background image

www.fmiproducts.com

126333-01A

6

AIR FOR COMBUSTION AND VENTILATION

Unusually Tight Construction

The air that leaks around doors and windows 

may provide enough fresh air for combustion 

and ventilation. However, in buildings of un

-

usually tight construction, you must provide 

additional fresh air.

Unusually tight construction is defined as 

construction where:

a.  walls and ceilings exposed to the out

-

side  atmosphere  have  a  continuous 

water vapor retarder with a rating of 

one perm (6 x 10

-11

 kg per pa-sec-m

2

) or 

less with openings gasketed or sealed 

and

b.  weather stripping has been added on 

openable windows and doors 

and

c.  caulking  or  sealants  are  applied  to 

areas such as joints around window 

and door frames, between sole plates 

and floors, between wall-ceiling joints, 

between wall panels, at penetrations 

for plumbing, electrical and gas lines 

and at other openings. 

If your home meets all of the three criteria 

above, you must provide additional fresh 

air.  See 

Ventilation Air From Outdoors

page 8. 

If your home does not meet all of the three 

criteria  above,  proceed  to 

Determining 

Fresh-Air Flow for Firebox Location

page 7. 
Confined and Unconfined Space

The

 National Fuel Gas Code, ANSI Z223.1/

NFPA 54

 defines a confined space as a space 

whose volume is less than 50 cubic feet per 

1,000 Btu per hour (4.8 m

3

 per kw) of the ag

-

gregate input rating of all appliances installed 

in that space and an unconfined space as a 

space whose volume is not less than 50 cubic 

feet per 1,000 Btu per hour (4.8 m

3

 per kw) 

of the aggregate input rating of all appliances 

installed in that space. Rooms communicating 

directly with the space in which the appliances 

are installed*, through openings not furnished 

with doors, are considered a part of the un

-

confined space.

* Adjoining rooms are communicating only if 

there are doorless passageways or ventilation 

grills between them.

 WARNING: This heater shall 

not be installed in a room or space 

unless the required volume of in

-

door combustion air is provided 

by the method described in the 

National Fuel Gas Code, ANSI 

Z223.1/NFPA 54,

 the 

International 

Fuel Gas Code,

  or  applicable 

local codes. Read the following 

instructions to insure proper fresh 

air for this and other fuel-burning 

appliances in your home.

Today’s homes are built more energy efficient 

than ever. New materials, increased insulation 

and new construction methods help reduce 

heat loss in homes. Home owners weather 

strip  and  caulk  around  windows  and  doors 

to keep the cold air out and the warm air in. 

During heating months, home owners want 

their homes as airtight as possible.
While it is good to make your home energy 

efficient, your home needs to breathe. Fresh 

air must enter your home. All fuel-burning ap-

pliances need fresh air for proper combustion 

and ventilation.

Exhaust fans, fireboxes, clothes dryers and 

fuel  burning  appliances  draw  air  from  the 

house to operate. You must provide adequate 

fresh air for these appliances. This will insure 

proper venting of vented fuel-burning appli-

ances.

PROVIDING ADEQUATE 

VENTILATION 

The following are excerpts from 

National Fuel 

Gas Code, ANSI Z223.1/NFPA 54, Air for 

Combustion and Ventilation.

All spaces in homes fall into one of the three 

following ventilation classifications:
1.  Unusually Tight Construction
2.  Unconfined Space
3.  Confined Space
The information on page 5 through 7 will help 

you classify your space and provide adequate 

ventilation. 

Summary of Contents for (V)BFBF36 series

Page 1: ...th the decorative type unvented room heater for the minimum fireplace size requirement DO NOT INSTALL AN APPLIANCE IN THIS FIREBOX UNLESS THIS FIREBOX MEETS THE MINIMUM DIMEN SIONS REQUIRED FOR THE INSTALLATION This firebox has been tested and approved under ANSI Z21 91 for use with any ANSI Z21 11 2 approved gas logs INSTALLER Leave this manual with the appliance CONSUMER Retain this manual for f...

Page 2: ...ce to avoid burns or clothing ignition Firebox will remain hot for a time after shutdown Allowsurfacetocool before touching Carefully supervise young chil dren when they are in the room with firebox WARNING Improper instal lation adjustment alteration service or maintenance can causeinjuryorpropertydamage Refer to this manual for correct installation and operational procedures For assistance or ad...

Page 3: ...nal Fuel Gas Code ANSI Z223 1 NFPA 54 Firebox must be electrically grounded in accordance with the National Electrical Code ANSI NFPA70 latest edition Available from American National Standards Institute Inc 1430 Broadway New York NY 10018 National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 State of Massachusetts The installation must be made by a licensed plumber or gas fit...

Page 4: ... following 1 Where the firebox will be located Allow for wall and ceiling clearances see Installa tion Clearances page 9 PRODUCT SPECIFICATIONS Figure 1 Firebox Dimensions 36 Models Right Side View Right Side View Firebox Top View Front View Outside Air Kit Location Optional 2 Everything needed to complete installation 3 These models CANNOT be installed in a bedroom unless the maximum Btu rating o...

Page 5: ... 9 227 9 705 8 193 12 933 3 628 7 330 9 705 8 163 26 504 24 926 21 041 4 392 7 763 28 612 Figure 2 Firebox Dimensions 42 Models Right Side View Right Side View Firebox Top View Front View Outside Air Kit Location Optional PRODUCT SPECIFICATIONS Continued 42 MODELS Electrical Outlet ...

Page 6: ...mmunicating directly with the space in which the appliances are installed through openings not furnished with doors are considered a part of the un confined space Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them WARNING This heater shall notbeinstalledinaroomorspace unless the required volume of in door combustion air is provided by the me...

Page 7: ...rom the outdoors and vents to the outdoors Example Gas water heater __________ Btu Hr Vent free heater _________ Btu Hr Total _________ Btu Hr AIR FOR COMBUSTION AND VENTILATION Continued 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used __________Btu Hr maximum the space can support __________Btu Hr actual amount of Btu Hr used Example 63 360 Btu Hr maximum ...

Page 8: ...n for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermo stat controlled power vent Heated air entering the attic will activate the power vent INSTALLATION Or Remove Door into Adjoining Room Option 3 Ventilation Grills Into Adjoining Room Option 2 Ventilation Grills Into Adjoining Room Option 1 12 12 Outlet Air Ve...

Page 9: ...ce cabinet see Figure 5 B Clearances from the top of firebox opening to ceiling should not be less than 42 C When firebox is installed on carpeting or other combustible material other than wood flooring firebox should be installed on a metal or wood panel extending the full width and depth of enclosure D Clearances from bottom of firebox to the floor is 0 These fireboxes can be installed as freest...

Page 10: ...s through holes in nailing flange see Figure 7 6 If using an optional perimeter trim kit install the trim after final finishing and or painting of wall See instructions included with trim accessory for attaching trim 7 Install and properly test gas log heater Follow installation instructions included with the vent free gas log heater that is being installed IMPORTANT When finishing your firebox co...

Page 11: ... Out One Hole Gas Line Hole Equipment Shutoff Valves Install One INSTALLING FIREBOX USING OPTIONAL ACCESSORY MANTELS WARNING A qualified ser vicepersonmustinstallfirebox Follow all local codes This firebox may be installed using a cabinet mantel accessory against a wall in your home The firebox and cabinet mantel can be installed directly on the floor A trim kit is included with the mantel accesso...

Page 12: ...rical cover plate with bush ing from fireplace by removing 2 sheet metal screws as shown in Figure 11 page 13 2 Slide power source wiring through electri cal bushing opening and electrical cover plate and make all necessary connec tions 3 Slide all wiring connections in electrical housing as shown in Figure 11 page 13 4 Secure electrical cover plate with screws previously removed Note Electrical h...

Page 13: ...out DO NOT FORCE The panels are actually held in place by means of a retention dimple embossed on the edge of removable panels Accessibility to the bottom on 36 and 42 models only can also be gained through the access cover plate on the bottom front of the firebox hearth Remove the screws to expose the rectangular shaped access panel see Figure 12 The sides and back refractory brick liner pieces d...

Page 14: ...oreign objects in blower wheel Also double check all wire leads and make sure wire routing is not pinched or in a precarious position Correct ac cordingly CAUTION Use gloves as sheet metal parts may be sharp Model BK Installation 1 Be certain that all wire terminals are securely attached to terminals on blower motor and that the screw retaining the greengroundwireistight seeFigure14 2 Place blower...

Page 15: ... a blowerwheelwhileinoperation 5 Turn on power to duplex outlet if previ ously turned off per warning in column 2 page 13 6 Plug in blower power cord to duplex outlet see Figure 13 page 13 7 Turn blower on and check for operation Turn blower off by turning knob fully counterclockwise before continuing 8 Peel off backing paper and stick supplied wiring diagram decal on firebox bottom approximately ...

Page 16: ... Installation Air Inlet Eyebrow Vented Crawl Space Check Local Codes Before Installing in a Vented Crawl Space Screws Hood INSTALLING FIREPLACE HOOD AND SCREEN 1 Attach hood to firebox using screws pro vided see Figure 18 2 Insert each rod through all rings located at top of screen 3 Insert first rod into rear hole in left side of firebox Fasten rod to rear hole near center of firebox using 10 x 3...

Page 17: ...ll FMI PRODUCTS LLC at 1 866 328 4537 to answer questions and replace parts under warranty Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty When calling or writing please have your model and serial numbers of your fireplace ready Model and serial number information are in the fireplace s rating plate located in the screen pocket to...

Page 18: ...www fmiproducts com 126333 01A 18 PARTS MODELS V BFBF36K V BFBL36K V BFBF36WS V BFBL36WS V BFBF42K V BFBL42K V BFBF42WS AND V BFBL42WS 1 3 4 2 5 5 11 12 7 7 6 9 10 8 ...

Page 19: ...Refractory White Stack 1 7 20027 Refractory Bracket 2 8 20280 Top Spacer 4 9 107128 01 Conduit Gas 4 10 110037 01 Electrical Duct Assembly 1 11 21198 Plate Blower Access 1 12 21171 Cover Gas Conduit 3 21171 Cover Gas Conduit 2 PARTS This list contains replaceable parts used in your firebox When ordering parts follow the instructions listed under Replacement Parts on page 17 of this manual V B F B ...

Page 20: ...and orFMIPRODUCTS LLC whowillprovideoriginalfactoryreplacementparts Failuretouseoriginalfactoryreplacementpartsvoidsthiswarranty Travel handling transportation diagnostic material laborandincidentalcostsassociatedwithwarrantyrepairs unless expressly covered by this warranty are not reimbursable under this warranty and are the responsibility of the owner Excluded from this warranty are products or ...

Reviews: