![Fluke 7312 User Manual Download Page 74](http://html.mh-extra.com/html/fluke/7312/7312_user-manual_2309393074.webp)
14
Troubleshooting
This section contains information on troubleshooting, CE Comments, and a
wiring diagram. This information pertains to a number of bath models and cer-
tain specifics may not pertain to your model.
14.1
Troubleshooting
In the event that the instrument appears to function abnormally, this section
may help to find and solve the problem. Several possible problem conditions
are described along with likely causes and solutions. If a problem arises, please
read this section carefully and attempt to understand and solve the problem. If
the probe seems faulty of the problem cannot otherwise be solved, contact an
Authorized Service Center (see Section 1.3) for assistance. Be sure to have the
model number, serial number, and voltage of your instrument available.
Problem
Causes and Solutions
The bath does not turn
on and the display re-
mains blank
If a fault condition exists upon application of power, the bath will not energize.
The bath needs to be plugged in to the line voltage for at least 2 minutes before
turning power on. This is only necessary for the first time that the bath is ener-
gized or when it is moved from one location to another.
If a high or low voltage condition exists for longer than 5 seconds, the compres-
sor is de-energized and the “Mains Out of Range” light on the back panel illumi-
nates indicating a fault condition.
Re-energization is automatic upon correction of the fault condition and after a
delay cycle of about 2 minutes.
High and low voltage protection limits at 115 VAC:
Voltage Cutout: ±12.5% (101 – 129 VAC)
Voltage Cutin: ±7.5% (106 – 124 VAC)
High and low voltage protection limits at 230 VAC:
Voltage Cutout: ±12.5% (203 – 257 VAC)
Voltage Cutin: ±7.5% (213 – 247 VAC)
See the
Caution
in the front of this manual for additional information.
Testing the Line Voltage
– If the power line voltage is too low (90% of the
compressor’s rated voltage), the compressor could be damaged. Place a DVM
in the supply line on the wall that feeds the bath. Measure the line voltage under
load (with the bath on). If the line voltage is low or marginal, disconnect any
other devices that are using the same line. Alternately, move the bath to a loca-
tion where the supply voltage is good. If none of these are possible, contact an
electrician to re-route the correct power. If necessary, you can inspect the oper-
ation of the line monitor by opening the electronics cover. See the
Caution
at
the front of this manual for a summary of the ICM491 operation. Hart does not
recommend adjustment of the operating voltage in order to use the instrument.
Instead, an electrician should be consulted to alleviate the problem with the
power source.
75
14 Troubleshooting
Troubleshooting
Summary of Contents for 7312
Page 2: ......
Page 3: ......
Page 18: ......
Page 29: ...25 6 Bath Use Triple Point of Water Cell Maintenance Fluid Level in Bath Figure 3 Fluid Level ...