![Fluidwell F113-A Manual Download Page 45](http://html1.mh-extra.com/html/fluidwell/f113-a/f113-a_manual_2309007045.webp)
FW_F113A_v1901_02_EN.docx
Page 45
PDU
ADDRESS
REGISTER
VARIABLE
FLOWMETER
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 98
[h] 0x062
40099
formula
1
r/w
uint16 0=linear
1=square root
[d] 99
[h] 0x063
40100
filter
1
r/w
uint16 1...99
[d] 100
[h] 0x064
40101
cut-off
1
r/w
uint16 0...999
Representation: 0.0
–
99.9%
[d] 102
[h] 0x066
40103
calibrate low
1
r/w
uint16 0=cal set
1=calibrate
2=default
[d] 103
[h] 0x067
40104
calibrate high
1
r/w
uint16 0=cal set
1=calibrate
2=default
PDU
ADDRESS
REGISTER
VARIABLE
ANALOG OUTPUT
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 112
[h] 0x070
40113
analog output
1
R/W
uint16
0=disable 1=enable
[d] 113
[h] 0x071
40114
minimum rate
2
R/W
uint32
0…9999999
Representation: unit, time, decimals
depending on variables 48, 49, 50
[d] 116
[h] 0x074
40117
maximum rate
2
R/W
uint32
0…9999999
Representation: unit, time, decimals
depending on variables 48, 49, 50
[d] 119
[h] 0x077
40120
cut off percentage
1
R/W
uint16
0...99
Representation: 0.0
–
9.9%
[d] 120
[h] 0x078
40121
tune minimum rate
1
R/W
uint16
0...9999
[d] 122
[h] 0x07A
40123
tune maximum rate
1
R/W
uInt16
0...9999
[d] 127
[h] 0x07F
40128
filter
1
R/W
uint16
1...99
PDU
ADDRESS
REGISTER VARIABLE
RELAYS
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 135
[h] 0x087
40136
relay 1
1
r/w
uint16 0=off
1=LL
2=LO
3=HI
4=HH
5=all
6=pulse
[d] 136
[h] 0x088
40137
relay 2
1
r/w
uint16 0=off
1=LL
2=LO
3=HI
4=HH
5=all
6=pulse
[d] 137
[h] 0x089
40138
relay 3
1
r/w
uint16 0=off
1=LL
2=LO
3=HI
4=HH
5=all
6=pulse
[d] 138
[h] 0x08A
40139
relay 4 (optional)
1
r/w
uint16 0=off
1=LL
2=LO
3=HI
4=HH
5=all
6=pulse
[d] 128
[h] 0x080
40129
pulse width
1
r/w
uint16 0.000
–
9.999 seconds (0=off)
[d] 133
[h] 0x085
40134
decimals
1
r/w
uint16
0 … 3
[d] 130
[h] 0x082
40131
amount
2
r/w
uint32 0.001 - 9999999
PDU
ADDRESS
REGISTER
VARIABLE
COMMUNICATION
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 144
[h] 0x090
40145
speed (Baudrate)
1
R/W
uint16
0=1200 1=2400 2=4800
3=9600
[d] 145
[h] 0x091
40146
Modbus address
1
R/W
uint16
1…247
[d] 146
[h] 0x092
40147
Modbus mode
1
R/W
uint16
0: ASCII 1: RTU 2: OFF
[d] 247
[h] 0x0F7
40248
Databits
1
r/w
uint16
0=8bits
1=7bits
[d] 248
[h] 0x0F8
40249
Parity
1
r/w
uint16
0=none 1=even