HF110AEN_v0501_04
Page 25
4.4.2.
VOLTAGE SELECTION SENSOR SUPPLY
For Intrinsically Safe applications: read chapter 5.
Type PL
Not applicable as the F110-A-PL is powered by the sensor signal.
Type PB / PC / PX (AP) - battery powered and output loop-powered applications:
Terminal 11 provides a limited supply voltage of 3.2 V DC for the signal output of the flowmeter. This
is not suitable to power analog sensors.
Type PD / PF / PM: Sensor supply: 1.2 - 3.2V - 8.2V - 12V or 24 V DC:
With this option, a real power supply for the sensor is available. The flowmeter can be powered with
8.2 - 12 or 24 V DC.
Total power consumption PD: max. 50mA@24V and PF / PM: max. 400mA@24V.
The voltage is selected with the three switches inside the enclosure.
Warning: be sure that all the leads to the terminals are disconnected from the unit when the
internal plastic protection cover has been removed !
HIGH VOLTAGE 400V !! NEVER connect the mains power supply to the unit when the plastic
protection cover has been removed !!!
First, remove the terminal strip(s) after which the internal plastic cover can be removed. The
switches are located in the top left corner (type PD) or on the right hand (type PF / PM) as indicated:
Fig. 8: Switch setting sensor supply voltage.
Switch positions
SENSOR
A
SENSOR
B
VOLTAGE SELECTION
SWITCH
1
VOLTAGE
SWITCH
3
SWITCH
4
VOLTAGE
internal
3.2 V DC
on
on
8.2 V DC
external switch
3+4
on
off 12
V
DC
off
off 23
V
DC
Function switch 1:
voltage selection sensor A - terminal 11.
Function switch 2:
not
available.
Function switch 3+4:
the combination of these switches determine the voltage as indicated.
Do move switch 1 and / or switch 2 to the OFF position to enable the
selected voltage with switch 3+4.