual with the appliance CONSUMER Retain this manual for f...

Page 2: ...ce to avoid burns or clothing ignition Firebox will remain hot for a time after shutdown Allowsurfacetocool before touching Carefully supervise young chil dren when they are in the room with firebox WARNING Improper instal lation adjustment alteration service or maintenance can causeinjuryorpropertydamage Refer to this manual for correct installation and operational procedures For assistance or ad...

Page 3: ...nal Fuel Gas Code ANSI Z223 1 NFPA 54 Firebox must be electrically grounded in accordance with the National Electrical Code ANSI NFPA70 latest edition Available from American National Standards Institute Inc 1430 Broadway New York NY 10018 National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 State of Massachusetts The installation must be made by a licensed plumber or gas fit...

Page 4: ... following 1 Where the firebox will be located Allow for wall and ceiling clearances see Installa tion Clearances page 9 PRODUCT SPECIFICATIONS Figure 1 Firebox Dimensions 36 Models Right Side View Right Side View Firebox Top View Front View Outside Air Kit Location Optional 2 Everything needed to complete installation 3 These models CANNOT be installed in a bedroom unless the maximum Btu rating o...

Page 5: ... 9 227 9 705 8 193 12 933 3 628 7 330 9 705 8 163 26 504 24 926 21 041 4 392 7 763 28 612 Figure 2 Firebox Dimensions 42 Models Right Side View Right Side View Firebox Top View Front View Outside Air Kit Location Optional PRODUCT SPECIFICATIONS Continued 42 MODELS Electrical Outlet ...

Page 6: ...mmunicating directly with the space in which the appliances are installed through openings not furnished with doors are considered a part of the un confined space Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them WARNING This heater shall notbeinstalledinaroomorspace unless the required volume of in door combustion air is provided by the me...

Page 7: ...rom the outdoors and vents to the outdoors Example Gas water heater __________ Btu Hr Vent free heater _________ Btu Hr Total _________ Btu Hr AIR FOR COMBUSTION AND VENTILATION Continued 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used __________Btu Hr maximum the space can support __________Btu Hr actual amount of Btu Hr used Example 63 360 Btu Hr maximum ...

Page 8: ...n for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermo stat controlled power vent Heated air entering the attic will activate the power vent INSTALLATION Or Remove Door into Adjoining Room Option 3 Ventilation Grills Into Adjoining Room Option 2 Ventilation Grills Into Adjoining Room Option 1 12 12 Outlet Air Ve...

Page 9: ...ce cabinet see Figure 5 B Clearances from the top of firebox opening to ceiling should not be less than 42 C When firebox is installed on carpeting or other combustible material other than wood flooring firebox should be installed on a metal or wood panel extending the full width and depth of enclosure D Clearances from bottom of firebox to the floor is 0 These fireboxes can be installed as freest...

Page 10: ...s through holes in nailing flange see Figure 7 6 If using an optional perimeter trim kit install the trim after final finishing and or painting of wall See instructions included with trim accessory for attaching trim 7 Install and properly test gas log heater Follow installation instructions included with the vent free gas log heater that is being installed IMPORTANT When finishing your firebox co...

Page 11: ... Out One Hole Gas Line Hole Equipment Shutoff Valves Install One INSTALLING FIREBOX USING OPTIONAL ACCESSORY MANTELS WARNING A qualified ser vicepersonmustinstallfirebox Follow all local codes This firebox may be installed using a cabinet mantel accessory against a wall in your home The firebox and cabinet mantel can be installed directly on the floor A trim kit is included with the mantel accesso...

Page 12: ...rical cover plate with bush ing from fireplace by removing 2 sheet metal screws as shown in Figure 11 page 13 2 Slide power source wiring through electri cal bushing opening and electrical cover plate and make all necessary connec tions 3 Slide all wiring connections in electrical housing as shown in Figure 11 page 13 4 Secure electrical cover plate with screws previously removed Note Electrical h...

Page 13: ...out DO NOT FORCE The panels are actually held in place by means of a retention dimple embossed on the edge of removable panels Accessibility to the bottom on 36 and 42 models only can also be gained through the access cover plate on the bottom front of the firebox hearth Remove the screws to expose the rectangular shaped access panel see Figure 12 The sides and back refractory brick liner pieces d...

Page 14: ...oreign objects in blower wheel Also double check all wire leads and make sure wire routing is not pinched or in a precarious position Correct ac cordingly CAUTION Use gloves as sheet metal parts may be sharp Model BK Installation 1 Be certain that all wire terminals are securely attached to terminals on blower motor and that the screw retaining the greengroundwireistight seeFigure14 2 Place blower...

Page 15: ... a blowerwheelwhileinoperation 5 Turn on power to duplex outlet if previ ously turned off per warning in column 2 page 13 6 Plug in blower power cord to duplex outlet see Figure 13 page 13 7 Turn blower on and check for operation Turn blower off by turning knob fully counterclockwise before continuing 8 Peel off backing paper and stick supplied wiring diagram decal on firebox bottom approximately ...

Page 16: ... Installation Air Inlet Eyebrow Vented Crawl Space Check Local Codes Before Installing in a Vented Crawl Space Screws Hood INSTALLING FIREPLACE HOOD AND SCREEN 1 Attach hood to firebox using screws pro vided see Figure 18 2 Insert each rod through all rings located at top of screen 3 Insert first rod into rear hole in left side of firebox Fasten rod to rear hole near center of firebox using 10 x 3...

Page 17: ...ll FMI PRODUCTS LLC at 1 866 328 4537 to answer questions and replace parts under warranty Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty When calling or writing please have your model and serial numbers of your fireplace ready Model and serial number information are in the fireplace s rating plate located in the screen pocket to...

Page 18: ...www fmiproducts com 126333 01A 18 PARTS MODELS V BFBF36K V BFBL36K V BFBF36WS V BFBL36WS V BFBF42K V BFBL42K V BFBF42WS AND V BFBL42WS 1 3 4 2 5 5 11 12 7 7 6 9 10 8 ...

Page 19: ...Refractory White Stack 1 7 20027 Refractory Bracket 2 8 20280 Top Spacer 4 9 107128 01 Conduit Gas 4 10 110037 01 Electrical Duct Assembly 1 11 21198 Plate Blower Access 1 12 21171 Cover Gas Conduit 3 21171 Cover Gas Conduit 2 PARTS This list contains replaceable parts used in your firebox When ordering parts follow the instructions listed under Replacement Parts on page 17 of this manual V B F B ...

Page 20: ...and orFMIPRODUCTS LLC whowillprovideoriginalfactoryreplacementparts Failuretouseoriginalfactoryreplacementpartsvoidsthiswarranty Travel handling transportation diagnostic material laborandincidentalcostsassociatedwithwarrantyrepairs unless expressly covered by this warranty are not reimbursable under this warranty and are the responsibility of the owner Excluded from this warranty are products or ...

Reviews: