Type AP:
A passive 4-20mA signal proportional to the flow rate is available with this option. When a power
supply is connected but the output is disabled, a 3.5mA signal will be generated.
Max. driving capacity 1000 Ohm. This output does loop power the unit as well.
Fig. 16: Terminal connections - Passive 4-20mA analog output (typical)
Type AU:
A 0-10VDC signal proportional to the flow rate is available with this option.
Max. load 10mA @ 10VDC. (Requires power supply type PD / PF / PM).
Fig. 17: Terminal connections - Active 0-10V analog output (typical)
Terminal 09-11: Type A
– Flowmeter input (general)
The F113-A requires a (0)4-20mA flowmeter signal which will be processed 4 times a second with a
16 bits accuracy. The input is not isolated.
For Intrinsically safe applications (without input loop power): please read chapter 5.
Fig. 18: Terminal connections - Analog signal input (typical)
Terminal 09-10: Type A-PL
– Flowmeter input / power supply
:
The F113-A-PL requires a 4-20mA flowmeter signal which has a double function:
The signal will be processed 4 times a second with a 16 bits accuracy and the unit will be powered
from the sensor signal (input loop powered). The input is not isolated and not intrinsically safe.