background image

9

Clearances

The Importance of Clearances

Warning to the structural engineer and/or building contractor: 

It  is  your  responsibility  to  be  certain  that  the  Grand  Meridian 

Fireplace can be properly supported by the combustible floor 

system  on  which  the  fireplace  will  rest.  Be  advised  that  this 

engineering  equation  will  be  in  addition  to  any  live  or  dead 

weights that the floor has to carry.

Clearances to Combustibles

Nothing  is  more  important  than  paying  strict  attention  to 

giving  clearance  between  fireplace  surfaces  and  surrounding 

“combustibles” the most common of which are:

Drywall

• 

Wood flooring

• 

Plywood sub-flooring

• 

Framing materials

• 

Particle board

• 

Mill board

• 

Plywood paneling

• 

Required Clearances are:

Unit front, sides, rear: ..........................................0"
Combustible Floor:  .............................................0"
Combustible Sheathing above opening top:  .......8" (200 mm)
Sheathing or trim to opening sides:  ....................8" (200 mm)
Mantle above opening:  .......................................12" (300 mm)
Opening to sidewall:  ...........................................24" (500 mm)
Insulation from firebox:  .......................................0"

 

The Grand Meridian Vent-Free fireplace may be installed 

at  “zero  clearance”  to  plywood  sheathing  and  to  uninsulated 

wood framing members at the unit bottom, sides, rear and top 

when used for enclosing any listed vent-free gas-fired log set 

with maximum heat input ratings up to 40,000 Btu/hr. However, 

when a Vent-Free fireplace is to be installed on carpeting, wood 

flooring, or any combustible material other than tile or concrete

the  Vent-Free  fireplace  shall  then  be  installed  on  a  metal  or 

wood platform extending the full width and depth of the Vent-

Free fireplace.

Clearance to Combustible Trim:

 

Grand  Meridian  Vent-Free  Fireplaces  are  designed  to  be 

custom  finished  with  facing  trim  and  mantle  to  be  an  owner 

option.  However,  all  such  trim  material  must  meet  standard 

fireplace code requirements.

 

Non-combustible  facing  material  must  be  applied  to  a 

minimum of eight inches (8”) beyond the sides of the finished 

opening of the Vent-Free fireplace and non-combustible facing 

material must cover a minimum of twelve inches (12”) above 

the finished opening of the installed unit.

Figure 11

1-1/2”

8” MIN

NON-

COMBUSTIBLE 

FACIA

Figure 12

1-1/2”

12” MIN

NON-COMBUSTIBLE 

FACIA

 

Clearance to combustible trim are those distances required 

to ensure that combustible mantle and facing material will not 

be exposed to excessive heat while the unit is operating.
 

These  clearances  should  be  adequate  to  prevent 

discoloration or warping of trim facings due to heat. However, 

circumstances unique to each installation create variables that 

may be beyond the scope of this manual. Therefore be sure 

to follow gas log appliance manufacturer’s explicit installation 

instructions  regarding  all  minimum  trim  facing,  mantle  height 

and side wall clearance requirements.

Figure 13

 

Parts  of  the  combustible  mantle  assembly  located  above 

and  projecting  more  than  one  and  one-half  inches  (1-1/2”) 

inches from the firebox opening shall be kept at least twelve 

inches (12”) from the top of the opening.
 

Mantle shelves with horizontal projection of ten inches (10”) 

from the face of the fireplace must be hel

d to a minimum vertical 

distance  of  twenty  inches  (20”)  from  the  top  of  the  finished 

fireplace opening.

Note

:

  Mantle  height  clearances  may  vary  among  gas  log 

appliance manufacturers or with the use of firebox canopies.
 

Be  sure  to  follow  the  gas  log  appliance  manufacturer’s 

explicit  installation  instructions  for  mantle  height  clearance 

requirements.

Summary of Contents for Masonry MM39

Page 1: ...and approved by PFS under ANSI Z21 91 for use with any ANSI Z21 11 2 approved gas logs FORUSEONLYWITHALISTEDGAS FIREDUNVENTED DECORATIVE ROOM HEATER NOT TO EXCEED 40 000 BTU HR DO NOT BUILD A WOOD FI...

Page 2: ...WITH ANSI Z21 91 2007 VENTLESS FIREBOX ENCLOSURES FOR GAS FIRED UNVENTED DECORATIVE ROOM HEATERS FOR USE WITH LISTED ANSI Z21 11 2 UNVENTED DECORATIVE ROOM HEATERS NOT TO EXCEED 40 000 BTU HR 0 10 NO...

Page 3: ...d Diagram 5 9 12 2 7 1 3A 2X 2X 3X 7X 2X 8X 3 6 11 Warning Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may re...

Page 4: ...ireplace Parts List ITEM P N DESCRIPTION QTY 1 MFP39 1 MFP44 1 MFP49 1 HEARTH Left or Right 2 2 MFP39 2 MFP44 2 MFP49 2 REAR WALL 4 3 MFP39 3 MFP44 3 MFP49 3 SIDE WALL 7 3A MFP39 3A MFP44 3A MFP49 3A...

Page 5: ...erve as a primary heat source rather the fireplace was expressly created as a supplemental source of heat The Grand Meridian Fireplace is Designed for Use Only with any Vent free decorative gas log se...

Page 6: ...ace if not enough fresh air is available See Air for Combustion and Ventilation page 8 If the fireplace keeps shutting off see appliance manufacturers troubleshooting instructions 9 Do not run firepla...

Page 7: ...ian fireplace Check with the local jurisdiction before you get started Supporting Floor Systems Floor Framing It is important to take into consideration that the load for the Grand Meridian Fireplace...

Page 8: ...dian Fireplace must be considered as additional dead load that will have to be supported by the floor framing Additional floor joists or I joists may be required as determined by the licensed design p...

Page 9: ...d structural members having a moisture content of less than 16 per cent at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted for th...

Page 10: ...designed to be custom finished with facing trim and mantle to be an owner option However all such trim material must meet standard fireplace code requirements Non combustible facing material must be...

Page 11: ...he house to operate You must provide adequate fresh air for these appliances This will insure proper venting of vented fuel burning appliances Non combustible Flex Hose Figure 16 Exterior Providing Ad...

Page 12: ..._ Btu hr Total _ _______ Btu hr Example Gas water heater 40 000 Btu hr Vent free fireplace 36 000 Btu hr Total 76 000 Btu hr Do not include direct vented gas appliances Direct vent draws combustion ai...

Page 13: ...prior to assembly This will minimize shrinkage and cracks developing in the joint areas Best way to accomplish this is with a bucket of water and a large sponge Dip sponge into water and apply a liber...

Page 14: ...28 Apply mortar between joints 12 inch rebar Mix a batch of mortar and prepare Right Side Hearth bottom 2 surface to be bonded as shown in Figure 18 Figure 18 1 2 AWAY FROM EDGES 1 2 MORTAR BEAD TYPIC...

Page 15: ...rebar to all 8 cells as shown in Figure 22 The rebar should enter the holes in the Hearth and lie adjacent to the 12 rebar secured in subfloor Then fill cells with approx 2 cu ft Ready Mix Concrete F...

Page 16: ...Fuel Gas Code ANSI Z223 1 This gas pipe provision must only be connected to an approved vent free gas log heater certified to ANSI Z21 11 2 heater standard Check local building codes for specific pip...

Page 17: ...smells created from the heater and fireplace curing We suggest operating the heater for several 30 minute intervals allowing the fireplace to cool for an hour in between This will allow any moisture i...

Page 18: ...ncrete slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MI...

Page 19: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Page 20: ...components FMI PRODUCTS LLC is not responsible for misuse or mishandling of component parts Nothing in this warranty makes FMI PRODUCTS LLC or any entity thereof liable in any respect for any injury...

Reviews: