The large 17mm digits can be set to display total or flowrate.
When "total" is selected, both total and flowrate are displayed
simultaneously.
When "flowrate" is selected, only flowrate will be displayed with it’s
measuring unit while total will be displayed after pressing SELECT.
4 - POWER MANAGEMENT
When used with the internal battery option, the user can expect reliable measurement over a long
period of time. The F110-A has several smart power management functions to extend the (optional)
battery life time significantly. Two of these functions can be set:
LCD NEW
41
The calculation of the display-information influences the power
consumption significantly. When the application does not require a fast
display update, it is
strongly advised
to select a slow refresh rate.
Please understand that NO information will be lost; the signal will be
processed and the output signals will be generated in the normal way.
The following can be selected:
Fast - 1 sec - 3 sec - 15 sec - 30 sec - off.
Example 3:
Battery life-time
battery life-time with a FAST update: about 3 years.
battery life-time with a 1 sec update: about 7 years.
Note:
after a button has been pressed by the operator - the display
refresh rate will always switch to FAST for 30 seconds. When "OFF" is
selected, the display will be switched off after 30 seconds and will be
switched on as soon as a button has been pressed.
BATTERY-MODE
42
The unit has two modes: operational or shelf.
After "shelf" has been selected, the unit can be stored for several years; it
will not process the signal, the display is switched-off but all settings and
totals are stored. In this mode, power consumption is extremely low.
To wake up the unit again, press the SELECT-key twice.