T+/T+PRO English Instruction Sheet
Page 15
Maintenance
W
Caution
Do not use abrasives or solvents on the Tester.
Clean the case with a damp cloth and mild detergent.
Replacing the Batteries
Perform a self test to determine the charge state of the batteries
on T+ Testers. The self test will not work with dead batteries. On
T+ PRO Testers, the low battery icon (
B
) on the LCD indicates
that the batteries need to be replaced.
XW
Warning
To avoid possible electric shock or personal injury:
•
Disconnect test leads from any electrical source
before opening the battery compartment.
•
Do not operate the Tester with the battery door or
portions of the cover removed or loosened.
1.
Turn the Tester over and use a flat-head screwdriver to
loosen the battery door screw and remove the door.
2.
Replace the batteries with two new AAA alkaline batteries.
3.
Reattach the battery compartment door and reinstall the
screw.
Specifications
Temperature:
Operating: -10
°
C to 55
°
C (14
°
F to 131
°
F)
Storage: -30
°
C to +60
°
C (-22
°
F to +140
°
F)
Relative Humidity: 0
°
C to 30
°
C (32
°
F to 86
°
F) 90 %
30
°
C to 40
°
C (86
°
F to 104
°
F) 75 %
40
°
C to 50
°
C (104
°
F to 122
°
F): 45 %
Altitude:
Operating: 2,000 m
Storage: 10,000 m
Battery Type/Life: AAA (2); 40 hours
Shock, Vibration: Sinusoidal vibration per MIL-PRF-28800F for a
Class 2 instrument
Safety:
ANSI/ISA S82.02.01, CSA C22.2-1010.1, IEC 61010-1
to 1000 V CAT III/600 V CAT IV; Pollution Degree II
AC Bandwidth:
45 Hz to 66 Hz
Maximum Input
Voltage Between
Terminal and
Earth Ground:
Maximum working voltage 1000 V ac or dc.
Maximum measurable voltage 600 V ac or dc. This will
be displayed on the LED and the LCD (T+ PRO).
Duty Cycle:
Indefinitely for voltages up to 240 V.
For voltages between 240 V to 600 V the duty cycle is
30 seconds on / 300 seconds off. For voltages above
240 V the Tester must connect to a voltage source
1.800.868.7495