VENTING INSTALLATION

Continued

10 FOOT RULE

All flue gas outlet chimney terminations must 

extend a minimum of 3 feet in height above the 

highest point where it passes through the roof 

and must be at least 2 feet above the high

-

est point of the roof that is within a horizontal 

distance of 10 feet (see Figure 20).

FINISHING FIREPLACE

Combustible  materials,  such  as  wallboard, 

gypsum board, sheet rock, drywall, plywood, 

etc. may make direct contact with sides and top 

around the fireplace face. It is important that 

combustible materials do not overlap the face 

itself. Brick, glass, tile or other noncombustible 

materials may overlap the front face provided 

they do not obstruct essential openings like 

louvered  slots  or  any  other  opening.  When 

overlapping  with  a  noncombustible  facing 

material, use only noncombustible mortar or 

adhesive.

24" Min.

24" Min.

18" 

Min.

Typ.

Figure 19 - Multiple Chase Installation

10'

2' Min.

10'

3' Min.

2' Min.

3' Min.

Level of 

Flue Gas 

Outlet

Figure 20 - 10 Foot Rule

Terminations/Spark Arrestor

The fireplace system must be terminated with 

the listed round top or chase terminations. In 

any case, refer to the installation instructions 

supplied with the termination.

 CAUTION: Do not seal open

-

ings on the rooftop flashing. Fol

-

low the installation instructions 

provided with the termination 

being used.

RTL-12D

Level of 

Flue Gas 

Outlet

Stainless 

Inner Flue 

Pipe

Waterproof 

Caulking

Storm 

Collar

Flashing

Underlap 

Shingles

Figure 18 - Termination

Overlap 

Shingles (Top 

and Sides of 

Flashing Base)

CHASE INSTALLATIONS

Instructions  for  chase  installations  are 

included  with  the  chase  style  termination 

chosen. In a multiple chase installation, be 

sure to provide adequate distance between 

terminations to prevent smoke spillage from 

one termination to another. We suggest that 

terminations be separated at least 24", center 

to center and stacked at a vertical height dif

-

ference of 18" (see Figure 19).

Note: If a decorative shroud is to be installed, 

contact the manufacturer for specifications.

Secure 

Termination 

to Outer 

Pipe with 3 

Screws

Summary of Contents for G36A Series

Page 1: ...with a vent free gas log heater approved to ANS Z21 11 2 standard This wood burning fireplace complies with UL127 CAN ULC S610 M87 standard as a FACTORY BUILT FIREPLACES FOR CANADA The authority havi...

Page 2: ...cation in fireplace and refer to fire log warnings and caution markings on packaging prior to use Thisfireplaceisnotintendedtobe used as a substitute for a furnace to heat an entire home Use for suppl...

Page 3: ...S 12 EACH SIDE COMBUSTIBLE WALL BOARD NO COMBUSTIBLE MATERIAL ON FACE MINIMUM 12 TO PERPENDICULAR SIDEWALL HEARTH EXTENSION 74 X 20 1 CHIMNEY AIRSPACE CLEARANCE TO COMBUSTIBLE MATERIAL OUTSIDE AIR 36...

Page 4: ...GAS LINE KNOCKOUTS 12 EACH SIDE COMBUSTIBLE WALL BOARD NO COMBUSTIBLE MATERIAL ON FACE MINIMUM 18 TO PERPENDICULAR SIDEWALL HEARTH EXTENSION 66 X 20 2 CHIMNEY AIRSPACE CLEARANCE TO COMBUSTIBLE MATERIA...

Page 5: ...OMBUSTIBLE MATERIAL COMBUSTIBLE WALL BOARD NO COMBUSTIBLE MATERIAL ON FACE 0 TO BOTTOM OUTSIDE AIR 11 2 AIR SPACE BACK AND SIDES GAS LINE KNOCKOUTS 12 EACH SIDE MINIMUM 18 TO PERPENDICULAR SIDEWALL HE...

Page 6: ...nges Figure 5 Corner Installation SELECTING LOCATION To determine the safest and most efficient location for the fireplace you must take into consideration the following guidelines 1 The location must...

Page 7: ...bustible material see Figure 6 WARNING Hearthextension is to be installed only as shown in Figure 6 FIREPLACE INSTALLATION Continued Figure 6 Hearth Extension Seal Gap Fireplace Front Ember Protector...

Page 8: ...ns Figure 8 Outside Air Kit Secure to Collars with Metal Tape Screws or Straps Min of 1 4 x 20 in size Air Inlet Location Must Allow For Bushes or Snow Vent Hood Required for Wall Installation Air Inl...

Page 9: ...ipe sections are locked to gether When installing double wall snap lock chimney together it is important to assure the joint between the chimney sections is locked Check by pulling chimney upward afte...

Page 10: ...igure 14 Firestop Spacer with Attic Space Above Ceiling Existing Ceiling Frame Firestop Spacer Screws or Staples Min of 8 Firestop Spacer Screws or Staples Min of 8 PENETRATING ROOF To maintain a 1 36...

Page 11: ...tom Overlap Shingles Top and Sides Only Figure 16 Flashing Installation FLASHING INSTALLATION V6F 10DM OR V12F 10DM Determine the flashing to be used with the roof opening chart Slide flashing over pi...

Page 12: ...2 Min 10 3 Min 2 Min 3 Min Level of Flue Gas Outlet Figure 20 10 Foot Rule Terminations Spark Arrestor The fireplace system must be terminated with the listed round top or chase terminations In any c...

Page 13: ...y should be postioned a distance apart as shown in Figure 21 4 Install rear refractory panel This panel has a top and bottom To determine which is which match up the pattern on the rear panel with the...

Page 14: ...la tion from gas line conduit sleeve Save insulation for reuse Replace screws 3 Run a 1 2 black iron gas line into fireplace through the rear at gas line conduit sleeve if usingaraisedplatform addheig...

Page 15: ...ce must comply with the Standard for Decorative Gas Appliance for Installation in Solid Fuel Burning Fireplaces ANS Z21 60 or Z21 84 and shall also be installed in accordance with the National Fuel Ga...

Page 16: ...Installing Bi Fold Doors Spring Clip Insert Pin into Spring Clip Pivot Hole Insert Bottom Pivot Pin into Hole Fold Door and Slide Top Pins Into Track Figure 29 Adjusting Bi Fold Doors INSTALLING GLAS...

Page 17: ...and a gradual temperature rise to 550 F which is more than a normal fire will generate Such materials as pitch wax laden logs very dry mill end lumber and large amounts of paper or cardboard boxes can...

Page 18: ...www fmiproducts com 124379 01A 18 PARTS MODELS V G36 42 50 SERIES AND V J36 42 50 SERIES 1 21 20 5 6 7 10 9 11 12 13 16 17 15 14 8 24 23 3 25 18 2 22 19 4...

Page 19: ...e 2 15 21171 Gas Conduit Cover 4 16 109752 01 Conduit One 2 17 109752 02 Conduit Two 2 18 Heat Shield Support 1 19 123298 02 Ash Box Assembly 1 20 Inner Dome Assembly 1 21 Smoke Shield 1 22 Damper Con...

Page 20: ...www fmiproducts com 124379 01A 20 PARTS MODELS MODELS V G36 42 50 SERIES AND V J36 42 50 SERIES Picture may vary from actual 1 2 5 3 4 6 6...

Page 21: ...1 125841 02 Right Herringbone 50 Red 1 3 116081 02 Left Stacked 36 Red 1 116086 02 Left Herringbone 36 Red 1 125833 02 Left Stacked 42 Red 1 125836 02 Left Herringbone 42 Red 1 125839 02 Left Stacked...

Page 22: ...116081 01 Left Stacked 36 Natural White 1 116086 01 Left Herringbone 36 Natural White 1 125833 01 Left Stacked 42 Natural White 1 125836 01 Left Herringbone 42 Natural White 1 125839 01 Left Stacked 5...

Page 23: ...tion or troubleshooting If so contact FMI PRODUCTS LLC at 1 866 328 4537 When calling please have your model and se rial numbers of your fireplace ready You can also visit our web site at www fmiprodu...

Page 24: ...FLASHING V6F 10DM 0 to 6 12 Pitch V12F 10DM 6 12 to 12 12 Pitch ACCESSORIES Continued SQUARE CHASE TOP TERMINATION STL 12D AND STL 12DMP BLACK ROUND TOP TERMINATIONS RLT 12D AND RLT 12HT STORM COLLAR...

Reviews: