background image

11

Unconfined Space

  An  unconfined  space  has  a  minimum  total  air  volume  of 

50  cu.ft.  (cubic  feet)  for  each  1,000  Btu/Hr  input  rating  of  all 

appliances in the total space (cu.ft. = length x width x height 

of  space).  Include  adjoining  rooms  only  if  there  are  doorless 

passageways or ventilation grills between the rooms. If the Btu 

per  50  cu.ft.  is  less  than  1,000  Btu/Hr,  then  fresh  air  will  be 

provided by the natural air flow into the house.

Confined Space

  A confined space has an air volume of less than 50 cu.ft. for 

each 1,000 Btu/Hr input rating of all appliances in the space (cu.

ft. = length x width x height of space). Include adjoining rooms 

only  if  there  are  door  less  passageways  or  ventilation  grills 

between the rooms.

Determining Total Air Volume

  Use  this  work  sheet  to  determine  if  you  have  a  confined 

or unconfined space. The space to be considered includes not 

only the room in which you will install the fireplace but also any 

adjoining  rooms  with  ventilation  grills  between  them  or  door 

less passageways.

1.  Determine the total volume of your space

  L x W x H = _______ cu.ft.

  Example: Space size = 20 ft. long x 20 ft. wide x 8 ft. high 

(ceiling height) = 3,200 cu.ft.

  If  adjoining  ventilation  to  adjoining  room  is  supplied  with 

grills or openings, add the volume of these rooms to the total 

volume of the space.

2.  Divide  the  space  volume  by  50  cu.ft.  to  determine  the 

maximum Btu/Hr the space can support.

  _______ cu.ft. (volume of space)

  50 cu ft. = (Maximum Btu/Hr the space can support)

  Example: 3200 cu ft. (Volume of space) / 50 cu. Ft. = 64.0 or 

64,000 (maximum Btu/Hr the space can support.)

3.  Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace 

  _______ Btu/hr

Gas water heater* 

  _______ Btu/hr

Gas furnace 

 

  _______ Btu/hr

Vented gas heater 

  _______ Btu/hr

Gas fireplace logs 

  _______ Btu/hr

Other gas appliances*    _______ Btu/hr

 

Total = 

  _______ Btu/hr

Example: 

Gas water heater 40,000 Btu/hr 

       

Vent-free fir36,000 Btu/hr

       

 

Total = 76,000 Btu/hr

* Do not include direct-vented gas appliances. Direct vent draws 

combustion air from the outdoors and vents to the outdoors.

4.  Compare the maximum Btu/Hr the space can support with 

the actual amount of Btu/Hr used.

  _________ Btu/Hr (maximum the space can support)

  _________ Btu/Hr (actual amount of Btu/Hr used)

  Example:

  64,000 Btu/Hr (maximum the space can support)

  76,000 Btu/Hr (actual amount of Btu/Hr used)

  The space in the previous example was a confined space 

because the actual Btu/Hr used was more than the maximum 

Btu/Hr the space could support.  If you find you have a Confined 

Space, you must provide additional fresh air. Your options are 

as follows:

a) Re-work worksheet, adding the space of an adjoining room 

that may not have qualified for the extra volume. If the extra 

space  provides  enough  volume  to  convert  the  area  to  an 

unconfined  space,  remove  door  to  adjoining  room  or  add 

ventilation grills between rooms.

b) Vent room directly to the outdoors.
c)  Install  a  lower  Btu/Hr  gas  log  (if  lower  Btu/Hr  size  makes 

room unconfined).

If the actual Btu/Hr used is less than the maximum Btu/Hr the 

space can support, the space is an unconfined space. You will 

need no additional fresh air ventilation.

WARNING

:

  If  the  area  in  which  the  heater  may  be  operated 

is smaller than that defined as an unconfined space, provide 

adequate combustion and ventilation air by one of the methods 

described in the National Fuel Gas Code, ANSI Z223.1 Section 

5.3 or applicable local codes.

Local  codes  may  have  stricter  definitions  for  confined  space 

and/or  for  unusually  tight  construction.  Installing  our  optional 

outside air kit may allow the space to be classified as not being 

unusually tight or being an unconfined space. Check you local 

codes.

IMPORTANT

:

  Do  not  provide  openings  for  inlet  or  outlet  air 

into an attic if the attic has a thermostat-controlled power vent. 

Heated air entering the attic will activate the power vent.

Summary of Contents for Masonry MM39

Page 1: ...and approved by PFS under ANSI Z21 91 for use with any ANSI Z21 11 2 approved gas logs FORUSEONLYWITHALISTEDGAS FIREDUNVENTED DECORATIVE ROOM HEATER NOT TO EXCEED 40 000 BTU HR DO NOT BUILD A WOOD FI...

Page 2: ...WITH ANSI Z21 91 2007 VENTLESS FIREBOX ENCLOSURES FOR GAS FIRED UNVENTED DECORATIVE ROOM HEATERS FOR USE WITH LISTED ANSI Z21 11 2 UNVENTED DECORATIVE ROOM HEATERS NOT TO EXCEED 40 000 BTU HR 0 10 NO...

Page 3: ...d Diagram 5 9 12 2 7 1 3A 2X 2X 3X 7X 2X 8X 3 6 11 Warning Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may re...

Page 4: ...ireplace Parts List ITEM P N DESCRIPTION QTY 1 MFP39 1 MFP44 1 MFP49 1 HEARTH Left or Right 2 2 MFP39 2 MFP44 2 MFP49 2 REAR WALL 4 3 MFP39 3 MFP44 3 MFP49 3 SIDE WALL 7 3A MFP39 3A MFP44 3A MFP49 3A...

Page 5: ...erve as a primary heat source rather the fireplace was expressly created as a supplemental source of heat The Grand Meridian Fireplace is Designed for Use Only with any Vent free decorative gas log se...

Page 6: ...ace if not enough fresh air is available See Air for Combustion and Ventilation page 8 If the fireplace keeps shutting off see appliance manufacturers troubleshooting instructions 9 Do not run firepla...

Page 7: ...ian fireplace Check with the local jurisdiction before you get started Supporting Floor Systems Floor Framing It is important to take into consideration that the load for the Grand Meridian Fireplace...

Page 8: ...dian Fireplace must be considered as additional dead load that will have to be supported by the floor framing Additional floor joists or I joists may be required as determined by the licensed design p...

Page 9: ...d structural members having a moisture content of less than 16 per cent at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted for th...

Page 10: ...designed to be custom finished with facing trim and mantle to be an owner option However all such trim material must meet standard fireplace code requirements Non combustible facing material must be...

Page 11: ...he house to operate You must provide adequate fresh air for these appliances This will insure proper venting of vented fuel burning appliances Non combustible Flex Hose Figure 16 Exterior Providing Ad...

Page 12: ..._ Btu hr Total _ _______ Btu hr Example Gas water heater 40 000 Btu hr Vent free fireplace 36 000 Btu hr Total 76 000 Btu hr Do not include direct vented gas appliances Direct vent draws combustion ai...

Page 13: ...prior to assembly This will minimize shrinkage and cracks developing in the joint areas Best way to accomplish this is with a bucket of water and a large sponge Dip sponge into water and apply a liber...

Page 14: ...28 Apply mortar between joints 12 inch rebar Mix a batch of mortar and prepare Right Side Hearth bottom 2 surface to be bonded as shown in Figure 18 Figure 18 1 2 AWAY FROM EDGES 1 2 MORTAR BEAD TYPIC...

Page 15: ...rebar to all 8 cells as shown in Figure 22 The rebar should enter the holes in the Hearth and lie adjacent to the 12 rebar secured in subfloor Then fill cells with approx 2 cu ft Ready Mix Concrete F...

Page 16: ...Fuel Gas Code ANSI Z223 1 This gas pipe provision must only be connected to an approved vent free gas log heater certified to ANSI Z21 11 2 heater standard Check local building codes for specific pip...

Page 17: ...smells created from the heater and fireplace curing We suggest operating the heater for several 30 minute intervals allowing the fireplace to cool for an hour in between This will allow any moisture i...

Page 18: ...ncrete slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MI...

Page 19: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Page 20: ...components FMI PRODUCTS LLC is not responsible for misuse or mishandling of component parts Nothing in this warranty makes FMI PRODUCTS LLC or any entity thereof liable in any respect for any injury...

Reviews: