REQUIREMENTS FOR THE COMMONWEALTH OF 

MASSACHUSETTS

For all side wall horizontally vented gas fueled 

equipment installed in every dwelling, building or 

structure used in whole or in part for residential 

purposes, including those owned or operated by 

the Commonwealth and where the side wall ex-

haust vent termination is less than seven (7) feet 

above finished grade in the area of the venting, 

including but not limited to decks and porches, 

the following requirements shall be satisfied:

INSTALLATION OF CARBON 

MONOXIDE DETECTORS

At the time of installation of the side wall horizon-

tal vented gas fueled equipment, the installing 

plumber or gasfitter shall observe that a hard 

wired carbon monoxide detector with an alarm 

and battery backup is installed on the floor level 

where the gas equipment is to be installed. In 

addition, the installing plumber or gasfitter shall 

observe that a battery operated or hard wired car-

bon monoxide detector with an alarm is installed 

on each additional level of the dwelling, building or 

structure served by the side wall horizontal vented 

gas fueled equipment. It shall be the responsibility 

of the property owner to secure the services of 

qualified licensed professionals for the installation 

of hard wired carbon monoxide detectors.

In the event that the side wall horizontally 

vented gas fueled equipment is installed 

in a crawl space or an attic, the hard wired 

carbon monoxide detector with alarm and 

battery back-up may be installed on the next 

adjacent floor level.

In the event that the requirements of this 

subdivision can not be met at the time of 

completion of installation, the owner shall 

have a period of thirty (30) days to comply with 

the above requirements; provided, however, 

that during said thirty (30) day period, a battery 

operated carbon monoxide detector with an 

alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required 

in accordance with the above provisions shall 

comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified.

SIGNAGE

A metal or plastic identification plate shall be 

permanently mounted to the exterior of the 

building at a minimum height of eight (8) feet 

above grade directly in line with the exhaust 

vent terminal for the horizontally vented gas 

fueled heating appliance or equipment. The 

sign shall read, in print size no less than 1/2" in 

size, "GAS VENT DIRECTLY BELOW. KEEP 

CLEAR OF ALL OBSTRUCTIONS".

INSPECTION

The state or local gas inspector of the side 

wall horizontally vented gas fueled equipment 

shall not approve the installation unless, upon 

inspection, the inspector observes carbon 

monoxide detectors and signage installed in 

accordance with the provisions of 248 CMR 

5.08(2)(a) 1 through 4.

EXEMPTIONS: The following equipment is 

exempt from 248 CMR 5.08(2)(a) 1 through 4:

•  The equipment listed in Chapter 10 entitled 

"Equipment Not Required To Be Vented" 

in the most current edition of NFPA 54 as 

adopted by the Board; and

•  Product Approved  side  wall  horizontally 

vented gas fueled equipment installed in a 

room or structure separate from the dwell-

ing, building or structure used in whole or 

in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided 

When the manufacturer of Product Approved 

side wall horizontally vented gas equipment 

provides a venting system design or venting 

system components with the equipment, the 

instructions provided by the manufacturer for 

installation of the equipment and the venting 

system shall include:

•  Detailed instructions for the installation of 

the venting system design or the venting 

system components; and

•  A complete parts list for the venting system 

design or venting system.

Gas Equipment Venting System Not 

Provided

When the manufacturer of a Product Ap-

proved side wall horizontally vented gas fu-

eled equipment does not provide the parts for 

venting the flue gases, but identifies "special 

venting systems", the following requirements 

shall be satisfied by the manufacturer:

• 

The referenced "special venting system" in-

structions shall be included with the appliance 

or equipment installation instructions; and

•  The "special venting systems" shall be Prod

-

uct Approved by the Board, and the instruc-

tions for that system shall include a parts list 

and detailed installation instructions.

A copy of all installation instructions for all 

Product Approved side wall horizontally 

vented gas fueled equipment, all venting in-

structions, all parts lists for venting instruc-

tions, and/or all venting design instructions 

shall remain with the appliance or equipment 

at the completion of the installation.

Summary of Contents for T32EN-A Series

Page 1: ...asoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use...

Page 2: ...ently located manufactured mobile home where not prohib ited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use...

Page 3: ...he influence of alcohol and those at high altitudes Natural and Propane LP Gas Natural and propane LP gases are odorless An odor making agent is added to the gas The odor helps you detect a gas leak H...

Page 4: ...cing installing or repairing Only a qualified service person should install service or repair this fireplace Have fire place inspected annually by a qualified service person 7 You must keep control co...

Page 5: ...nt through the roof vertical or it may vent to an outside exterior wall hori zontal The vent pipe installation is very important to allow for proper operation You must follow the venting instructions...

Page 6: ...p of yourfireplace exceptwherestandoffspacers are integrally attached If standoff spacers are attached to your fireplace these spacers can be placed directly against wall or framing material See frami...

Page 7: ...ental heat Use this fireplace along with your primary heating sys tem Do not install this fireplace as your primary heat source If you have a central heating system you may run system s circulating bl...

Page 8: ...0 000 and 50 000 12 30 cm in Canada if between 10 000 and 100 000 12 30 cm in US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canad...

Page 9: ...ctly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than 1 2 in size GAS VENT DIRECTLY BELOW KEE...

Page 10: ...bowing or offsetting Always use wall firestops when penetrating walls and firestops when penetrating ceil ings or attic spaces If using a venting configuration of only horizontal venting with no verti...

Page 11: ...d twist one section clockwise approximately one quarter turn until the sections are fully locked see Figure 8 Note Horizontal runs of vent must be supported every three feet Use wall straps for this p...

Page 12: ...terior fascia material 7 Combustible Exterior Wall Only Slide the wall firestop over the vent pipe before connecting horizontal run to vent cap see Figure 12 8 Carefully move fireplace with vent as se...

Page 13: ...NT If using a venting configuration of only horizontal venting with no vertical run a 1 4 rise for every 12 of run toward the termina tion is required WARNING Never run vent downward as this may cause...

Page 14: ...loor installation where pipe vents horizontally through wall over 12 horizontal pipe Basement installation where one foot clearance from ground to termination is possible SNORKEL TERMINATION INSTALLAT...

Page 15: ...iguration for Venting Using Two 90 Elbows Venting with Two 90 Elbows Horizontal H1 Vertical V Horizontal H1 Horizontal H2 5 min 2 max 6 max 6 min 4 max 12 max 7 min 6 max 18 max 8 min 8 max 20 max 20...

Page 16: ...earance space If the area above the ceiling is a living space install firestop below the framed hole The firestop should be installed with no less than three nails per side see Figure 20 2 Assemble th...

Page 17: ...Figures 21 through 24 show four different configurations for vertical termination VENTING INSTALLATION INSTRUCTIONS Continued Figure 21 Vertical Venting Configuration Using Two 90 Elbows with Two Hori...

Page 18: ...NENTS FMI PRODUCTS LLC 5 8 Pipe Vent Kits Number Description P58 6 6 Section Double Wall Pipe Galvanized P58 12 12 Section Double Wall Pipe Galvanized P58 24 24 Section Double Wall Pipe Galvanized P58...

Page 19: ...LLATION CHECK GAS TYPE Use proper gas type for the fireplace unit you are installing If your gas supply is not correct do not install fireplace See retailer where you purchased the fireplace for prope...

Page 20: ...are no other foreign objects in blower wheel Turn blower on and check for operation Turn blower off by turning knob fully counterclockwise before continuing 10 Peel off the backing paper and stick the...

Page 21: ...ower to duplex outlet if previ ously turned off per the warning in column 2 page 19 9 Plug in blower power cord to duplex outlet 10 The blower will only run when the speed control knob is in the ON po...

Page 22: ...as pressure to between 11 and 14 inches of water If you do not reduce incoming gas pressure fire place regulator damage could occur Install external regulator with the vent pointing down as shown in F...

Page 23: ...ccess holes on side of fireplace 3 Attach flexible gas line from gas supply to control valve see Figure 32 4 Check all gas connections for leaks See Checking Gas Connections FIREPLACE INSTALLATION Con...

Page 24: ...gas fireplace 3 Make sure control knob of fireplace is in the OFF position 4 Check all joints from equipment shutoff valve to gas valve see Figure 34 or Figure 35 Apply noncorrosive leak detection fl...

Page 25: ...bondoorandpushing down and back on latch see Figure 38 6 Replace screen rod assembly by revers ing step 1 7 Replace louvers by reversing procedure under Removing Louver Panels for T32 series 8 Replace...

Page 26: ...brick panel by sliding it between the grate and the side of the firebox see Figure 40 7 Install the right brick panel using the same method described Figure 39 Installing Rear Brick Panel Rear Brick...

Page 27: ...ce log 4 right log onto the landing on right side of front log as shown in Figure 44 5 6 Metal Pins Rear Log 7 Place lava rock along sides and front of firebox bottom in areas that are visible only It...

Page 28: ...eless hand held re mote control the wall switch must be in the ON position to be operational The remote control then becomes the switching mechanism for fireplace operation 1 Open lower louver panel 2...

Page 29: ...lower louver panel OPERATING FIREPLACE FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not fol low these instructions exactly a fire or explosion may result causing property damage per sonal in...

Page 30: ...f the firebox and remove any dust dirt or other obstructions that will hinder the flow of air INSPECTING BURNERS Check pilot flame pattern and burner flame patterns often PILOT ASSEMBLY The pilot asse...

Page 31: ...CAUTION Do not vacuum if pieces are hot Use only the tempered glass door replace ment intended for this fireplace see Replace ment Parts page 35 for detail on ordering No substitutions may be made See...

Page 32: ...ot open ing 7 No power to unit or the ignition module or power transformer is bad 8 Vent damper not fully open REMEDY 1 Check to see if you have gas supply and that equip ment shutoff valve is opened...

Page 33: ...e blockage 1 Residues from manufac turing processes and logs curing 1 Metal expanding while heating or contracting while cooling REMEDY 1 Check wiring connection Refer to wiring diagram see Wiring Dia...

Page 34: ...t the flame does not exces sively impinge on it 2 Inspect the opening at the base of the burner to see that it is NOTpacked with any type of material 1 Properly locate logs see log placement section o...

Page 35: ...arranty Contact authorized retailers of this product If they can not supply original replacement part s call FMI PRODUCTS LLC s Techni cal Service Department at 1 866 328 4537 When calling have ready...

Page 36: ...6 ILLUSTRATED PARTS BREAKDOWN MODELS V T32E N P A V T32E NB PB A V T32E NR PR A V T32ENRB A V T32EPRB A V TC32E N P AND V TC32E NB PB 6 7 21 18 19 10 13 2 12 20 8 22 2 22 6 22 4 22 5 22 3 22 1 1 14 9...

Page 37: ...3 Heat Shield 1 12 108897 01 108897 01 Rear Refractory Brick Panel B Models Only 1 13 108901 01 108901 01 Right Refractory Brick Panel B Models Only 1 14 108901 02 108901 02 Left Refractory Brick Pane...

Page 38: ...P V M V T R TH M V 21 23 24 26 25 27 17 22 16 14 20 12 9 8 10 13 15 19 18 28 29 11 2 1 7 3 5 4 6 ILLUSTRATED PARTS BREAKDOWN BURNER ASSEMBLY MODELS V T32E N P A V T32E NB PB A V T32E NR PR A V T32ENR...

Page 39: ...25 Orifice 47 Natural 1 14514 Orifice 55 Propane LP 1 16 14528 Brass Elbow Fitting 1 17 108863 01 Supply Connect Plug 1 18 23416 Electronic Components Board 1 19 14129 Transformer 1 20 11147 Screw 10...

Page 40: ...ERSION KIT Not Shown PCDE 32T Propane LP Gas NCDE 32T Natural Gas FACE LOUVER PANEL KIT Not Shown RLD32 Rolled Black ROLLED LOUVER TRIM KIT Not Shown LT32B Brushed Brass LT32P Platinum DEFLECTION HOOD...

Page 41: ..._____ _____________________________________________________ _____________________________________________________ _____________________________________________________ ________________________________...

Page 42: ..._____ _____________________________________________________ _____________________________________________________ _____________________________________________________ ________________________________...

Page 43: ..._____ _____________________________________________________ _____________________________________________________ _____________________________________________________ ________________________________...

Page 44: ...originalfactoryreplacementparts Failuretouseoriginalfactoryreplacementpartsvoidsthiswarranty Travel handling transportation diagnostic material laborandincidentalcostsassociatedwithwarrantyrepairs unl...

Reviews: