HF197AEN_v0501_04
Page 25
4.4.3. TERMINAL
CONNECTORS
For Intrinsically Safe applications: read chapter 5.
The following terminal connectors are available:
Fig. 10: Overview of terminal connectors standard configuration F197-A and options.
REMARKS: TERMINAL CONNECTORS:
Power Supply: Terminal GND- 01- 02 only available with type PD / PF or PM:
T
YPE
SENSOR SUPPLY
T
erminal
backlight
T
YPE
AA
T
YPE
AU
Type
O
A
Type
O
R
GND
01
02
PD
8-24V AC
8,2-12-24V max. 50mA
AC AC
◊
◊
◊ ◊
PD
8-30V DC
8,2-12-24V max. 50mA
L-
L+
◊
◊
◊ ◊
PF
24V AC
±
15%
8,2-12-24V max. 400mA
AC AC
◊
◊
◊
◊
PF
24V DC
±
15%
8,2-12-24V max. 400mA
L-
L+
◊
◊
◊
◊
PM
115-230V AC
±
15%
8,2-12-24V max. 400mA EARTH
AC
AC
◊
◊
◊ ◊ ◊
Note PD
do not use a AC autotransformer (Spartrafo) without a galvanic isolation.
Note PF / PM
The total consumption of the sensors and outputs may not exceed 400mA@24V
◊
=option
For Intrinsically Safe applications: read chapter 5.
7
8
ANALOG
OUTPUT
TYPE AA / AB /
AI / AP/ AU
I
R2
GND
3
1
4
POWER SUPPLY:
TYPE
PD / PF / PM
N
L1
R2
2
I
HIGH ALARM
OUTPUT R 2
TYPE
OA / OR / OT
9
10
SENSOR SIGNAL
ANALOG INPUT
TYPE A
11
+
6
5
R1
R1
LOW ALARM
OUTPUT R 1
TYPE
OA / OR / OT
I