background image

www.fmiproducts.com

115603-01D

13

Figure 31 - Bi-Fold Glass Doors

Doors Fully Closed

Fireplace Front

Fireplace Front

Doors

Fully Opened

  WARNING:  Fireplaces 

equipped  with  glass  doors 

should  be  operated  only  with 

doors fully opened or doors fully 

closed. Doors, if left partly open, 

may draw gas and flame out of 

the  fireplace  opening  creating 

risks of both fire and smoke.

  WARNING:  Do  not  oper-

ate an unvented gas log set in 

this fireplace with the chimney 

removed.

  WARNING:  If  the  fireplace 

has been used for wood burning, 

the firebox and chimney must be 

cleaned  of  soot,  creosote  and 

ashes  by  a  qualified  chimney 

cleaner.  Creosote  will  ignite  if 

heavily heated.

opTional gaS line inSTallaTion

Continued

Cleaning Glass

Clean  glass  with  any  commercial  glass 

cleaner or soap and water. Do not use any 

abrasive material to clean glass. Do not clean 

glass with any cool water if glass is still hot 

from the fire. To remove doors, refer to instruc-

tions included with glass door kit.

  WARNING:  When  using  a 

decorative  vented  gas  log,  the 

damper must be removed or per-

manently locked in the fully open 

position and the glass doors must 

be in the fully open position.

Note: An appropriate FMI PRODUCTS, LLC 

hood (see Replacement and Accessory Parts, 

page  15)  must  be  installed  when  using  an 

unvented gas log set.

operaTion and MainTenance guidelineS

GLASS DOORS

Bi-fold  glass  doors  are  optional  with  this 

fireplace.  Check  with  your  local  distributor 

for availability.
To  install  glass  doors,  refer  to  installation 

instructions that are included with kit. When 

fireplace is in operation, doors must be fully 

open or fully closed position only or a fire haz-

ard may be created (see Figure 31).
A fireplace equipped with glass doors oper-

ates much differently than a fireplace with an 

open front. A fireplace with glass doors has a 

limited amount of air for combustion. Excessive 

heat within the fireplace can result if too large 

a fire is built or if combustion air gate is not 

completely open. 
The following tips should be followed to as-

sure that both the fireplace and glass door 

retain their beauty and function properly. 
•  Both the flue damper and glass doors must 

be  fully  opened  before  starting  fire. This 

will provide sufficient combustion air and 

maintain safe temperatures in firebox.

•  The glass must be allowed to warm slowly 

and evenly. The tempered glass will with-

stand a gradual temperature rise to 550° F, 

which is more than a normal fire will gener-

ate. Such materials as pitch/wax laden logs, 

very dry mill end lumber and large amounts 

of paper or cardboard boxes. Always keep 

the fire well back from the doors and never 

allow flames to contact the glass.

Summary of Contents for (V)3612ST

Page 1: ...roved to ANS Z21 60 or Z21 84 standards or for use with a vent free gas log heater approved to ANS Z21 11 2 standard This wood burning fireplace complies with UL127 CAN ULS S610 M87 standard as a FACTORY BUILT APPLIANCE FOR CANADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation to deter mine the need to obtain ...

Page 2: ... place clothing or other flammablematerialsonornear the appliance Never leave children unat tended when a fire is burning in the fireplace IMPORTANT Check local codes before installing this fireplace Models V 3612STseriesisawoodburningfire place intended and approved for installation in either residential homes or buildings of standard construction This fireplace system requires the utilization of...

Page 3: ...ARNING Use solid wood or processed solid fuel fire logs only When processed wood fuel fire logs are used do not poke or stir the logs while they are burning Use only fire logs that have been evaluated for the application in fireplace and refer to fire log warnings and caution markings on packaging prior to use WARNING Always leave glass doors fully opened or fully closed when operating fireplace W...

Page 4: ...acers on Sides of Fireplace Provide Required 1 2 5 cm Clearance 2 5 cm Min Clearance From Pipe to Combustibles 3 7 6 cm 12 30 4 cm Min From Perpendicular Side Wall to Fireplace Opening Typ Figure 3 Fireplace Clearances selecting location To determine the safest and most efficient location for the fireplace you must take into consideration the following guidelines 1 The location must allow for prop...

Page 5: ...r should extend under fireplace a minimum of 1 1 2 The ember protector should be made of galvanized sheet metal 28 gauge minimum to prevent corrosion 6 Using screws or nails secure fireplace to the framing through flanges located on sides of the fireplace see Figure 8 Fireplace Installation Continued Figure 7 Ember Protectors Ember Protector Typ of 2 1 2 1 2 cm Maximum Figure 8 Nailing Flanges Nai...

Page 6: ...NSION 52 1 2 MIN 133 3cm 36 1 2 MIN 92 7cm 8 MIN 20 3cm 16 MIN 40 6cm Figure 9 Hearth Extensions the front face must not be placed within 9 of fireplace opening Combustible materials above and projecting more than 1 1 2 from the fireplace front face see Figure 11 must not be placed less than 12 from effective opening of the fireplace NFPA STD 211 Sec 7 3 3 3 Mantels or any other combustible materi...

Page 7: ...imney together exception see Figure 17 page 8 WARNING The opening in the collar around the chimney at the top of the fireplace must not be obstructed Neveruseblowninsula tion to fill the chimney enclosure Figure 13 Outside Air Kit Installation Secure to Collars with Duct Tape or Screws Air Inlet Location Must Allow For Bushes or Snow Vent Hood Required for Wall Installation Air Inlet Termination V...

Page 8: ...stop Spacers FS 10 Firestop spacers are required at each point where the chimney penetrates a floor or ceil ing joist space Their purpose is to establish and maintain the required clearance between the chimney and the combustible materials When the pipe passes through a framed opening into a living space above the firestop must be placed onto the ceiling from below as shown in Figure 19 page 9 The...

Page 9: ... flue pipe MINIMUM HEIGHT 15 FT 4 5m MAXIMUM HEIGHT CHASE TERMINATION 40 FT 12m Figure 22 Maximum Chimney Height Storm Collar Flashing Firestop Spacer RLT 12D RLT 12D STL 12D Minimum Maximum Chimney Height The minimum height of the chimney mea sured from the base of the fireplace to the flue gas outlet end of pipe is 16 feet for a straight run 16 feet minimum for a run with 1 elbow set and 25 feet...

Page 10: ...roof Caulk Storm Collar Flashing Flashing Installation Determine flashing to be used with roof open ing chart Slide flashing over pipe until base is flat against roof Replace as many shingles as needed to cover exposed area and flashing base Secure in position by nailing through shingles see Figure 24 DO NOT NAIL THROUGH FLASHING CONE Storm Collar Installation SC 10 Place storm collar over pipe an...

Page 11: ... tile or other noncom bustible materials may overlap the front face provided they do not obstruct essential open ings like louvered slots or any other opening When overlapping with a noncombustible facing material use only noncombustible mortar or adhesive Installing fireplace facing Any noncombustible material may be used for facing glass tile brick etc as long as proper clearances are adhered to...

Page 12: ...ping approved by local codes When installing a gas line a shutoff valve designed for installation outside the appliance is recommended The gas pipe is intended for connection to a decorative gas appliance that operates using natural or propane LP gas only This appliance must have an automatic shutoff device and must comply with the Standard for Decora tive Gas Appliances for Installation in Vented...

Page 13: ...ge 15 must be installed when using an unvented gas log set Operation and Maintenance Guidelines Glass Doors Bi fold glass doors are optional with this fireplace Check with your local distributor for availability To install glass doors refer to installation instructions that are included with kit When fireplace is in operation doors must be fully open or fully closed position only or a fire haz ard...

Page 14: ...erials Chimney Have your chimney system cleaned and in spected regularly to ensure safe and efficient operation damper Mechanism The damper control lever is located inside the fire chamber see Figure 32 Make sure lever is cool before handling Pull down to close and push up to open Damper must be open when lighting a fire Not doing so will cause smoke spillage into the room When fireplace is not in...

Page 15: ...in triple wall Double Wall Pipe support assembly 12S 12DM Also available in triple wall Outside Air Kit AK4 Vent Plaster Collar Vent Hood Connector Duct 4 x 3 Storm Collar SC2 1 Firestop Spacer FS 10 for Straight Pipe 30FS 10 for 30 Angled Run Flashing V6F 10DM 0 to 6 12 Pitch V12F 10DM 6 12 to 12 12 Pitch Round Top Termination RLT 12D Econo Top Termination STL 12D Bi Fold Glass Doors DG368ST Brus...

Page 16: ...115603 01 Rev D 09 09 2701 S Harbor Blvd Santa Ana CA 92704 1 866 328 4537 www fmiproducts com ...

Reviews: