Fireplace inSTallaTion

Continued

MANTEL CLEARANCES

Woodwork  such  as  wood  trims,  mantels  or 

any other combustible material projecting from 

Figure 12 - Mantel Clearances to Metal 

Face

VenTing inSTallaTion

8" Max.

“K” Factor

.84

1

/

2

" Typ.

1

/

2

" Typ.

Noncombustible 

Hearth 

Extension

“Z” Type Ember 

Protector

Noncombustible 

Hearth Extension

Ember Protector

Figure 10 - Raised Hearth Extension

Front

Face

Fireplace Front View

Fireplace Side View

3" Nom.

(7.6 cm)

9" Min.

(22.8 cm)

12" Min.

(30.4 cm)

33°

6" Nom.

(15.2 cm)

1

/

2

" Max.

(3.8 cm)

Drywall

2" X 4" Stud

Combustible

Materials

Figure 11 - Mantel Clearances to 

Combustible Materials

Seal Gaps with

Noncombustible

Mortar or Adhesive

Top View of Fireplace

Drywall

4"

(Approx.)

(10.1 cm) 33°

Nom.

6" Nom.

(15.2 cm)

3

/

8

Min.

(11.1 cm)

Combustible

Material Must

Not Overlap

Black Metal

Front Face

3

/

4

" Max.

(6.98 cm)

NONCOMBUSTIBLE

HEARTH EXTENSION

52 

1

/

2

" MIN.

(133.3cm)

36 

1

/

2

" MIN.

(92.7cm)

8" MIN.

(20.3cm)

16" MIN.
(40.6cm)

Figure 9 - Hearth Extensions

the front face must not be placed within 9" of 

fireplace opening. 
Combustible materials above and projecting 

more than 1 

1

/

2

" from the fireplace front face 

(see Figure 11) must not be placed less than 12" 

from effective opening of the fireplace (

NFPA 

STD 211, Sec. 7-3.3.3

).

Mantels  or  any  other  combustible  material 

may  also  come  up  to  the  side  edge  of  the 

black metal face of the fireplace only if the 

projection from the front face falls within limits 

shown in Figure 12.

OPTIONAL OUTSIDE AIR KIT

The  installation  of  an  outside  air  kit  should 

be  performed  during  the  rough  framing  of 

the fireplace due to the nature of it’s location. 

Outside combustion air is accessed through 

and exterior wall or a vented crawl space.

 CAUTION: Air inlet ducts must 

not terminate in attic space.

Maximum height for air inlet above the fire-

place platform must be no less than 3 feet 

below chimney cap.
For further details on installation of outside 

air  kit,  please  refer  to  instructions  included 

with air kit.

Summary of Contents for (V)3612ST

Page 1: ...roved to ANS Z21 60 or Z21 84 standards or for use with a vent free gas log heater approved to ANS Z21 11 2 standard This wood burning fireplace complies with UL127 CAN ULS S610 M87 standard as a FACTORY BUILT APPLIANCE FOR CANADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation to deter mine the need to obtain ...

Page 2: ... place clothing or other flammablematerialsonornear the appliance Never leave children unat tended when a fire is burning in the fireplace IMPORTANT Check local codes before installing this fireplace Models V 3612STseriesisawoodburningfire place intended and approved for installation in either residential homes or buildings of standard construction This fireplace system requires the utilization of...

Page 3: ...ARNING Use solid wood or processed solid fuel fire logs only When processed wood fuel fire logs are used do not poke or stir the logs while they are burning Use only fire logs that have been evaluated for the application in fireplace and refer to fire log warnings and caution markings on packaging prior to use WARNING Always leave glass doors fully opened or fully closed when operating fireplace W...

Page 4: ...acers on Sides of Fireplace Provide Required 1 2 5 cm Clearance 2 5 cm Min Clearance From Pipe to Combustibles 3 7 6 cm 12 30 4 cm Min From Perpendicular Side Wall to Fireplace Opening Typ Figure 3 Fireplace Clearances selecting location To determine the safest and most efficient location for the fireplace you must take into consideration the following guidelines 1 The location must allow for prop...

Page 5: ...r should extend under fireplace a minimum of 1 1 2 The ember protector should be made of galvanized sheet metal 28 gauge minimum to prevent corrosion 6 Using screws or nails secure fireplace to the framing through flanges located on sides of the fireplace see Figure 8 Fireplace Installation Continued Figure 7 Ember Protectors Ember Protector Typ of 2 1 2 1 2 cm Maximum Figure 8 Nailing Flanges Nai...

Page 6: ...NSION 52 1 2 MIN 133 3cm 36 1 2 MIN 92 7cm 8 MIN 20 3cm 16 MIN 40 6cm Figure 9 Hearth Extensions the front face must not be placed within 9 of fireplace opening Combustible materials above and projecting more than 1 1 2 from the fireplace front face see Figure 11 must not be placed less than 12 from effective opening of the fireplace NFPA STD 211 Sec 7 3 3 3 Mantels or any other combustible materi...

Page 7: ...imney together exception see Figure 17 page 8 WARNING The opening in the collar around the chimney at the top of the fireplace must not be obstructed Neveruseblowninsula tion to fill the chimney enclosure Figure 13 Outside Air Kit Installation Secure to Collars with Duct Tape or Screws Air Inlet Location Must Allow For Bushes or Snow Vent Hood Required for Wall Installation Air Inlet Termination V...

Page 8: ...stop Spacers FS 10 Firestop spacers are required at each point where the chimney penetrates a floor or ceil ing joist space Their purpose is to establish and maintain the required clearance between the chimney and the combustible materials When the pipe passes through a framed opening into a living space above the firestop must be placed onto the ceiling from below as shown in Figure 19 page 9 The...

Page 9: ... flue pipe MINIMUM HEIGHT 15 FT 4 5m MAXIMUM HEIGHT CHASE TERMINATION 40 FT 12m Figure 22 Maximum Chimney Height Storm Collar Flashing Firestop Spacer RLT 12D RLT 12D STL 12D Minimum Maximum Chimney Height The minimum height of the chimney mea sured from the base of the fireplace to the flue gas outlet end of pipe is 16 feet for a straight run 16 feet minimum for a run with 1 elbow set and 25 feet...

Page 10: ...roof Caulk Storm Collar Flashing Flashing Installation Determine flashing to be used with roof open ing chart Slide flashing over pipe until base is flat against roof Replace as many shingles as needed to cover exposed area and flashing base Secure in position by nailing through shingles see Figure 24 DO NOT NAIL THROUGH FLASHING CONE Storm Collar Installation SC 10 Place storm collar over pipe an...

Page 11: ... tile or other noncom bustible materials may overlap the front face provided they do not obstruct essential open ings like louvered slots or any other opening When overlapping with a noncombustible facing material use only noncombustible mortar or adhesive Installing fireplace facing Any noncombustible material may be used for facing glass tile brick etc as long as proper clearances are adhered to...

Page 12: ...ping approved by local codes When installing a gas line a shutoff valve designed for installation outside the appliance is recommended The gas pipe is intended for connection to a decorative gas appliance that operates using natural or propane LP gas only This appliance must have an automatic shutoff device and must comply with the Standard for Decora tive Gas Appliances for Installation in Vented...

Page 13: ...ge 15 must be installed when using an unvented gas log set Operation and Maintenance Guidelines Glass Doors Bi fold glass doors are optional with this fireplace Check with your local distributor for availability To install glass doors refer to installation instructions that are included with kit When fireplace is in operation doors must be fully open or fully closed position only or a fire haz ard...

Page 14: ...erials Chimney Have your chimney system cleaned and in spected regularly to ensure safe and efficient operation damper Mechanism The damper control lever is located inside the fire chamber see Figure 32 Make sure lever is cool before handling Pull down to close and push up to open Damper must be open when lighting a fire Not doing so will cause smoke spillage into the room When fireplace is not in...

Page 15: ...in triple wall Double Wall Pipe support assembly 12S 12DM Also available in triple wall Outside Air Kit AK4 Vent Plaster Collar Vent Hood Connector Duct 4 x 3 Storm Collar SC2 1 Firestop Spacer FS 10 for Straight Pipe 30FS 10 for 30 Angled Run Flashing V6F 10DM 0 to 6 12 Pitch V12F 10DM 6 12 to 12 12 Pitch Round Top Termination RLT 12D Econo Top Termination STL 12D Bi Fold Glass Doors DG368ST Brus...

Page 16: ...115603 01 Rev D 09 09 2701 S Harbor Blvd Santa Ana CA 92704 1 866 328 4537 www fmiproducts com ...

Reviews: